– 81 –
Yes
Outdoor fan
rotates
Outdoor fan rotates normally
heavy. Check the compressor.
Check the electric expansion valve.
Clean the filter.
The compressor may be too hot. Check to
see that the coolant is not leaking.
to the recommended conditions.
Replace the fan motor.
Outdoor fan rotates,
but soon stops.
No problems
with installation
position
No coolant leak
Abnormal
Normal
Coolant leak
Normal
Coolant leak
Yes
LD301: Blinks five times
Overload stop
Insert the power source and operate, and
then check to see that the outdoor fan is
rotating
No
No
LD 301: Blinks six times
Overheating stop
Yes
No
LD301: Blinks eight times
Acceleration abnormally
LD301: Blinks fourteen times
ACT error
Yes
No
LD301: Blinks thirteen times
E
2
PROM error
The protection circuit may
cause the fan to stop when
the wind is extremely strong
in the place where the
outdoor unit is installed or
when the outdoor unit is
covered.
Refil the coolant
Check the compressor.
NO CHANGE
(still same)
Replace MAIN P.W.B..
NO CHANGE
(still same)
Check the compressor.
Replace POWER P.W.B..
Replace the electric expansion valve.
There is the possibility that the electric expansion valve
may not be working.
Check the voltage between BEN-12V and BEN-OV
Refil the coolant
Replace the MAIN P.W.B..
The SPM2 is broken. Replace the SPM2.
There is the possibility that the cycle load may have become extremely
Check the position of the outdoor unit. If there is a problem, install according
The compressor does not accelerate.
Check to see that the coolant is not
leaking.
Summary of Contents for RAM-130QH5
Page 10: ... 11 SIX ROOM SYSTEM MULTI R A C RAM 130QH5 CONNECTING POSISION TO BE ABLE TO INSTALL ...
Page 20: ... 22 CAPACITY DIAGRAM RELATED TO THE PIPING LENGTH MODEL RAM 130QH5 ...
Page 25: ... 29 6V01 ...
Page 26: ... 31 ...
Page 28: ... 35 ...
Page 33: ... 41 Outdoortemperature STAROTP_C TSKTM1_C1 Outdoortemperature STAROTP_C TSKTM1_C2 ...
Page 34: ... 43 ...
Page 35: ... 45 ...
Page 36: ... 47 ...
Page 37: ... 49 ...
Page 47: ... 59 5A ...
Page 54: ... 66 ...
Page 55: ... 67 5 Reversing valve control circuit Fig 5 1 ...
Page 77: ... 92 TROUBLESHOOTING OF THE SYSTEM POWER MODULE ...
Page 78: ... 93 ...
Page 79: ... 94 ...
Page 83: ... 98 ...
Page 84: ...HITACHI PM NO 0000 Printed in Malaysia RAM 130QH5 ...