© Hills Industries 2006
Page 31
Data
Default Zone Configuration (Zones 21-30 are not reprogrammable)
21
Instant: Partial – Twin Trip
– Produces an instant alarm if tripped when armed. Ignored when
disarmed. This zone will be bypassed in partial mode. This zone type will require two triggers or
another zone would have to have been trigged before it will activate an alarm.
22
Instant: Partial – Group Bypass
– Produces an instant alarm if tripped when armed. Ignored when
disarmed. This zone will be active in partial mode. This zone type will be part of the group bypass
zones.
23
Instant: Twin Trip – Group Bypass
– Produces an instant alarm if tripped when armed. Ignored
when disarmed. This zone will be bypassed in partial mode. This zone type will require two triggers
or another zone would have to have been trigged before it will activate an alarm. This zone type will
be part of the group bypass zones.
24
Instant: Partial – Twin Trip – Group Bypass
– Produces an instant alarm if tripped when armed.
Ignored when disarmed. This zone will be active in partial mode. This zone type will require two
triggers or another zone would have to have been trigged before it will activate an alarm. This zone
type will be part of the group bypass zones.
25
Instant: Local
– Produces an instant alarm if tripped when armed. Ignored when disarmed. This
zone will be bypassed in partial mode. This zone will not activate the communicator.
26
24 Hour: Audible
–
A trip on a 24 Hour zone produces an instant alarm when armed or disarmed.
This zone type will set sirens.
27
24 Hour: Silent
–
A trip on a 24 Hour zone produces an instant alarm when armed or disarmed. This
zone type will not set sirens.
28
Fire:
– A short on a fire zone will create an alarm condition when the system is armed or disarmed.
An open will create a Trouble condition. Requires smoke detectors wired Normally Open. Code pad
zone LED is steady for fire condition and flashing for trouble condition. After a fire activation,
press
[*]
[7]
on the code pad to clear & reset fire zone. Note: 120 seconds of chamber full = alarm.
29
Day Zone:
– When armed, a trip produces an instant alarm. When disarmed, a trip activates the
code pad sounder.
30
Key-Switch:
– A zone attached to a momentary key switch will cause the panel to arm or disarm
when the zone is momentarily shorted from a sealed condition I.e. a 3.3K resister must be used to
seal the zone for the option to work. Note: If DEOL monitoring is enabled in system options, this
zone type must have its EOL configuration as all other DEOL zones. I.e. Two 3.3K resistors must be
used to allow full line monitoring for this zone type.
Feature 19
Zone Area Select - Zones 1-8
Feature 19 is used to select the area(s) that zones 1 - 8 reside in. A zone may reside in any combination of the eight areas.
If a burglary zone resides in more than one area, it will only be active when all areas it resides in are armed. A zone that
resides in more than one area will be reported to its lowest area number. Feature 19 has 8 segments. Segment 1
corresponds to zone 1, and Segment 8 corresponds to zone 8.
Area 1
Area 2
Area 3
Area 4
Area 5
Area 6
Area 7
Area 8
Segment 1 – Zone 1
(1) 2 3 4 5 6 7 8
Segment 2 – Zone 2
(1) 2 3 4 5 6 7 8
Segment 3 – Zone 3
(1) 2 3 4 5 6 7 8
Segment 4 – Zone 4
(1) 2 3 4 5 6 7 8
Segment 5 – Zone 5
(1) 2 3 4 5 6 7 8
Segment 6 – Zone 6
(1) 2 3 4 5 6 7 8
Segment 7 – Zone 7
(1) 2 3 4 5 6 7 8
Segment 8 – Zone 8
(1) 2 3 4 5 6 7 8
Zones 9 – 16 Configuration
Feature 20
Zones 9-16 Configuration Group
Segments 1-8
16
16
16
16
16
16
16
16
Feature 20 contains the Configuration Group (zone type) for zones 9-16. Segment 1 is for zone 9, and Segment 8 is for
zone 16. Refer to the ‘Default Zone Configuration’ table in this section for zone type selections.