The following table lists the holding registers for the “C” Group Intelligent Input Functions.
List of Holding Registers
Network Data
Func.
Code
Name
R/W
Description
Reg.
Range
Res.
C001
Terminal [1] function
R/W
1103h
C201
Terminal [1] function,
2nd motor
R/W
1532h
C002
Terminal [2] function
R/W
1104h
C202
Terminal [2] function,
2nd motor
R/W
1533h
C003
Terminal [3] function
R/W
1105h
C203
Terminal [3] function,
2nd motor
R/W
1534h
C004
Terminal [4] function
R/W
1106h
C204
Terminal [4] function,
2nd motor
R/W
1535h
C005
Terminal [5] function
R/W
1107h
C205
Terminal [5] function,
2nd motor
R/W
See “Input Terminal Configuration”
on page 3-49
1536h
0, 1, 2, 3,
4, 5, 6, 7,
8, 9, 11,
12, 13,
15, 16,
18, 19,
20, 21,
22, 23,
24, 27,
28, 29,
31, 50,
51, 52,
53, 64,
255
C011
Terminal [1] active state
R/W
110Bh
0, 1
C012
Terminal [2] active state
R/W
110Ch
0, 1
C013
Terminal [3] active state
R/W
110Dh
0, 1
C014
Terminal [4] active state
R/W
110Eh
0, 1
C015
Terminal [5] active state
R/W
Select logic conversion, two option
codes:
00
}
normally open [NO]
01
}
normally closed [NC]
110Fh
0, 1
C021
Terminal [11] function
R/W
1114h
C026
Alarm relay terminal
function
R/W
See “Output Terminal
Configuration” on page 3-54
1119h
0, 1, 2, 3,
4, 5, 6, 7,
8, 9, 10,
43
C028
[AM] signal selection
R/W Two available functions:
00
}
motor speed
01
}
motor current
111Bh
0, 1
C031
Terminal [11] active
state
R/W Select logic conversion:
00
}
normally open [NO]
01
}
normally closed [NC]
111Dh
0, 1
C036
Alarm relay active state
R/W Select logic conversion:
00
}
normally open [NO]
01
}
normally closed [NC]
1122h
0, 1
C038
Output mode of low load
detection signal
R/W Three option codes:
00
}
Disabled
01
}
During acceleration,
deceleration and constant speed
02
}
During constant speed only
1178h
0, 1, 2
C039
Low load detection level
R/W Set the level of low load detection,
range is 0.0 to 2.0*rated current
1179h
0 to
20000
0.01%
C041
Overload level setting
R/W
1124h
C241
Overload level setting,
2nd motor
R/W
Sets the overload signal level
between 0% and 200% (from 0 to two
time the rated current of the
inverter)
153Ah
0 to
20000
0.01%
C042
Frequency arrival
setting for acceleration
R/W Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
1126h 0 to 4000
*1
0.1 Hz
C043
Frequency arrival
setting for deceleration
R/W Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
1128h 0 to 4000 0.1 Hz
B
36
Appe
ndix B
B
−
36
Appendix B