WARNING: BE SURE TO FOLLOW ALL CHIMNEY MANUFACTURER’S 
INSTRUCTIONS.  FAILURE TO FOLLOW INSTRUCTIONS CAN RESULT IN FIRE, 
INJURY, AND EVEN DEATH. 

 

  CAUTION: DO NOT CONNECT THIS UNIT TO A CHIMNEY SERVING ANOTHER 
APPLIANCE.  

 

Flue Requirements: 

It is required to have your chimney inspected and cleaned by a certified 

chimney professional before Hitzer Furnace installation, and at least twice monthly during the 
heating season. If material has accumulated, it should be removed immediately to reduce the risk 
of a chimney fire. If a chimney fire does occur the fire department should be called immediately 
and the draft controls should be closed on the stove. It is also required to have a chimney that is 
built according to the 

manufacturer’s specifications and meet local building codes. 

 

Flue Size:  

The proper flue size is very important.  The proper flue size is essential in order to 

have the correct amount of draft required to operate the Hitzer Stove.  The diameter of the flue 
size including chimney liner should never be less than the diameter of the flue exhaust collar on 
the Hitzer Furnace. The flue size for the 55 furnace should be a minimum of 6 inches in diameter.  
The flue size for the 82 furnace should be a minimum of 7 inches in diameter. 

 
Flue Size (Continued): 

The flue size also has a maximum size of inches in order to sustain the 

desired draft.  For an interior chimney the flue and chimney liner size 

cannot 

be larger than 

times

 the square inches of the flue exhaust collar on the Hitzer stove. For an exterior chimney 

that has at least one side exposed to the exterior of the house the flue and chimney liner 

cannot

 

be more than 

2 times

 the square inches of the flue exhaust collar of the Hitzer Stove.  Also keep 

in mind the warmer the chimney is the better the draft. 
 
Model  Flue Size (Sq. Inch) 

Minimum (Sq. inch) 

Maximum (Sq. Inch) 

Int/Ext 

55 FA 

 

6” 

28 sq. in. 

6” 

28 sq. in. 

 

84 sq. in.  

          interior 

55 FA 

 

6

” 

28 sq. in. 

6” 

28 sq. in. 

 

56 sq. in. 

         exterior 

 
82FA 

 

7

” 

38.5 sq. in.  7

” 

38 sq. in. 

 

115.5 sq. in.            interior 

82FA 

 

7

” 

38.5 sq. in.  7

” 

38 sq. in. 

 

  77 sq. in. 

         exterior 

 
Chimney Height Requirements: 

The minimum 

height of a chimney system for the Hitzer Furnace  
is 15 feet.  The chimney must exceed the roof of a 
house a minimum of 3 feet at any   point of exit.  In 
pitched roof installation the chimney must be 2 feet 
higher than anything within a 10 foot radius of the 
chimney.  It is important to have a chimney draft of 
.03 - .06 It is required to abide by the 
manufacturer’s instructions on class A chimney’s as 
well as local building codes.  
                                                                                     

Note:

  All illustrations are for design                                     

 

 

 

 

  

 

 

                      purposes only.   

  

 

 

 

 

 

 

 

 

 

 

           Actual installations may vary 

 

Summary of Contents for 55 FA

Page 1: ...DAMAGE PERSONAL INJURY OR DEATH FURNACE SURFACES MAY BECOME HOT WHILE IN OPERATION HIGH FURNACE TEMPERATURES MAY IGNITE CLOTHING OR FLAMMABLE MATERIAL FOR USE OF SOLID FUEL COAL ONLY OTHER FUEL SOURC...

Page 2: ...FM output of each furnace You can then get an idea if the ductwork is sized such that the operating static pressure of the two combined will not go over the maximum for either if both operate at the s...

Page 3: ...d by a chimney professional The structural foundation of the chimney and liner is important If existing clay liner is cracked or damaged it is recommended to re line the chimney with a stainless steel...

Page 4: ...urnace should be a minimum of 7 inches in diameter Flue Size Continued The flue size also has a maximum size of inches in order to sustain the desired draft For an interior chimney the flue and chimne...

Page 5: ...FOR SOLID FUEL VENTING IS UNSAFE AND PROHIBITED BY THE NATIONAL FIRE PROTECTION ASSOCIATION CODE III Location of Furnace and Installation WARNING THE INSTALLATION OF THESE STOVES MUST COMPLY WITH STA...

Page 6: ...ng concealed spaces or enter the chimney in the attic If connection is made through a combustible wall a listed and approved wall thimble pass through must be used following the manufacturer s instruc...

Page 7: ...all or Ceiling 18 Unit must be placed on a noncombustible floor Hot Air Supply Duct Hookup With the furnace now in place and the flue connector connected to the chimney it is time to connect the suppl...

Page 8: ...ill greatly improve the air movement up through the system There are also cover plates along both sides at the bottom of the furnace These can also be removed during a power outage to increase the nat...

Page 9: ...ation formats Note these illustrations reflect typical installations and are for design purposes only Illustrations and diagrams are for informational purposes only These diagrams are not drawn to sca...

Page 10: ......

Page 11: ...to operate other than as intended Do not have hot air from gas or oil furnace flow downward into the Hitzer Furnace and flow out the Hitzer Furnace to existing duct work IV Operation Of Furnace WARNI...

Page 12: ...y load the stove to maximum heating potential Starting An Anthracite Coal Fire Starting an Anthracite coal fire takes time and patience Take several sheets of newspaper crumble into balls and place on...

Page 13: ...t air flow and the ability of the coal to burn When this happens this block of burning coal must be broken up with a poker to restore proper operation Add the coal in a couple of stages however it is...

Page 14: ...However when the stove is turned down and not much heat is needed the thermostat controlling the draft closes The gases now have no oxygen to burn and there is very little air movement through the st...

Page 15: ...EXTREMELY HOT FIRE THE CHIMNEY CONNECTOR AND CHIMNEY SHOULD BE INSPECTED AT LEAST TWICE MONTHLY DURING THE HEATING SEASON TO DETERMINE IF A SOOT BUILD UP HAS OCCURRED IF SOOT HAS ACCUMULATED IT SHOUL...

Page 16: ...till you are ready to use the furnace again in the fall Have the chimney inspected and cleaned if necessary If the optional filter housing is not installed you will need to clean the blower wheel Alwa...

Page 17: ...all be the responsibility of the original purchaser and the said Hitzer Inc shall have the final determination and be the final determiner as to whether or not said component is defective Any labor co...

Page 18: ...order for the above stated limited warranty to be effective and binding upon Hitzer Inc this portion herein must be detached and sent by the original owner to Hitzer Inc to the above stated address wi...