
ENGLISH
12 MAIN SAFETY DEVICES
Compressor Protection
The compressor is protected by the following devices and their combinations.
• High Pressure Switch: This switch cuts out the operation of the compressor when the discharge pressure exceeds the setting.
Oil Heater: This band type heater protects against oil foaming during cold starting, as it is energized while the compressor is
stopped.
AC Fan Motor Protection
Internal thermostat: Embedded in the fan motor winding, this internal thermostat cuts out the operation of the fan motor when the fan
motor winding temperature exceeds the setting.
Safety and control device setting for outdoor units
Model
RAS-8FSNM
RAS-10FSNM
RAS-12FSNM
For compressor
Automatic Reset, Non-Adjustable
Pressure switch
(each one for each compressor)
High
Cut-out
MPa
4.15
-0.05
4.15
-0.05
4.15
-0.05
-0.15
-0.15
-0.15
Cut-in
MPa
3.20±0.15
3.20±0.15
3.20 ±0.15
Fuse capacity
A
40
40
40
3N~ 400V 50Hz
CCP timer
Non-Adjustable
Setting time
min.
3
3
3
For condenser AC fan motor
Automatic Reset, Non-Adjustable
Internal thermostat
(each one for each motor)
DC
Cut-out
ºC
125±5
125±5
125±5
AC
Cut-out
ºC
150±5
150±5
150±5
Cut-in
ºC
150±5
150±5
150±5
For control circuit
Fuse capacity PCB1,5
A
5
5
5
Fuse capacity PCB3
A
10
10
10
CCP Timer: Enforced 3 minutes operation and stoppage.
MAIN SAFETY DEVICES
PMML0390B REV.0 - 11/2015 - P5416649
23