6 MAINTENANCE
6-10
6.3.3 Communication
errors
(1) Network errors
When an error was found on the network of the IR.LINK module, the status error flag of the
NET status and the ALM of the S-register is turned ON and write error code (see table
below) into S-table.
In the S10mini, the following “error code” is displayed on the indicator of the CPU module.
In the S10V, an error code (ex. 0x7110) with “0x” appended to the beginning of the
following error code is displayed by selecting the error log from the S10V BASE SYSTEM.
Table 6-3 IR.LINK Module Network Error Table
Error code
Explanation
User response
7110
An undefined service was instructed.
•
If this error recurs even after the CPU (or LPU) has been
reset once and then set to the original position again,
restart the IR.LINK module.
•
If this error still recurs, replace the IR.LINK module.
7120
The data length is incorrect.
7130
The packet configuration is incorrect.
2010
An error was detected during CRC check.
•
Check whether the network line is normal.
•
Check whether SVPT setting matches station setting.
•
If this error still recurs, replace the IR.LINK module.
2020
The station number is from 128 to 254 or
the received station number is incorrect.
2030
An undefined service was specified.
2040
The I-frame length is greater than or equal
to 137 bytes or the UI-frame length is
greater than or equal to 134 bytes.
2041
No I-frame exists in the I-response.
2042
An I-frame exists in the monitoring frame.
2050
Data link procedure error
2060
A timeout was detected (no response was
made from the slave station within the
specified time).
•
Power on the station again.
•
Check whether the switches of the IR.LINK module and
station are set correctly.
•
If this error still recurs even after the switches have been
set correctly, replace the station.
2061
The error could not be recovered by retry.
2070
No frame could be transmitted to the line or
an error was detected during frame
reception.
•
Check the network line connection and terminating
resistor connection.
•
Check whether SVPT setting matches station setting.
•
If this error recurs even after the CPU (or LPU) has been
reset once and then set to the original position again,
restart the IR.LINK module.
•
If this error still recurs, replace the IR.LINK module.
2080 Other
errors
•
If this error recurs even after the CPU (or LPU) has been
reset once and then set to the original position again,
restart the IR.LINK module.
•
If this error still recurs, replace the IR.LINK module.
Summary of Contents for IR.LINK
Page 1: ......
Page 2: ......
Page 15: ...This Page Intentionally Left Blank ...
Page 25: ...This Page Intentionally Left Blank ...
Page 26: ...1 SPECIFICATIONS ...
Page 30: ...2 NAMES AND FUNCTIONS OF EACH PART ...
Page 33: ...This Page Intentionally Left Blank ...
Page 34: ...3 MOUNTING AND WIRING ...
Page 43: ...This Page Intentionally Left Blank ...
Page 44: ...4 OPERATION ...
Page 68: ...5 USER GUIDE ...
Page 86: ...6 MAINTENANCE ...