OPERATING MODES |
PAGE 10
3. OPERATING MODES
3.1 MANUAL MODE
In manual mode, the control unit is commanded by the user via the front panel of
the display module. The user can start and stop the engine by pressing the
START and STOP keys respectively.
Pressing the START key initiates the engine starting procedure (without
deactivating the network contactor CEM7 + CEA7CC2). Pressing the STOP key
initiates the engine stopping procedure with cooling; a second press of the STOP
key causes the engine to stop immediately without waiting for the cooling time.
x 1 click
WITH cooling
x 2 (double click)
WITHOUT cooling
NOTE
In manual mode, the control unit's protection devices remain active, being able
to produce alarms that cause the motor to stop.
In manual mode, the control unit does not take into consideration the start
conditions (programmed, by external signal) that can be programmed.
Activation of the genset contactor on the CEM7P display module is performed by
pressing the GENSET key.