(APPENDIX I) PARAMETERS TABLE |
PAGE 64
Table 12
Parameters clearance selector Table
Parameter PSW Description
Default
value
Range
1
2
Signal type clearance 1
1
0- Three-phase without
neutral
1- Three-phase
2- Two-phase
3- Single-phase
4- Delta with neutral
5- Delta without neutral
6- Two-phase selector
2
2
Maximum Unit Voltage clearance 1
440V
3
2
Minimum Unit Voltage clearance 1
360V
4
2
Maximum generator current clearance 1
1000A
5
2
Short circuit detection clearance 1
3000A
6
2
Maximum Unit Frequency clearance 1
58Hz
7
2
Minimum Unit Frequency clearance 1
45Hz
8
2
Signal type clearance 2
1
0- Three-phase without
neutral
1- Three-phase
2- Two-phase
3- Single-phase
4- Delta with neutral
5- Delta without neutral
6- Two-phase selector
9
2
Maximum Unit Voltage clearance 2
440V
10
2
Minimum Unit Voltage clearance 2
360V
11
2
Maximum generator current clearance 2
1000
Amps
12
2
Short circuit detection clearance 2
3000
Amps
13
2
Maximum Unit Frequency clearance 2
58Hz
14
2
Minimum Unit Frequency clearance 2
45Hz
15
2
Engine speed clearance 1 (only option CEM7J)
1500
rpm
0..10000 rpm
16
2
Speed J1939 clearance 2 (only option CEM7J)
1500 rpm 0..10000 rpm
17
2
Nominal Power of the genset clearance 1
220 kW
18
2
Nominal Power of the genset clearance 2
220 kW
19
2
Minimum engine speed clearance 1
1350
20
2
Maximum engine speed clearance 1
1740
21
2
Minimum engine speed clearance 2
1350
22
2
Maximum engine speed clearance 2
1740
Parameter PSW Description
Default value
Range
22
2
Input associated to AL4 mode
0
0- Not programmed
2- BPA (option CEM7J)
3- ATA (option CEM7J)
4- NA (option CEM7J)
5- ENT4
6- ENT5
8- ENT1
9- ENT2
10- ENT3
17- Extension ENT1
18- Extension ENT2
19- Extension ENT3
20- Extension ENT4
23
2
Input associated to AL5 mode
0
24
0
-
-
25
2
Input associated with gas train
checking mode
0
Table 11
Programmable output genset alarms allocation
Contents
Alarm
32
Water temperature
33
Oil pressure
34
Emergency stop
35
Alternator batteries
36
Starting failure
37
Water level
38
Fuel reserve
39
Overspeeding
40
Under Speed
41
Overload
42
Asymmetry
43
Maximum genset voltage
44
Maximum genset frequency
45
Phase sequence
46
Reverse Power
47
Battery voltage
48
Water temperature (sensor)
49
Oil pressure (sensor)
50
Fuel level
51
Short Circuit
52
Minimum genset voltage
53
Minimum genset frequency
54
Unexpected stop
55
Stop failure
Contents
Alarm
56
Low Engine Temperature
57
Unit failure
58
Programmable 1
59
Programmable 2
60
Programmable 3
61
Com switching
62
Rental counter
63
Maintenance counter
64
Programmable 4
65
Programmable 5
66
Auxiliary battery
67
Battery high voltage
68
Start battery low voltage
69
Unit contactor
70
Unit power
71
Temperature probe 1
72
Temperature probe 2
73
Temperature probe 3
74
Temperature probe 4
75
J1939
76
Temperature probe 1
77
Temperature probe 2
78
Temperature probe 3
79
Temperature probe 4