background image

 

On the top of the furnace is a 12” collar. Determine where you will attach the 12” pipe to the 
plenum or duct of your present furnace. Pick a spot where you have to use the least amount of 
pipe to connect the two furnaces. This will help transfer the maximum amount of heat to your duct 
system. Also do not downsize this pipe as this will decrease air flow and performance of your  
 
Hitzer Furnace. Restricting can also cause damage to your furnace by trapping to much of the 
produced heat. If a central air conditioning coil is installed in the central furnace this connection 
must be made above the coil.  

Cut the 12” hole in your picked spot. Attaching a 12” takeoff collar, 

like on the top of the Hitzer furnace, to this hole will facilitate a better hookup. A takeoff collar is 
available at the same places where you get the 12” duct pipe. Assemble the duct pipe connecting 
the two systems. Sheet metal screws should be used to secure each joint.  Each joint can be 
wrapped with aluminum heat resistant tape for an air tight seal. If a backflow damper is used it 
must be installed in the plenum of your existing furnace. Do not install in the outlet of the Hitzer 
furnace as this will trap the heat in a power outage. 
  

NOTE:  

It is always best to run the supply duct up In the case of a power outage the stove can still 

be utilized. With the supply duct up, this will allow gravity heat to still rise into the system. If you  
have the optional filter housing installed, remove filters during a power outage. This will greatly 
improve the air movement up through the system. There are also cover plates along both sides at 
the bottom of the furnace. These can also be removed during a power outage to increase the 
natural air flow through the system. 
 
Next connect the blower and optional filter housing if applicable. The blower and filter housing 
attach to the flange on the rear of the furnace with the four bolts provided. The wires on the blower 
are then fed into the junction box where the prewired thermostat and power cord attached. 
Connect one blower wire to the open wire from the thermostat with provided wire nut. Connect the 
other blower wire to the open wire of the power cord with provided wire nut. Replace cover on the 
junction box. 
 
When setting up the furnace with blower and optional filter housing they must be assembled 
together and be fastened to blower flange on back of the furnace. Both sides of the filter box are 
removable. Remove the screw from the center bottom of the housing and slide the side up and 
out. 

If you are not running cold air return ducts to the furnace replace these sides with two 20” x 

20” x 1” standard furnace filters. Slide them down in place of the metal sides and replace the lid. If 
connecting cold air return ducts to the furnace cut the holes in the filter housing sides. Takeoff 
collars can be installed to facilitate ease of attaching the returns. Reassemble the sides back into 
the filter housing and slide filters down into the slots in the sides. Attach the return ducts to the 
takeoff collars. Filters should checked periodically and change at least monthly. Dirty filters will 
restrict the air flow causing a reduction in the performance of your Hitzer furnace. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for 55 FA

Page 1: ...DAMAGE PERSONAL INJURY OR DEATH FURNACE SURFACES MAY BECOME HOT WHILE IN OPERATION HIGH FURNACE TEMPERATURES MAY IGNITE CLOTHING OR FLAMMABLE MATERIAL FOR USE OF SOLID FUEL COAL ONLY OTHER FUEL SOURC...

Page 2: ...FM output of each furnace You can then get an idea if the ductwork is sized such that the operating static pressure of the two combined will not go over the maximum for either if both operate at the s...

Page 3: ...d by a chimney professional The structural foundation of the chimney and liner is important If existing clay liner is cracked or damaged it is recommended to re line the chimney with a stainless steel...

Page 4: ...urnace should be a minimum of 7 inches in diameter Flue Size Continued The flue size also has a maximum size of inches in order to sustain the desired draft For an interior chimney the flue and chimne...

Page 5: ...FOR SOLID FUEL VENTING IS UNSAFE AND PROHIBITED BY THE NATIONAL FIRE PROTECTION ASSOCIATION CODE III Location of Furnace and Installation WARNING THE INSTALLATION OF THESE STOVES MUST COMPLY WITH STA...

Page 6: ...ng concealed spaces or enter the chimney in the attic If connection is made through a combustible wall a listed and approved wall thimble pass through must be used following the manufacturer s instruc...

Page 7: ...all or Ceiling 18 Unit must be placed on a noncombustible floor Hot Air Supply Duct Hookup With the furnace now in place and the flue connector connected to the chimney it is time to connect the suppl...

Page 8: ...ill greatly improve the air movement up through the system There are also cover plates along both sides at the bottom of the furnace These can also be removed during a power outage to increase the nat...

Page 9: ...ation formats Note these illustrations reflect typical installations and are for design purposes only Illustrations and diagrams are for informational purposes only These diagrams are not drawn to sca...

Page 10: ......

Page 11: ...to operate other than as intended Do not have hot air from gas or oil furnace flow downward into the Hitzer Furnace and flow out the Hitzer Furnace to existing duct work IV Operation Of Furnace WARNI...

Page 12: ...y load the stove to maximum heating potential Starting An Anthracite Coal Fire Starting an Anthracite coal fire takes time and patience Take several sheets of newspaper crumble into balls and place on...

Page 13: ...t air flow and the ability of the coal to burn When this happens this block of burning coal must be broken up with a poker to restore proper operation Add the coal in a couple of stages however it is...

Page 14: ...However when the stove is turned down and not much heat is needed the thermostat controlling the draft closes The gases now have no oxygen to burn and there is very little air movement through the st...

Page 15: ...EXTREMELY HOT FIRE THE CHIMNEY CONNECTOR AND CHIMNEY SHOULD BE INSPECTED AT LEAST TWICE MONTHLY DURING THE HEATING SEASON TO DETERMINE IF A SOOT BUILD UP HAS OCCURRED IF SOOT HAS ACCUMULATED IT SHOUL...

Page 16: ...till you are ready to use the furnace again in the fall Have the chimney inspected and cleaned if necessary If the optional filter housing is not installed you will need to clean the blower wheel Alwa...

Page 17: ...all be the responsibility of the original purchaser and the said Hitzer Inc shall have the final determination and be the final determiner as to whether or not said component is defective Any labor co...

Page 18: ...order for the above stated limited warranty to be effective and binding upon Hitzer Inc this portion herein must be detached and sent by the original owner to Hitzer Inc to the above stated address wi...

Reviews: