SJ200 Inverter
Appendix B
B–29
A077
Reverse PID action
R/W Two option codes:
00... PID input = SP – PV
01... PID input = –(SP – PV)
00E1h
0, 1
—
A078
PID output limit
R/W Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0%
00E2h
0 to 1000
0.1 %
A081
AVR function select
R/W Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
00... AVR enabled
01... AVR disabled
02... AVR enabled except
during deceleration
0072h
0, 1, 2
—
A082
AVR voltage select
R/W 200V class inverter settings:
00... 200
01... 215
02... 220
03... 230
04... 240
400V class inverter settings:
00... 380
01... 400
02... 415
03... 440
04... 460
05... 480
0073h
0 to 5
—
A092
(high)
Acceleration (2) time
setting
R/W Duration of 2nd segment of
acceleration, range is:
0.01 to 3000 sec.
0074h
1 to
300000
*1
0.1 sec
A092
(low)
R/W
0075h
A292
(high)
Acceleration (2) time
setting, (2nd motor)
R/W Duration of 2nd segment of
acceleration, 2nd motor,
range is: 0.01 to 3000 sec
0076h
1 to
300000
*1
0.1 sec
A292
(low)
R/W
0077h
A093
(high)
Deceleration (2) time
setting
R/W Duration of 2nd segment of
deceleration, range is:
0.01 to 3000 sec.
0078h
1 to
300000
*1
0.1 sec
A093
(low)
R/W
0079h
A293
(high)
Deceleration (2) time
setting, (2nd motor)
R/W Duration of 2nd segment of
deceleration, range is:
0.01 to 3000 sec.
007Ah
1 to
300000
*1
0.1 sec
A293
(low)
R/W
007Bh
Holding Registers for “A” Group Standard Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.