SAFETY AND CONTROL DEVICE SETTING
19.
SAFETY AND CONTROL DEVICE SETTING
Safety and Control Device Setting for Indoor Units
Model
RCI
RCD
RPC
RPI
RPK
RPF
RPFI
Remarks
For Evaporator Fan Motor
Internal Thermostat
Cut-Out
Cut-In
°C
°C
145±5
90±15
130±5
83±15
135±5
90±15
140±5
90±15
130±5
83±15
130±5
83±15
130±5
83±15
Automatic Reset, Non-
adjustable (each one
for each motor)
For Control Circuit
Fuse Capacity
A
5
Freeze Protection
Thermostat
Cut-Out
Cut-In
°C
°C
0
14
Thermostat Differential
°C
2
Safety and Control Device Setting for Outdoor Units
Model
RAS-5
RAS-8
RAS-10
RAS-16
RAS-20
RAS-24
RAS-30
Automatic Reset, Non-Adjustable
(each one for each compressor)
For Compressor
Pressure Switches
High Cut-Out
MPa
05
.
0
15
.
0
4.15
Cut-In
MPa
3.20
r
0.15
Fuse
3~, 380/415, 50Hz
A
20x2
20x4
20x4
20x6
20x8
20x10
20x12
FSN
40
40 x 3
40 x 4
40 x 5
40 x 6
Oil Heater
Capacity
FXN
W
-
40 x 2
40 x 2
40X4
40 x 5
40 x 6
40 x 7
Non-Adjustable
CCP Timer
Setting Time
min
3
3
3
3
3
3
3
Automatic Reset, Non-Adjustable
(each one for each compressor)
For Condenser Fan Motor
Internal Thermostat
Cut-Out
Cut-In
ºC
ºC
130
r
5
83
r
15
130
r
5
83
r
15
130
r
5
83
r
15
130
r
5
83
r
15
130
r
5
83
r
15
130
r
5
83
r
15
130
r
5
83
r
15
For Control Circuit
Fuse Capacity on
PCB
A
12
12
12
12
12
12
12
CCP Timer: Enforced 3 minutes operation and stoppage.