Be aware that running the motor at a low speed for a long time can cause motor
overheating. This is particularly true when manual torque boost is ON, or if the motor
relies on a built-in fan for cooling.
Voltage gain – Using parameter A045 you can
modify the voltage gain of the inverter (see
graph at right). This is specified as a
percentage of the full scale output voltage.
The gain can be set from 20% to 100%. It
should be adjusted in accordance with the
motor specifications.
The following table shows the methods of
torque control selection.
“A” Function
Defaults
Func.
Code
Name /
SRW Display
Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)
Units
Torque boost select
A041
V-Bst Slct
MN
U
00
00
%
Torque boost select, 2
nd
motor
A241
2VBst Slct
MN
Two options:
00
}
Manual torque boost
01
}
Automatic torque boost
U
00
00
%
Manual torque boost value
A042
V-Bst V
0005.0%
9
1.8
1.8
%
Manual torque boost value,
2
nd
motor
A242
2VBst V
0005.0%
Can boost starting torque
between 0 and 20% above normal
V/f curve,
range is 0.0 to 20.0%
9
0.0
0.0
%
Manual torque boost
frequency adjustment
A043
M-Bst F
0003.0%
9
10.0
10.0
%
Manual torque boost
frequency adjustment,
2nd motor
A243
2MBst F
0000.0%
Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque boost,
range is 0.0 to 50.0%
9
0.0
0.0
%
V/f characteristic curve
A044
CTRL
C-TRQ
U
00
00
V/f characteristic curve,
2nd motor
A244
2CTRL
C-TRQ
Two available V/f curves;
00
}
Constant torque
01
}
Reduced torque
06
}
Reduced torque1
U
00
00
V/f gain setting
A045
V-Gain
00100%
9
100.
100.
%
V/f gain setting,
2nd motor
A245
2V-Gain
00100%
Sets voltage gain of the inverter,
range is 20. to 100.%
9
100.
100.
%
100%
fbase
fmax
A045=100
80%
A045=80
V
0
3
17
3
−
17
&RQ¿JXULQJ'ULYH
Parameters