10.3 ELECTRICAL WIRING BETWEEN INDOOR UNIT AND OUTDOOR UNIT
Connect the electrical wires between the indoor unit and the outdoor unit, as shown in next figure
Check to ensure that the terminal for power source wiring (terminals “L1” to “L1” and “N” to “N” of each terminal board) and
intermediate wiring (Operating Line: terminals “1” to “1” and “2” to “2” of each terminal board: DC5V) between the indoor unit and the
outdoor unit coincide correctly. If not, some component will be damaged.
1
Use shielded wires (≥0.75mm
2
) for intermediate wiring to protect electrically noise obstacle at length of less than 1,000m and
size complied with local code.
2
Open a hole near the connection hole of power source wiring when the multiple outdoor units are connected from one power
source line.
3
The recommended breaker sizes are shown in the table of selecting the main switches.
4
In the case that a conduit tube for field-wiring is not used, fix rubber bushes with adhesive on the panel.
ELB
FUSE
3N
400V 50Hz
1N
220-240V 50Hz
230V 50Hz
ELB
ELB
TB1
TB2
L1 L2 L3 N
1 2
TB1
TB2
L1 L2 L3 N
1 2
TB1
TB2
L1 L2 L3 N
1 2
1 2 A B
TB2
1 2 A B
TB2
TB1
TB1
L1 L2 N
L1 L2 N
TB
PCB :
:
:
:
Terminal Board
Printed circuit board
Field wiring
Field supplied
Optional accessory
Remote
control switch
(PC-ART)
Nº 0 Indoor
unit
Nº 1 Indoor
unit
Remote
control cable
(Shielded
twist pair
cable)
Remote
control cable
(Shielded
twist pair
cable)
Nº 0 System indoor units
Main switch
Nº 1 System indoor units
Remote
control switch
(PC-ART)
Operating line (shielded twist pair cable)
DC5V (Non-pole transmission H-LINK II system)
Operating line (shielded twist pair cable)
DC5V (Non-pole transmission H-LINK system)
Distribution box or pull box Distribution box or pull box
Max 1 Outdoor Unit / Power Supply Line
The power source for outdoor units mus be made individually. If not, fire may occur in the worst case.
10.4 WIRE SIZE AND MAIN BREAKER SWITCH
Electrical wiring connection. Field minimum wire sizes for power source
Model
Power Source
Maximum
Current
(A)
Power Source
Cable Size
Transmitting
Cable Size
CB(A)
ELB
Nº poles/A/mA
EN60 335-1
EN60 335-1
All indoor units
1~ 230V 50Hz
5.0
0.75 mm
2
0.75mm
2
6
2/40/30
RPI-(8.0/10.0)FSN2E
10.0
1.5 mm
2
16
RAS-8FSNM
3N~ 400V 50Hz
14.0
2.5 mm
2
0.75mm
2
20
4/20/30
RAS-10FSNM
18.0
4.0 mm
2
30
RAS-12FSNM
23.0
4.0 mm
2
30
ELECTRICAL WIRING
PMML0390B REV.0 - 11/2015 - P5416649
18