background image

SJ100DN Inverter

51

Step 6 – Monitor Test – Verify Network Host Can 

Monitor

 Inverter

This step requires that you have completed the previous 5 steps, and that the powerup 
test during the installation was successful (see “Running the Motor” on page 25). At this 
point in the procedure, the inverter is using front panel keypad inputs for Run/Stop 
commands. The DeviceNet host computer can monitor inverter operation 

without 

actually controlling

 the inverter. So, you do not have to change any “P Group” parame-

ters from their defaults to do this network monitoring test.

Inverter Status LEDs

 – The two status LEDs on the 

inverter’s front panel are to the right of the Stop key.

• MS – Module Status

• NS – Network Status

The status LEDs may be green or red, and may or OFF, 
ON, or flashing between OFF and ON. The table below 
shows how to interpret the status LED indications. (At 
this point, the correct status is MS=green, NS=OFF.)

LED

Color

Status

Corrective Action

MS

Green

Normal power-ON status

Flashing Green

Inverter in standby state

Red

Fatal error (trip E11 or E12)

Confirm electrical noise level 
is acceptable

Replace inverter

Flashing Red

Trip condition (non-fatal)

Look up error code in manual 
Chapter 6, press Stop/Reset

OFF

Inverter power is OFF

NS

Green

Connected to network/online

Flashing Green

Connected to network/idle

Red

Critical network error

Check network for:

Disconnected cable

Termination resistor not 
present / wrong value

Duplicate MAC IDs

Baud rate settings mis-match

Cable too long

Flashing Red

Communications time-out

Check network for:

Disconnected cable

Termination resistor not 
present / wrong value

Baud rate settings mis-match

Cable too long

OFF

Power OFF or DeviceNet offline

Hz

POWER

A

RUN

PRG

RUN

STOP

RESET

MS
NS

HITACHI

FUNC.

STR

1

2

5 0.0

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Summary of Contents for SJ100DN DeviceNet Series Addendum

Page 1: ...l service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR MORE INFORMATION Visit us on the web at www artisantg com for more information on ...

Page 2: ...erations and Monitoring 32 Network Control and Monitoring 39 Troubleshooting and Maintenance 70 In the Appendices DeviceNet Object Lists 71 Network Register Map 78 Drive Parameter Settings Tables 91 Restoring Factory Default Settings 99 Addendum to SJ100 Series Inverter Instruction Manual READ THIS FIRST Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 3: ... DeviceNet Vendor Association Inc Revision History Table No Revision Comments Date of Issue Addendum No Initial Release of Addendum NB643X Jan 2003 NB643X Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 4: ... UL or CE version available Sensorless vector control Regenerative braking circuit Convenient keypad for parameter settings Built in DeviceNet network interface to allow control and monitoring via a DeviceNet network Sixteen programmable speed levels Three wire control interface Up Down electronic motorized speed pot function Motor constants are programmable or may be set via auto tuning The desig...

Page 5: ...rking MS Module Status LED NS Network Status LED Front panel door Half door for programming keys and control terminals Analog input terminals H O OI L PWM output terminal FM Intelligent input terminals 1 2 3 4 5 6 1 2 3 only Intelligent input functions Includes AT Includes STA STP F R DNT OPE Intelligent output terminals 11 12 AL0 to AL2 11 12 only Intelligent output functions Includes OD Digital ...

Page 6: ...r this model Output Rating Frequency voltage current Manufacturing codes Lot number date etc Specifications label Regulatory agency approvals Power Input Rating frequency voltage phase current SJ100DN 004 H F U Restricted distribution E Europe U USA Input voltage N single or three phase 200V class H three phase 400V class L three phase only 200V class Applicable motor capacity in kW 002 0 2 kW 004...

Page 7: ...wn node address One device will be the network master all other device s will be network slaves The SJ100DN inverter will operate as a network slave as the network master also called host computer will send commands to the slaves A factory network such as DeviceNet allows you to integrate devices of many different types even from various manufacturers all into an integrated control system A common...

Page 8: ...e run change by command External signal Forward run stop Reverse run stop on intelligent terminals Network Forward run stop Reverse run stop Intelligent input terminal FW forward run command RV reverse run command CF1 CF4 multi stage speed setting JG jog command 2CH 2 stage accel decel command FRS free run stop command EXT external trip USP startup function SFT soft lock RS reset PTC thermal prote...

Page 9: ...perature refers to the short term temperature during transport Note 6 Conforms to the test method specified in JIS C0911 1984 For the model types excluded in the standard specifications contact your Hitachi sales repre sentative Operat ing Environ ment Temperature Operating ambient 10 to 50 C 4 Storage 25 to 70 C 5 Humidity 20 to 90 humidity non condensing Vibration 6 5 9 m s2 0 6G 10 to 55 Hz Loc...

Page 10: ...nstruction has a heat sink at the back of the housing The larger models include a fan s to enhance heat sink perfor mance The mounting holes are pre drilled in the heat sink for your convenience Never touch the heat sink during or just after operation it can be very hot The electronics housing and front panel are built onto the front of the heat sink The front panel has two levels of physical acce...

Page 11: ...d Then locate the recessed retention screw on the left side main front panel it is along the left hinge area on some models or behind the first access door on others Use a small screwdriver Regular or Phillips to loosen the screw Swing the door around to the right to reveal the internal components of the drive The two level tiered 12 position terminal block accepts wires for the power input and wi...

Page 12: ...s you from touching a n unexpected live circuit and it protects the inverter from electrostatic discharge ESD The power and motor connector terminals are accessible with the removal of the housing partition The input power and motor connec tions use the lower row of terminals The upper row is for connecting dynamic braking components Housing partition Power and motor connector terminals Artisan Te...

Page 13: ... standard manual with the exception of the dimension drawings which follow below NOTE After doing the basic installation physical mounting and power wiring per the instructions in Chapter 2 of the SJ100 manual be sure to return to this addendum for the Powerup Test and Front Panel Keypad orientation Check Inverter Dimensions Locate the applicable drawing on the following pages for your inverter Di...

Page 14: ... 5 0 10 SJ100DN 004HFE2 004HFU2 007NFE2 007NFU2 011NFE2 MODEL Ground Terminal 98 3 86 118 4 65 130 5 12 110 4 33 5 0 20 5 0 20 156 6 14 6 6 24 SJ100DN 007HFE2 no fan 007HFU2 no fan 015HFE2 022HFE2 022HFU2 015HFU2 Ground Terminal Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 15: ...28 5 04 168 6 61 5 0 20 140 5 51 180 7 09 10 0 39 153 6 02 6 0 24 Ground Terminal 140 5 51 168 6 61 128 5 04 180 7 09 164 6 46 5 0 20 5 0 20 SJ100DN 022NFE2 022NFU2 037LFU2 030HFE2 040HFE2 040HFU2 6 0 24 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 16: ...ntinued 182 7 17 236 9 29 160 6 30 257 10 12 7 0 28 7 0 28 170 6 69 6 0 24 055LFU2 075LFU2 055HFE2 055HFU2 075HFE2 SJ100DN 075HFU2 1 0 04 Ground Terminal Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 17: ...3 Give a brief introduction to the use of the built in operator keypad The powerup test gives you an important starting point to ensure a safe and successful application of the Hitachi inverter We highly recommend performing this test before proceeding to the other chapters in this manual Pre test and Operational Precautions The following instructions apply to the powerup test or to any time the i...

Page 18: ...d warnings up to this point you re ready to apply power After doing so the following events should occur The POWER LED will illuminate The numeric 7 segment LEDs will display a test pattern then stop at 0 0 The Hz LED will be ON This assumes the inverter is in Monitor Mode and is displaying D_01 the output frequency The MS Module Status and NS Network Status LEDs will exhibit a test pattern each L...

Page 19: ...ess this key to stop the motor when it is running uses the programmed deceleration rate This key will also reset an alarm that has tripped Module Status LED ON green when the inverter has power The Module Status LED may also be flashing and or red in color For a description of all LED states and their meanings see the table in Step 6 Monitor Test Verify Network Host Can Monitor Inverter on page 51...

Page 20: ...ED will be ON You use the front panel keys to first select the function code A_04 After displaying the value for A_04 use the Up Down or keys to edit it NOTE The inverter 7 segment display shows lower case b and d meaning the same as the upper case letters B and D used in this manual for uniformity A to F The inverter automatically switches into Monitor Mode when you access D Group functions It sw...

Page 21: ... to become familiar with the basic navigational map of parameters and functions in the diagram below 1 2 2 1 Edit Write data to EEPROM Increment decrement value 2 1 2 1 2 1 2 1 2 1 2 1 1 Select Parameter Select Function or Group Display Data 2 Return to parameter list 2 1 2 1 2 1 2 1 2 1 2 1 2 1 Edit Parameter FUNC FUNC FUNC FUNC FUNC STR 000 0 d 1 6 d 01 h C b A F 04 F 01 A 01 A 9 8 b 01 C 4 3 b ...

Page 22: ...frequencies after getting their approval Otherwise there is the danger of equipment damage Setting the Motor Base Frequency The motor is designed to operate at a specific AC frequency Most commercial motors are designed for 50 60 Hz operation First check the motor specifications Then follow the steps in the table below to verify the setting or correct for your motor DO NOT set it for greater than ...

Page 23: ...evious table NOTE When you press the STR key in the last step above and the display 02 the Run Key Enable LED above the RUN key on the keypad will turn ON This is normal and does not mean the motor is trying to run It means that the RUN key is now enabled DO NOT press the RUN key at this time finish out the programming exercise first Action Display Func Parameter Press the key Run command source P...

Page 24: ...y arrive via the network In this case you have the additional option of using the inverter s parameters includes F_01 Output Frequency Setting or the network host device can send the output frequency setting via the network upon each network scan More details are in Network Control and Monitoring on page 39 This step in the powerup test will set F_01 Output Frequency Setting to 15Hz CAUTION Be sur...

Page 25: ...ate of the PRG LED Then study the Keypad Navigational Map on page 20 to determine the current state of the keypad controls and display As long as you do not press the STR key no parameters will be changed by keypad entry errors Note that power cycling the inverter will not cause it to reset to a particular programming state The next section will show you how to monitor a particular parameter from ...

Page 26: ...particular monitoring parameter After pressing the Function key the display shows the current speed is zero at this point Running the Motor If you have programmed all the parameters up to this point you re ready to run the motor First review this checklist 1 DO NOT connect the inverter to the DeviceNet network or supply 24V network power yet 2 Verify the Power LED and Module Status MS LEDs are ON ...

Page 27: ...culate the RPM The theoretical speed for the motor is 1800 RPM speed of torque vector rotation However the motor cannot generate torque unless its shaft turns at a slightly different speed This difference is called slip So it s common to see a rated speed of approxi mately 1750 RPM on a 60 Hz 4 pole motor Using a tachometer to measure shaft speed you can see the difference between the inverter out...

Page 28: ... C_06 C_14 C_15 C_16 Intelligent output terminal settings for 4 to 6 C_23 FM signal selection C_24 C_33 Intelligent output terminal settings for AL0 to AL2 New intelligent input terminal functions not present in standard SJ100 STA Start Motor option code 20 STP Stop Motor option code 21 F R Forward Reverse option code 22 DNT Select DeviceNet option code 25 OPE Force Operation from Digital Operator...

Page 29: ...erminal 1 function Select function for terminal 1 22 options see inverter manual 00 FW 00 FW 00 FW C_02 Terminal 2 function Select function for terminal 2 22 options see inverter manual 21 STP 21 STP 21 STP C_03 Terminal 3 function Select function for terminal 3 23 options see inverter manual and Note below 12 EXT 12 EXT 12 EXT C Function Run Mode Edit Defaults Func Code Name Description FE CE FU ...

Page 30: ...ble Option Code Terminal Symbol Function Name Description 20 STA Start Motor ON Start motor rotation on momentary contact uses acceleration profile OFF No change to motor operation 21 STP Stop Motor ON Stop motor rotation on momentary contact uses deceleration profile OFF No change to motor operation 22 F R FWD REV ON Select reverse direction of rotation OFF Select forward direction of rotation 25...

Page 31: ...terminals in order to invert the sense of the logic C Function Run Mode Edit Defaults Func Code Name Description FE CE FU UL F Jpn Units C_21 Terminal 11 function Select function for terminal 11 5 options see inverter manual 00 RUN 00 RUN 00 RUN C_22 Terminal 12 function Select function for terminal 12 5 options see inverter manual 05 AL 05 AL 05 AL C Function Run Mode Edit Defaults Func Code Name...

Page 32: ...ect codes 00 Disable 01 Enable 01 01 01 P_44 DeviceNet comm watchdog timer Range is 0 00 to 99 99 seconds 1 00 1 00 1 00 P_45 Inverter action on DeviceNet comm error Five options 00 Trip 01 Decelerate and trip 02 Hold last speed 03 Free run stop 04 Decelerate and stop 01 01 01 P_46 DeviceNet polled I O Output instance number Three settings 20 21 100 1 100 100 100 P_47 DeviceNet polled I O Input in...

Page 33: ... 12 11 1 2 3 L D CL V CM2 SJ100DN P24 Open collector outputs CANbus High Power source 3 phase or 1 phase per inverter model R L1 S L2 T N L3 U T1 V T2 W T3 Motor FW STP Intelligent inputs 3 terminals CANbus Low Drain NOTE For the wir ing of intelligent I O be sure to use twisted pair shielded cable Attach the shield wire for each signal to its respective common terminal at the inverter end only Bu...

Page 34: ...requirements given by the DeviceNet industry standards For more information visit the Open DeviceNet Vendor Association website at http www odva org Logic inputs Logic outputs L 3 1 2 P24 CM2 12 11 DeviceNet network connector Auxiliary network power connector Terminal Name Description Ratings P24 24VDC for logic inputs 24VDC 30 mA max Notes Do not use for network power Do not short to terminal L 1...

Page 35: ...trol of motor If you have a motor control interface that needs logic level control rather than momentary pulse control use the FW and RV inputs instead Option Code Terminal Symbol Function Name Input State Description 20 STA Start Motor ON Start motor rotation on momentary contact uses acceleration profile OFF No change to motor operation 21 STP Stop Motor ON Stop motor rotation on momentary conta...

Page 36: ... the Start command The control of direction is level sensitive and the direction may be changed at any time STP Stop Motor is also a level sensitive input and the Stop signal has priority over the Start signal When both STA and STP signals are ON the STP signal has priority motor output will be OFF However the motor output resumes after STP signal is no longer active if the STA input is still ON 1...

Page 37: ...shown below In the graph below the network FWD command places the inverter in Run mode While the motor is running the local STP input terminal activates causing the inverter to decelerate the motor to a stop It remains stopped even though the FW command is still active The FW command must turn OFF and ON again to resume motor operation Inverter Network host DeviceNet network STP Run Stop commands ...

Page 38: ...e 43 Option Code Terminal Symbol Function Name State Description 25 DNT DeviceNet Select ON The inverter operates per commands and param eters output freq accel decel from DeviceNet OFF The inverter operates per local commands keypad or terminal Run Stop and its internal parameters speed accel decel Valid for inputs C_01 C_02 C_03 Required settings Notes When any input terminal is assigned as DNT ...

Page 39: ... to over ride commands from input terminals such as FW RV OFF Run command operates normally as configured by A_02 Valid for inputs C_01 C_02 C_03 Required settings A_02 01 Notes When the OPE signal is ON the keypad Run and Stop keys are active and FW or RV signal is ignored However OPE cannot cause the keypad to over ride the DeviceNet host commands To enable disable DeviceNet control via an input...

Page 40: ...er devices such as motor drives still require a main power source Devices may be connected or disconnected without powering down the network if daisy chained Flexible device definitions the device protocol provides for many types of input and output structures Open standard allows multiple vendors to produce many types of products that can coexist on a network DeviceNet is an open network standard...

Page 41: ...E Be sure to install the inverter and perform the powerup test described in the Inverter Mounting and Installation on page 9 before attempting network operation The step to DeviceNet network control and monitoring are 1 Design your network layout 2 Connect network devices a Add network termination b Add network power 3 Prepare network host computer 4 Prepare inverter for network 5 Understand the i...

Page 42: ...s shown in the diagram the node addresses do not have to occur in a particular sequence in the physical layout Showing node connections now in greater detail the connection to each device in the middle of the network may be a daisy chain connection or a drop connection The differ ence is that a daisy chain connection enters and exits right at the connector while a drop connection inserts an extra ...

Page 43: ...e trunk line the maximum distance is 100m for all baud rates Baud Rate Trunk length thick cable Drop Length Maximum Cumulative 125 kbps 500m 1640 ft 6m 20 ft 156m 512 ft 250 kbps 250m 820 ft 6m 20 ft 78m 256 ft 500 kbps 100m 328 ft 6m 20 ft 39m 128 ft Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...

Page 44: ...er would overload a network The terminations provides signal integrity and noise immunity Therefore add two resistors as close to the endpoint connectors as possible TIP To simplify configuration and startup we recommend starting with just the network host PLC or computer and the inverter It is easier to resolve addressing or other conflicts with fewer devices With network wiring for just two devi...

Page 45: ...o 8A per network segment NOTE Class II NEC Code limits the current for any network segment to 4A DeviceNet thick type cable is limited to 8A thin type cable is limited to 3A Add a 24VDC supply to the network as shown below It is not necessary to power it for this step later steps will provide powerup instructions Alternatively you can use the auxiliary network power connector as shown below left T...

Page 46: ...intained The power supply must provide proper output current limit and fusing for the network device load Remember that you must open the front door panel of the inverter to connect or disconnect wiring to the auxiliary network power connector If power has been connected wait five minutes after powerdown and verify the Power LED is OFF before opening the inverter front door panel L 3 1 2 P24 CM2 1...

Page 47: ...e to the Downloads area and then to EDS files From the EDS files select Hitachi as the manufacturer Download the file that matches your inverter s version SJ100DN2 for example Then load or place the EDS file in your network host device in the location directory it requires for use in network device scanning Refer to the documentation of your host device for this information Set node address of hos...

Page 48: ... baud rate Three options select codes 00 125 kbps 01 250 kbps 02 500 kbps 00 P_42 DeviceNet MAC ID Selects the DeviceNet node address range is 0 to 63 63 P_43 DeviceNet control enable Two options select codes 00 Disable 01 Enable 01 P_44 DeviceNet comm watchdog timer Range is 0 00 to 99 99 seconds 1 00 P_45 Inverter action on DeviceNet comm error Five options 00 Trip 01 Decelerate and trip 02 Hold...

Page 49: ...e oriented to simpler I O devices time based updates or value change updates More suited to simple or analog applications such as data logging these network master commands are not supported by SJ100DN inverters Explicit Messaging supported in SJ100DN The Explicit Messaging mechanism goes beyond the four standard scan mechanisms listed above A master can use an Explicit Message request to Get read...

Page 50: ...ble defines individual bits of the status byte Inverter Produced Data Host Input Instance P_47 101 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Input term 3 Input term 2 Input term 1 Freq Arrival Trip RV Run FW Run 1 Inverter status see status code table next page 2 Output frequency monitor low byte D_01 value 3 Output frequency monitor high byte D_01 value 4 Output current monitor low b...

Page 51: ...he inverter is executing DC braking includes CD braking wait time 5 The inverter is attempting a restart with frequency matching B_01 03 6 The output is stopped for an instantaneous power failure 7 The inverter is attempting a restart with frequency matching B_01 02 8 The inverter is waiting before it attempts a restart with frequency matching The wait time is set by parameter B_03 9 The inverter ...

Page 52: ...rpret the status LED indications At this point the correct status is MS green NS OFF LED Color Status Corrective Action MS Green Normal power ON status Flashing Green Inverter in standby state Red Fatal error trip E11 or E12 Confirm electrical noise level is acceptable Replace inverter Flashing Red Trip condition non fatal Look up error code in manual Chapter 6 press Stop Reset OFF Inverter power ...

Page 53: ... If the NS LED OFF the network is disconnected Check the cable and also check the host application software settings If the NS LED Flashing Green the network is connected but idle Start the host network scan to cause NS LED Green If Red or Flashing Red use the Status LED table on the previous page to troubleshoot h Confirm that the host computer can see the inverter s polled I O You will be monito...

Page 54: ...ale factor of 10 is applied This value represents a small inverter and motor size your reading may differ Word 3 The decimal value of 0 for trip code D_08 reading corresponds to no trip status NOTE When a trip event occurs the polled I O will indicate it by Trip Bit 1 in Word 0 and the actual Trip Code in Word 3 When the trip condition is cleared Stop Reset key then the Trip bit 0 but the Trip Cod...

Page 55: ...ng or signal at the inverter enables or permits network control This means that an operator or control system at the inverter can at any time take back control of the inverter from a network host by disabling DeviceNet control The inverter uses P_43 DeviceNet Control Enable for the primary method of control selection By default P_43 1 set to enable network control Alternatively you can assign the ...

Page 56: ... Network Reference setting logic The logic requires that the inverter has enabled DeviceNet control as described above Note 1 Logic above requires inverter s P_43 or DNT to enable DeviceNet control Typically a network host computer needs to have control of Run Stop speed accel and decel This corresponds to No 3 above where both Network Control and Network Reference bits are set 1 If the inverter n...

Page 57: ...ta Host Output Instance P_46 100 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Network Refer ence Network Control Free run Stop Fault Reset RV Run FW Run 1 2 Output frequency low byte host override for F_01 value 3 Output frequency high byte host override for F_01 value 4 Acceleration time low byte host override for F_02 value 5 Acceleration time high byte host override for F_02 value 6 D...

Page 58: ...e inverter has switched its control source from local to network control e Turn ON the FW Run bit bit 0 in Word 0 as shown below The motor will now begin to run The output frequency will be 15 00Hz set by F_01 To verify the motor speed monitor D_01 on the inverter display or use the host computer to observe the actual output frequency reported in the polled I O f Now turn OFF the FW Run bit bit 0 ...

Page 59: ... The scaling of the polled I O data for output frequency accel decel values corresponds to the network scale factors for parameters F_01 F_02 and F_03 respec tively A listing of inverter parameters and scale factors is in the Network Register Map on page 78 d Turn ON the FW Run bit bit 1 in Word 0 as shown below The motor will now begin to run The output frequency will be 20 00Hz To verify the mot...

Page 60: ...enly in certain conditions to avoid injury to personnel or equipment damage If so be sure to configure the STP input terminal on the inverter described in Three wire Interface Operation on page 34 This will provide a way for the control environment at the inverter to stop the motor should the host computer fail to turn the motor OFF when required MSB LSB High byte MSB LSB Low byte Word 0 0060h Hex...

Page 61: ...1 CF2 CF3 CF4 JG or 2CH turns ON the inverter performs the related function with priority If the inverter reset is ON at powerup a communication time out error will occur at the master In this case the master will need to re establish communications When an inverter has a power cycle or reset the DeviceNet master may request to start or resume motor rotation If the master does not specify the acce...

Page 62: ...work has a specific node address default 63 To access a particular parameter in that inverter the host computer uses the class instance and attribute numbers together The address ranges indicated in the table above could access any one of thousands of values within a device if needed In DeviceNet terminology a read access is called get and a write access is called a set The assignment of DeviceNet...

Page 63: ...onse if your host application provides this e Have the host computer send the explicit message f Verify the inverter s response is 5DCh or 1500 decimal If not check the values in the get attribute request and check the present value of parameter F_01 at the inverter g Apply the scale factor in the Network Register Map table For F_01 divide by 100 so 1500 becomes 15 00Hz A set attribute request wor...

Page 64: ...velocity profile for the example program It consists of a forward rotation followed by a reverse rotation The program will send the commands and parameter values to set the speed and accel decel values Command Bit Sequencing The order of 0 to 1 transitions of the host computer s Word 0 command bits is important First set the Network Control bit bit 5 and or the Network Reference bit bit 6 as neede...

Page 65: ...ency 15 0 Hz Set accel decel times 20 sec Set RV Run bit 1 Wait 15 seconds Set RV Run bit 0 Freq Arrival 0 Run Mode 0 FW Run 0 RV Run 0 Freq monitor 0 00Hz Current monitor 0 0A Trip code 0 Freq Arrival 1 Run Mode 1 FW Run 1 RV Run 0 Freq monitor 25 0Hz Current monitor 1 1A Trip code 0 Freq Arrival 1 Run Mode 1 FW Run 1 RV Run 0 Freq monitor 10 00Hz Current monitor 1 1A Trip code 0 Freq Arrival 0 R...

Page 66: ...sec 00C8h Accel stage 0102h xxxxh 9 Constant speed 0112h 05DCh 10 Stop 0060h same same Decel stage 0102h xxxxh 11 Stop 0000h 0000h 8 9 10 11 6 7 1 2 3 4 5 Host output hex Word 0 Word 1 Word 2 Word 3 Program Example With Data Forward rotation Reverse rotation 0060 09C4 0064 0064 freq 25Hz freq 10Hz freq 15Hz accel decel 10sec accel decel 20sec 0061 09C4 0064 0064 0061 09C4 0064 0064 0061 03E8 0064 ...

Page 67: ...ride for F_01 value 3 Output frequency high byte host override for F_01 value Inverter Consumed Data Host Output Instance P_46 21 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Network Refer ence Network Control Fault Reset RV Run FW Run 1 2 Output frequency low byte host override for F_01 value 3 Output frequency high byte host override for F_01 value Inverter Consumed Data Host Output In...

Page 68: ...trol Run Stop control is local to inverter Run Stop control is from network host polled I O 6 Network Reference Output freq accel decel is from F_01 F_02 F_03 Output freq accel decel is from network host polled I O 7 Inverter Produced Data Host Input Instance P_47 70 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 FW Run Trip 1 Inverter status see status code table next page 2 Output freque...

Page 69: ...eady Inverter is ready status byte code 3 4 or 5 5 Network Control Run Stop control is local to inverter Run Stop control is from network host polled I O 6 Network Reference Output freq accel decel is from F_01 F_02 F_03 Output freq accel decel is from network host polled I O 7 Frequency Arrival Inverter stopped or in accel or decel Inverter output arrived at target freq Inverter Produced Data Hos...

Page 70: ...de 3 The inverter is in Stop Mode and the motor output is free running coasting 4 The inverter is executing DC braking includes CD braking wait time 5 The inverter is attempting a restart with frequency matching B_01 03 6 The output is stopped for an instantaneous power failure 7 The inverter is attempting a restart with frequency matching B_01 02 8 The inverter is waiting before it attempts a res...

Page 71: ...inal DNT if assigned DNT input has priority over P_43 Note 4 The DeviceNet connection time out refers to the time out within the DeviceNet Connection Object per the DeviceNet specifications In if Run Mode when the time out occurs the inverter decelerates the motor to a stop Note 5 The host computer can release the connection to the inverter via the standard service release mechanism In if Run Mode...

Page 72: ...e Hitachi Ltd Vendor ID 74 Device profile name AC Drive Profile number 2 Product catalog number Product revision 3 2 Physical conformance data Network power consumption 50mA at 11VDC Connector style Open pluggable Isolated physical layer Yes LEDs supported Module Status LED Network Status LED Default MAC ID 63 Baud rate selection Software selectable Baud rate settings 125 250 and 500 k bits sec Co...

Page 73: ...ned short integer Int 1 Byte 128 127 INT Signed integer Int 2 Bytes 32768 32767 DINT Signed double integer Int 4 Bytes 231 231 1 Identity Object Class ID 1 hex Category Attribute ID Access Rule Data Type Initialization Class not supported Instance 1 Vendor ID 1 Get UINT 74 Device type 2 Get UINT 2 AC drive Product code 3 Get UINT SJ100DN2 0702h Major revision 4 Get USINT 3 Minor revision Get USINT...

Page 74: ...ter check F_01 A_03 A203 A_20 A_35 A220 A_38 A_52 A_61 A_62 20h 00 Value less than lower frequency limit setting 01 Value more than upper frequency limit setting 02 Value more than maximum frequency setting 03 Out of range condition not listed above Invalid parameter 04 DeviceNet Object Class ID 3 hex Category Attribute ID Access Rule Data Type Initialization Class Revision 1 Get UINT 2 Instance 1...

Page 75: ...ribute ID Access Rule Data Type Initialization Class not supported Instance 1 State 1 Get USINT Instance type 2 Get USINT 00 Transport class trigger 3 Get BYTE 83h Produced connection ID 4 Get UINT Consumed connection ID 5 Get UINT Initial comm characteristics 6 Get BYTE 21h Produced connection size 7 Get UINT C8h Consumed connection size 8 Get UINT C8h Expected packet rate 9 Get Set UINT 09C4h Wa...

Page 76: ...NT 03E8h Watchdog time out action 12 Get Set USINT 0 Produced conn path length 13 Get UINT 3 Produced connection path 14 Get UINT array 623625 Consumed conn path length 15 Get UINT 3 Consumed connection path 16 Get UINT array 623624 Supported Services Connection Object Service Name Code Description Reset 05h Get_Attribute_Single 0Eh Set_Attribute_Single 10h Connection Object Class ID 5 hex Categor...

Page 77: ...visor Object Class ID 29 hex Category Attribute ID Access Rule Data Type Initialization Class Revision 1 Get WORD 0001 Instance 1 Run1 3 Get Set BYTE 00 Run2 4 Get Set BYTE 00 Network Control 5 Get Set BYTE 00 State 6 Get BYTE Running1 7 Get BYTE 00 Running2 8 Get BYTE 00 Ready 9 Get BYTE 00 Faulted 10 Get BYTE 00 Warning 11 Get BYTE 00 Fault reset 12 Get Set BYTE 00 Fault code 13 Get WORD 0000 Co...

Page 78: ...Get WORD 0000 Current limit 10 Get Set WORD B_21 setting Input voltage 16 Get WORD Output voltage 17 Get WORD 0000 Accel time 18 Get Set WORD F_02 setting Decel time 19 Get Set WORD F_03 setting Low speed limit 20 Get Set WORD A_62 setting High speed limit 21 Get Set WORD A_04 setting Speed scale 22 Get Set BYTE 00 Current scale 23 Get Set BYTE 00 Voltage scale 27 Get Set BYTE 00 Time scale 28 Get...

Page 79: ...imal fractional part Main Profile Parameters and Basic Inverter Data D Group Parameters and Basic Inverter Data DeviceNet Class ID 100 Func Code Name Inst Attr Size Range Scaling Get Set Rated capacity 1 100 1 1 0 2 kW 2 0 4 kW 3 0 55 kW 4 0 75kW 5 1 1 kW 6 1 5 kW 7 2 2 kW 8 8 3 kW 9 3 7 kW 10 4 0 kW 11 5 5 kW 12 7 5 kW Get Input AC voltage class 1 101 1 1 200V 2 400V Get Rated output current 1 10...

Page 80: ...n RUN time at trip point 1 126 4 0 FFFFFFh hex hours 1 Get D_09 Trip event monitor nth 1 trip 1 128 1 00 to 60 see Ch 6 in manual Get Output frequency at trip point 1 129 2 0 01 360Hz 100 Get Motor current at trip point 1 130 2 0 00 655 35A 100 Get DC bus voltage at trip point 1 131 2 0 0 6553 5V 10 Get Cumulative operation RUN time at trip point 1 132 4 0 FFFFFFh hex hours 1 Get D_09 Trip event m...

Page 81: ... routing 1 162 1 0 forward 1 reverse 2 F R terminal Get Input terminal functions monitor1 1 163 2 See EDS file Get Input terminal functions monitor2 1 164 2 See EDS file Get Input terminal functions setting1 1 165 2 See EDS file Get Input terminal functions setting2 1 166 2 See EDS file Get Output terminal functions monitor 1 167 1 See EDS file Get Supported Services DeviceNet Class ID 100 Service...

Page 82: ...2 0 00 360 00Hz 100 G S A_23 Multi speed 3 setting 1 123 2 0 00 360 00Hz 100 G S A_24 Multi speed 4 setting 1 124 2 0 00 360 00Hz 100 G S A_25 Multi speed 5 setting 1 125 2 0 00 360 00Hz 100 G S A_26 Multi speed 6 setting 1 126 2 0 00 360 00Hz 100 G S A_27 Multi speed 7 setting 1 127 2 0 00 360 00Hz 100 G S A_28 Multi speed 8 setting 1 128 2 0 00 360 00Hz 100 G S A_29 Multi speed 9 setting 1 129 2...

Page 83: ...educed torque 2 Sensorless vector control G S A244 V f characteristic curve selec tion 2nd motor 2 144 1 0 Constant torque 1 Reduced torque 2 Sensorless vector control G S A_45 V f gain setting 1 145 1 50 100 1 G S A_51 DC braking enable 1 151 1 0 Disable 1 Enable G S A_52 DC braking frequency setting 1 152 2 0 5 10 0Hz 100 G S A_53 DC braking wait time 1 153 1 0 1 5 0 sec 10 G S A_54 DC braking f...

Page 84: ... 2 time setting 1 193 2 0 1 3000 0 sec 10 G S A293 Deceleration 2 time setting 2nd motor 2 193 2 0 1 3000 0 sec 10 G S A_94 Select method to switch to Acc2 Dec2 profile 1 194 1 0 2CH input from terminal 1 transition frequency G S A294 Select method to switch to Acc2 Dec2 profile 2nd motor 2 194 1 0 2CH input from terminal 1 transition frequency G S A_95 Acc1 to Acc2 frequency transi tion point 1 1...

Page 85: ...gle 10h B Group Parameters DeviceNet Class ID 103 Func Code Name Inst Attr Size Range Scaling Get Set B_01 Selection of automatic restart mode 1 101 1 0 Alarm output after trip no automatic restart 1 Restart at 0Hz 2 Resume opera tion after freq matching 3 Resume previous freq after freq matching then decelerate to stop and display trip info G S B_02 Allowable under voltage power failure time 1 10...

Page 86: ... 100 G S B_23 Deceleration rate at overload restriction 1 123 2 0 3 30 0 10 G S B_31 Software lock mode selection 1 131 1 0 all parameters except B_31 are locked if SFT is ON 1 all parameters except B_31 and output freq F_01 when SFT is ON 2 all parameters except B_31 are locked 3 all parameters except B_31 and F_01 are locked G S B_82 Start frequency adjustment 1 182 2 0 5 9 9 Hz 100 G S B_83 Car...

Page 87: ...y matching G S B_90 Dynamic braking usage ratio 1 190 2 0 0 100 0 10 G S B_91 Stop mode selection 1 191 1 0 Decel and stop 1 Free run stop G S B_92 Cooling fan control 1 192 1 0 Fan always ON 1 Fan ON during Run OFF during stop G S B Group Parameters DeviceNet Class ID 103 Func Code Name Inst Attr Size Range Scaling Get Set Supported Services DeviceNet Class ID 103 Service Name Code Description Ge...

Page 88: ...ate 1 113 1 0 normally open 1 normally closed G S C_21 Terminal 11 function 1 121 1 0 1 2 3 5 see manual Ch 3 G S C_22 Terminal 12 function 1 122 1 same as above G S C_31 Terminal 11 active state 1 131 1 0 normally open 1 normally closed G S C_32 Terminal 12 active state 1 132 1 0 normally open 1 normally closed G S C_41 Overload level setting 1 141 2 0 to 200 rated current in A 100 G S C_42 Frequ...

Page 89: ... 1 1 kW 6 1 5 kW 7 2 2 kW 8 3 0 kW 9 3 7 kW 10 4 0 kW 11 5 5 kW 12 7 5 kW 13 11 kW G S H203 Motor capacity 2nd setting 2 103 1 same as above G S H_04 Motor poles setting 1 104 1 0 2 poles 1 4 poles 2 6 poles 3 8 poles G S H204 Motor poles setting 2nd motor 2 104 1 same as above G S H_05 Motor constant Kp 1 105 1 0 99 1 G S H205 Motor constant Kp 2nd motor 2 105 1 0 99 1 G S H_06 Motor stabilizatio...

Page 90: ...otor constant R2 1 131 2 0 000 65 535Ω 1000 G S H231 Auto tuned motor constant R2 2nd motor 1 131 2 0 000 65 535Ω 1000 G S H_32 Auto tuned motor constant L 1 132 2 0 00 655 35mH 100 G S H232 Auto tuned motor constant L 2nd motor 2 132 2 0 00 655 35mH 100 G S H_33 Auto tuned motor constant Io 1 133 2 0 00 655 35A 100 G S H233 Auto tuned motor constant Io 2nd motor 2 133 2 0 00 655 35A 100 G S H_34 ...

Page 91: ...ip 1 Decel and trip 2 Hold last speed 3 Free run stop 4 Decel and stop G S P_46 DeviceNet polled I O Output instance number 1 146 1 20 21 100 1 G S P_47 DeviceNet polled I O Input instance number 1 147 1 70 71 101 1 G S P_48 Inverter action on DeviceNet idle mode 1 148 1 0 Trip 1 Decel and trip 2 Hold last speed 3 Free run stop 4 Decel and stop G S P_49 DeviceNet motor poles setting for RPM 1 149 ...

Page 92: ...ions and parameters that can be configured by the user We recommend that you record all parameters that have been edited in order to help in troubleshooting or recovery from a loss of parameter data Main Profile Parameters Inverter model MFG No SJ100 This information is printed on the specification label located on the right side of the inverter F Group Parameters Default Setting User Setting Func...

Page 93: ...15 A_24 Multi speed 4 setting 0 0 20 A_25 Multi speed 5 setting 0 0 30 A_26 Multi speed 6 setting 0 0 40 A_27 Multi speed 7 setting 0 0 50 A_28 Multi speed 8 setting 0 0 60 A_29 Multi speed 9 setting 0 0 0 A_30 Multi speed 10 setting 0 0 0 A_31 Multi speed 11 setting 0 0 0 A_32 Multi speed 12 setting 0 0 0 A_33 Multi speed 13 setting 0 0 0 A_34 Multi speed 14 setting 0 0 0 A_35 Multi speed 15 sett...

Page 94: ... 0 0 0 0 0 A_63 A_65 A_67 Jump center frequency setting 0 0 0 0 0 0 A_64 A_66 A_68 Jump hysteresis frequency width setting 0 5 0 5 0 5 A_81 AVR function select 02 00 02 A_82 AVR voltage select 230 400 230 460 200 400 A_92 Acceleration 2 time setting 15 0 15 0 15 0 A292 Acceleration 2 time setting 2nd motor 15 0 15 0 15 0 A_93 Deceleration 2 time setting 15 0 15 0 15 0 A293 Deceleration 2 time sett...

Page 95: ...e 00 00 00 B_02 Allowable under voltage power failure time 1 0 1 0 1 0 B_03 Retry wait time before motor restart 1 0 1 0 1 0 B_12 Level of electronic thermal setting Rated current for each inverter Rated current for each inverter Rated current for each inverter B212 Level of electronic thermal setting 2nd motor Rated current for each inverter Rated current for each inverter Rated current for each ...

Page 96: ...0 0 0 0 B_91 Stop mode selection 00 00 00 B_92 Cooling fan control 00 00 00 B Group Parameters Default Setting User Setting Func Code Name FE Europe FU USA F Japan C Group Parameters Default Setting User Setting Func Code Name FE Europe FU USA F Japan C_01 Terminal 1 function 00 00 00 C_02 Terminal 2 function 21 21 21 C_03 Terminal 3 function 12 12 12 C_11 Terminal 1 active state 00 00 00 C_12 Ter...

Page 97: ...ity Specified by the inverter capacity Specified by the inverter capacity H203 Motor capacity 2nd setting Specified by the inverter capacity Specified by the inverter capacity Specified by the inverter capacity H_04 Motor poles setting 4 4 4 H204 Motor poles setting 2nd motor 4 4 4 H_05 Motor constant Kp 20 20 20 H205 Motor constant Kp 2nd motor 20 20 20 H_06 Motor stabilization constant 100 100 1...

Page 98: ...ned motor constant R2 Factory set Factory set Factory set H231 Auto tuned motor constant R2 2nd motor Factory set Factory set Factory set H_32 Auto tuned motor constant L Factory set Factory set Factory set H232 Auto tuned motor constant L 2nd motor Factory set Factory set Factory set H_33 Auto tuned motor constant Io Factory set Factory set Factory set H233 Auto tuned motor constant Io 2nd motor ...

Page 99: ... enable 01 01 01 P_44 DeviceNet comm watchdog timer 1 00 1 00 1 00 P_45 Inverter action on DeviceNet comm error 01 01 01 P_46 DeviceNet polled I O Output instance number 100 100 100 P_47 DeviceNet polled I O Input instance number 101 101 101 P_48 Inverter action on DeviceNet idle mode 01 01 01 P_49 DeviceNet motor poles setting for RPM 00 00 00 Artisan Technology Group Quality Instrumentation Guar...

Page 100: ...key Initialization function selected 8 Press the key 00 initialization disabled clear trip history only 9 Press the key 00 clear trip history 01 initialize all settings 10 Press the key Initialization now enabled to restore all defaults 11 Press and hold the and keys Do not release yet First part of special key sequence 12 Holding the keys above press and hold the STOP key for 3 sec Final part of ...

Page 101: ...ss ID 100 to perform the unitization The parameters in Class IDs of 100 101 103 105 107 and 109 are initialized NOTE Executing the host Reset service causes the inverter to stop network communi cations similar to power on reset Therefore the network master will detect a time out error It cannot re connect to the inverter until the initialization is complete 3 4 sec NOTE A DeviceNet initialization ...

Page 102: ...l service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR MORE INFORMATION Visit us on the web at www artisantg com for more information on ...

Reviews: