2. Name of each portion (removed front cover)
Name
Description
①
Connector for dedicated operator
for NES1-OP
Dedicated operator for NE-S1 (NES1-OP) can be connected on this connector.
②
RUN/STOP/RESET key
Push key for run, stop and reset operation.
③
Intelligent relay terminal
Output terminal for intelligent relay (1 from c contact).
④
Main terminal
For connecting power supply, motor output and DC reactor.
⑤
Switch for termination resistor
Switch for integrated termination resistor (100
Ω
) for RS485.Integrated resistor of 100
Ω
is
connected when switched ON.
⑥
Switch for RS485/OPE
Changeover switch for RS422/RS485 communication setting.
⑦
RS422/RS485 port
Connector for RS485 external operator or PC software (RJ45 jack)
⑧
Switch for O/OI (analog input)
changeover
Voltage input (O) or current input (OI) can be selected using this switch.
⑨
Logic terminal A,B
Terminal for connecting input/output signals (digital/analog) for the inverter control.
⑩
Charge lamp
Turns ON when the internal DC bus voltage is 45V or more.
In case of wiring, maintenance or else, please be sure to check that this lamp is turned OFF
after waiting 10 minutes of power OFF.
Note
1
) Refer to page 13 for the description of the display and key operation.
Note 2) Position of
⑩
charge lamp depends on the model. Refer to page 11 for the details.
Note 3) Pay attention when operating by PC via
⑦
RS422/RS485 port, as the operation can also be done from the panel of the inverter.
Note 4) Be sure to turn power OFF when connecting or disconnecting the operator such as OPE-SRmini,OPE-S,WOP to the
⑦
RS422/RS485
port.
3. Cautions for installation
①
Caution during transportation
Please pay attention when carrying the product as it is covered by a plastic case.
Especially, do not put pressure onto the front cover and terminal cover. Otherwise there is a risk of damaging the product.
Please do not use products that are damaged, and/or lacking components.
⑥
Switch for RS485/OPE SW5
⑤
Switch for termination resistor SW4
⑦
RS422/RS485 port
②
RUN/STOP/RESET keys
④
Main terminal
⑨
Logic terminal A
P8 to 9
⑧
Switch for O/OI (analog input)
changeover SW6
⑨
Logic terminal B
③
Intelligent relay terminal
⑩
Charge indicator lamp
①
Connector for dedicated
operator for NES1-OP
P8 to 9
OFF
(Default)
ON
P9
RS485
OPE
(Default)
→
P9
Voltage O
(Default)
Current OI
P9
P8 to 9