6 MAINTENANCE
6-9
6.3.2 Hardware
errors
When the IR.LINK module detects a hardware error, the following contents of the “CPU display”
are displayed on the indicator of the CPU module in the S10mini. In the S10V, the following
error codes are displayed by selecting the error log from the S10V BASE SYSTEM.
In any case, the IR.LINK module operation is stopped.
Table 6-2 IR.LINK Module Hardware Error Table
CPU display
(S10mini)
Error code
(S10V)
Contents
Action to be taken
BUS
0x0010
Bus error
The IR.LINK module may be faulty.
Replace the module.
ADDR 0x0011 Address
error
ILLG
0x0012
Illegal instruction error
ZERO
0x0013
Division by zero error
PRIV 0x0014
Privilege
violation
WDT 0x0015
WDT
error
FMAT 0x0016 Format
error
SINT 0x0017
Spurious
interrupt
EXCP 0x0018 Unused
exception
PTY 0x0019
Parity
error
MDSW
0x0100
Module number switch setting error
Check the module number switch setting.
BRSW
0x0101
Bit rate switch setting error
Check the bit rate switch setting.
ROM1
0x0102
ROM1 sum error
The IR.LINK module may be faulty.
Replace the module.
RAM1
0x0103
RAM1 compare error
RAM2
0x0105
RAM2 compare error
ROM3
0x010B
ROM3 sum error
ROME
0x010C
ROM erase error (program)
0x010E
ROM erase error (parameter)
ROMW 0x010D ROM
write
error
(program)
0x010F
ROM write error (parameter)
WOVR
0x0110
ROM rewrite count over
The ROM rewrite count exceeds 50,000
times. Replace the module.
PRME
0x0112
Parameter error
Set the parameter again. For details, see the
Note in the following frame.
For the starting method for the S10V basic system and the display method for error log
information in the S10V, refer to the “USER’S MANUAL BASIC MODULE (Manual number
SVE-1-100).”
NOTICE
A parameter error of LQE546 occurs when hardware is mounted in a different
system from the system in which the parameters shown in “4.3 Commands”
were set.
When parameters are set in the S10V and hardware is installed in an S10mini
unit:
“IRM PRME” (“IRS PRME”) is displayed on the CPU indicator.
When parameters are set in the S10mini system and hardware is installed in an
S10V unit:
0x112 (error code that is displayed by error log of the S10V BASE SYSTEM)
This error is intended to prevent a malfunction by referring to the parameters set
in a different model.
If this error occurs, set the parameters (definition information) in the installed
model.
Summary of Contents for IR.LINK
Page 1: ......
Page 2: ......
Page 15: ...This Page Intentionally Left Blank ...
Page 25: ...This Page Intentionally Left Blank ...
Page 26: ...1 SPECIFICATIONS ...
Page 30: ...2 NAMES AND FUNCTIONS OF EACH PART ...
Page 33: ...This Page Intentionally Left Blank ...
Page 34: ...3 MOUNTING AND WIRING ...
Page 43: ...This Page Intentionally Left Blank ...
Page 44: ...4 OPERATION ...
Page 68: ...5 USER GUIDE ...
Page 86: ...6 MAINTENANCE ...