ModBus Data Listing
Appendix B
B–36
The following table lists the holding registers for the “C” Group Intelligent Input
Functions.
I
“C” Group Intelligent Terminal Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.
C001
Terminal [1] function
R/W
See
00A7h
0, 1, 2, 3,
4, 5, 6, 7,
8, 9, 11,
12, 13,
15, 16,
18, 19,
20, 21,
22, 23,
24, 27,
28, 29,
31, 50,
51, 255
—
C002
Terminal [2] function
R/W
00A8h
C003
Terminal [3] function
R/W
00A9h
C004
Terminal [4] function
R/W
00AAh
C005
Terminal [5] function
R/W
00ABh
C006
Terminal [6] function
R/W
00ACh
C011
Terminal [1] active state R/W Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
00ADh
0, 1
—
C012
Terminal [2] active state R/W
00AEh
0, 1
—
C013
Terminal [3] active state R/W
00AFh
0, 1
—
C014
Terminal [4] active state R/W
00B0h
0, 1
—
C015
Terminal [5] active state R/W
00B1h
0, 1
—
C016
Terminal [6] active state R/W
00B2h
0, 1
—
C021
Terminal [11] function
R/W
00B3h
0, 1, 2, 3,
4, 5, 6, 7,
8, 9
—
C022
Terminal [12] function
R/W
00B4h
C026
Alarm relay terminal
function
R/W
00B5h
C028
[AM] signal selection
R/W Two available functions:
00... Actual motor speed
01... Motor current
00B7h
0, 1
—
C031
Terminal [11] active
state
R/W Select logic convention, two
option codes:
00... normally open (NO)
01... normally closed (NC)
00B8h
0, 1
—
C032
Terminal [12] active
state
R/W Select logic convention, two
option codes:
00... normally open (NO)
01... normally closed (NC)
00B9h
0, 1
—
C036
Alarm relay active state
R/W Select logic convention, two
option codes:
00... normally open (NO)
01... normally closed (NC)
00BAh
0, 1
—