– 78 –
Inspection method 1
Insert the power source, and check to see that the
LED is on at electrical unit 1 or electrical unit 2.
Is the 25A fuse working normally?
Is the 5A fuse working normally?
Yes
Yes
Yes
Yes
No
No
No
No
LED on
LED off
The control P.W.B. is broken.
Replace the control P.W.B.
Is AC220~240V flow to the L/N (A/B) terminal?
Follow "Inspecting external electrical parts" and check
the cause of the problem.
Connect a commercial-use 220-240V power source
to the L/N (A/B) terminal.
Replace the broken part
and the 25A fuse.
The control power source is broken.
Replace the control P.W.B.
Is varistor 2 broken?
There is the possibility that an irregular voltage has been
flowing to the L/N (A/B) terminal. Check to see that the
power source is not abnormality.
Replace the 5A fuse and varistor 2.
Check to see that varistors 1-3,
diode stacks SPM2 are not
broken.
Summary of Contents for RAM-130QH5
Page 10: ... 11 SIX ROOM SYSTEM MULTI R A C RAM 130QH5 CONNECTING POSISION TO BE ABLE TO INSTALL ...
Page 20: ... 22 CAPACITY DIAGRAM RELATED TO THE PIPING LENGTH MODEL RAM 130QH5 ...
Page 25: ... 29 6V01 ...
Page 26: ... 31 ...
Page 28: ... 35 ...
Page 33: ... 41 Outdoortemperature STAROTP_C TSKTM1_C1 Outdoortemperature STAROTP_C TSKTM1_C2 ...
Page 34: ... 43 ...
Page 35: ... 45 ...
Page 36: ... 47 ...
Page 37: ... 49 ...
Page 47: ... 59 5A ...
Page 54: ... 66 ...
Page 55: ... 67 5 Reversing valve control circuit Fig 5 1 ...
Page 77: ... 92 TROUBLESHOOTING OF THE SYSTEM POWER MODULE ...
Page 78: ... 93 ...
Page 79: ... 94 ...
Page 83: ... 98 ...
Page 84: ...HITACHI PM NO 0000 Printed in Malaysia RAM 130QH5 ...