SJ200 Inverter
Appendix B
B–27
A042
Manual torque boost
value
R/W Can boost starting torque
between 0 and 20% above
normal V/f curve,
range is 0.0 to 20.0%
004Fh
0 to 200
0.1 %
A242
Manual torque boost
value, 2nd motor
R/W
0050h
A043
Manual torque boost
frequency adjustment
R/W Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque
boost, range is 0.0 to 50.0%
0051h
0 to 500
0.1 %
A243
Manual torque boost
frequency adjustment,
2nd motor
R/W
0052h
A044
V/f characteristic curve
selection
R/W Two available V/f curves;
three select codes:
00... Constant torque
01... Reduced torque
02... Intelligent sensorless
vector control
0053h
0, 1, 2
—
A244
V/f characteristic curve
selection, 2nd motor
R/W
0054h
A045
V/f gain setting
R/W Sets voltage gain of the
inverter, range is 20. to 100.%
0055h
20 to 100
1 %
A046
Automatic torque boost
voltage gain
R/W Sets torque boost voltage gain
of the inverter,
range is 0 to 255
0056h
0 to 255
—
A246
Automatic torque boost
voltage gain, 2nd motor
R/W
0057h
A047
Automatic torque boost
slip gain
R/W Sets torque boost slip gain of
the inverter,
range is 0 to 255
0058h
0 to 255
—
A247
Automatic torque boost
slip gain, 2nd motor
R/W
0059h
A051
DC braking enable
R/W Two options; select codes:
00... Disable
01... Enable
005Ch
0, 1
—
A052
DC braking frequency
setting
R/W The frequency at which DC
braking begins,
range is from the start
frequency (B082) to 60 Hz
005Dh
(B082 x
10) to 600
0.1 Hz
A053
DC braking wait time
R/W The delay from the end of
controlled deceleration to start
of DC braking (motor free runs
until DC braking begins),
range is 0.0 to 5.0 sec.
005Eh
0, 1
—
A054
DC braking force for
deceleration
R/W Level of DC braking force,
settable from 0 to 100%
005Fh
0 to 100
1 %
A055
DC braking time for
deceleration
R/W Sets the duration for DC
braking, range is 0.0 to 60.0
seconds
0060h
0 to 600
0.1 sec
Holding Registers for “A” Group Standard Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.