ModBus Data Listing
Appendix B
B–34
B085
Country code for initial-
ization (not accessible
to ModBus)
—
Select default parameter values
for country on initialization.
Note: Write not allowed from
network.
009Bh
—
—
B086
Frequency scaling
conversion factor
R/W Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9
009Ch
1 to 999
0.1
B087
STOP key enable
R/W Select whether the STOP key
on the keypad is enabled, two
option codes:
00... enabled
01... disabled
009Dh
0, 1
—
B088
Restart mode after FRS
R/W Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)
009Eh
0, 1
—
B090
Dynamic braking usage
ratio
R/W Selects the rate of use (in %) of
the regenerative braking
resistor per 100 sec. intervals,
range is 0.0 to 100.0%
0% . Dynamic braking disabled
>0% Enabled, per value
009Fh
0 =
disabled
, 1 to
1000
enabled
0.1 %
B091
Stop mode selection
R/W Selects how the inverter stops
the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)
00A0h
0, 1
—
B092
Cooling fan control
R/W Selects when the fan is ON per
inverter operation, two options:
00... Fan is always ON
01... Fan is ON during run,
OFF during stop (5 min.
delay from ON to OFF)
02... Fan is temperature
controlled
00A1h
0, 1, 2
—
B095
Dynamic braking
control
R/W Three option codes:
00... Disable
01... Enable during RUN only
02... Enable always
00A2h
0, 1, 2
—
B096
Dynamic braking
activation level
R/W Range is:
330 to 380V (200V class),
660 to 760V (400V class)
00A3h
330 to
380, 660
to 760
1 V
“B” Group Fine Tuning Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.