2
Obstacles on discharge side
a.
Upper side is open
(mm)
Single Installation
Multiple Installation
?
N O T E
Mount the airflow guide (*1) and open both right and left sides.
Fit positions " " with unit back side
Front side
?
N O T E
Mount the airflow guide (*1) and open both right and left sides.
?
N O T E
Mount the airflow guide (*1) and
open both right and left sides.
?
N O T E
Mount the airflow guide (*1)
and open both right and left
sides.
No more than 2 units for
multiple installation
(*1): Optional Part
3
Obstacles on right and left
a.
Upper side is open
(mm)
Single Installation
b.
Obstacles in above
(mm)
Single Installation
?
N O T E
• If L is higher than H, mount the units on a base so that H is greater or equal to L. H: Unit Height (1650mm) + Base Concrete Height
• In this situation ensure that the base is closed and does not allow the airflow to short circuit. In each case, install the outdoor unit so that the
discharge flow is not short-circuited.
L
A
0 < L < 1/2H
600 or more
1/2H < L < H
1400 or more
UNITS INSTALLATION
PMML0390B REV.0 - 11/2015 - P5416649
8