(APPENDIX I) PARAMETERS TABLE |
PAGE 58
Parameter PSW Description
Default
value
Range
19
2
Phase voltage as starting condition
3
0- No consultation
1- Motor started
2- Motor stopped
3- Motor started/stopped
20
2
Alternator voltage as starting condition 1
21
2
PICK-UP input as starting condition.
3
22
2
BPA input as starting condition
2
23
2
Voltage transformer
0
0- Not installed
1- Transformer 400/600
24
2
Position of current measured.
0
0- Unit panel
1- Output line
25
3
Management of forced operation
0
0- Not permitted
1- Starting due to network
failure
2- Starting due to forced
operation.
26
2
Ratio engine flywheel ring gear speed
and genset voltage frequency
0
0-50 Hz / 1500 rpm
60 Hz / 1800 rpm
1-50 Hz / 3000 rpm
27
2
Temperature display
0
0-Celsius
1-Fahrenheit
28
2
Pressure display
0
0-Bars
1-Psi
29
3
Type of analogue sensors
0
See table
Analogue sensors
30
2
Selection of control unit type
0
0-Manual
1-Automatic
31
2
External start configuration
(display: ver. 4.46; measurements ver.
4.00 or higher)
0
0-Alarm delay
1-Immediate start
2-Delay without AL output
activation
3-Immediate start without AL
activation
NOTE
After modifying parameter 30 the control unit must be reset by disconnecting its
power, to allow the updating of its operating mode.
Table 3
Regulations Table
Parameter PSW Description
Default
value
Range
1
2
Fuel transfer pump operating mode
3
0-Off
1-Manual
2-Automatic
3-Control unit mode/
Combined mode
2
2
Default Starting Mode
1
0-Locked
1-Manual
2-Automatic
3-Test
3
2
Deactivation of D+
0
0-Alternator
1-Dynamo
4
2
Configuration of the LV relay output
1
0-Inhibited
1-Fuel transfer pump
2-Heating resistance
3-Thermal protection
5
2
Configuration of the RC input
1
0-OFF
1- Normally open
2- Normally closed
6
2
Configuration of the BPA input
1
7
2
Configuration of the ATA input
1
8
2
Configuration of the NA input
1
9
2
Configuration of the ENT4 input
1
10
2
Configuration of the ENT5 input
1
11
2
Configuration of the PEM input
2
12
2
Configuration of the ENT1 input
1
13
2
Configuration of the ENT2 input
1
14
2
Configuration of the ENT3 input
1
15
2
Configuration of the SETA1/PC input
2
16
2
Input associated with the AUX1 LED on
the display module
0
0- Not programmed
1- RC
2- BP
3- AT
4- NA
5- ENT4
6- ENT5
7- PE
8- ENT1
9- ENT2
10- ENT3
17
2
Input associated with the AUX2 LED on
the display module
0
18
2
Configuration of the preheating and config-
urable stop outputs
0
0- PD/PR
1- PE/PR
2- PD/PE
3- PULL/HOLD
4- GAS