Network Control and Monitoring
66
Polled I/O Configurations
SJ100DN inverters offer three host output and host input polled I/O data configurations.
These correspond to P_46 / P_47 = 20 / 70, 21 / 71, or 100 / 101. Each configuration
differs in its use of up to 4 output or 4 input words (other combinations can cause
network errors.) The DeviceNet networking example in the previous steps used the
default polled I/O configuration (P_46 = 100 and P_47 = 101). This section describes
each available polled I/O configuration.
Host Output Instance Configurations
– The tables below list the three configurations
for host output data (settable by P_46).
Inverter Consumed Data, (Host) Output Instance (P_46) = 20
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
—
—
—
—
—
Fault
Reset
—
FW Run
1
—
2
Output frequency (low byte), host override for F_01 value
3
Output frequency (high byte), host override for F_01 value
Inverter Consumed Data, (Host) Output Instance (P_46) = 21
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
—
Network
Refer-
ence
Network
Control
—
—
Fault
Reset
RV Run
FW Run
1
—
2
Output frequency (low byte), host override for F_01 value
3
Output frequency (high byte), host override for F_01 value
Inverter Consumed Data, (Host) Output Instance (P_46) = 100
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
—
Network
Refer-
ence
Network
Control
—
Free run
Stop
Fault
Reset
RV Run
FW Run
1
—
2
Output frequency (low byte), host override for F_01 value
3
Output frequency (high byte), host override for F_01 value
4
Acceleration time (low byte), host override for F_02 value
5
Acceleration time (high byte), host override for F_02 value
6
Deceleration time (low byte), host override for F_03 value
7
Deceleration time (high byte), host override for F_03 value
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com