26
ELECTRICAL WIRING
FXN(E)
No.0
No.1
No.2
(*) Operating Line (Twisted Shielded Pair Cable) or Twisted Cable DC5V (Non-Pole Transmission, H-LINK System)
16.5.
WIRE SIZES
Electrical Wiring Connection
Field Minimum Wire Sizes for Power Source
Power Source Cable Size
Transmitting Cable Size
Model
Power Source
Max. Current
EN60 335-1
MLFC
EN60 335-1
MLFC
All Indoor Units
220-240V/1
I
/50Hz
5 A
0.75 mm²
0.5 mm²
RAS-5FSN
8 A
2.5 mm²
0.75 mm²
RAS-8FSN(E)
14 A
2.5 mm²
0.75 mm²
RAS-10FSN(E)
18 A
2.5 mm²
1.25 mm²
RAS-16FSN
33 A
6 mm²
3.5 mm²
RAS-20FSN
37 A
-
3.5 mm²
RAS-24FSN
50 A
-
5.5 mm²
RAS-30FSN
66 A
-
8 mm²
RAS-8FXN(E)
14 A
2.5 mm²
0.75 mm²
RAS-10FXN(E)
18 A
2.5 mm²
1.25 mm²
RAS-16FXN
33 A
6 mm²
3.5 mm²
RAS-20FXN
37 A
-
3.5 mm²
RAS-24FXN
50 A
-
5.5 mm²
RAS-30FXN
380-415V/3
I
/50Hz
66 A
-
8 mm²
0.75 mm²
0.5 mm²
Outdoor Unit
Models:
RAS-8FXN(E)
RAS-10FXN(E)
RAS-16FXN
RAS-20FXN
RAS-24FXN
RAS-30FXN
No.0 System
Outdoor Unit
No.1 System
Outdoor Unit
No.2 System
Outdoor Unit
Operating Line (*)
Indoor Unit
Remote Control
Switch
: Terminal Board
: Printed Circuit Board
: Field Wiring
: Field Wiring
: Field-Supplied
: Optional Accessory
Main Switch
Earth Leakage
Breaker
No.0 System Indoor Units
Max. 20 Units per Refrigerant Cycle 16~20HP
Max. 27 Units per Refrigerant Cycle 24HP
Max. 32 Units per Refrigeant Cycle 30HP
No.1 System
Indoor Units
Remote Control
Switch
Indoor Unit
Indoor Unit
Remote Control
Switch
No.0 Group
CH Unit
No.0 Group
CH Unit
No.1 System
CH Unit