background image

12

EURO 46 V10 Programming Manual

Change Inputs?

By default, all inputs are set to ‘unused’. Before programming, identify the input type required:

PLEASE NOTE:

 

A full list of all input types can be found in ‘Appendix 1’.

Choose Input

Choose an input to program.

Input Type

: Assign an input type to the chosen input. For a full list of input types, please refer to 

‘Appendix 1’.

Input Areas: 

Enter the areas (0,1,A,B,C,D) for input to operate in. 

Input Areas (Any or All)

In some installations a ‘common’ area may be required. A common area is an area that only sets 
when other specific areas become set. Example: An entry and exit reception area in a building may 
only need to be set if both the offices and warehouse are set. If the office in Area A is set, but the 
warehouse in Area B is still occupied, then the reception would still need to be inactive so people 
would be able to leave the premises via the entry / exit reception route. One input can be allocated 
to one or more areas. In this example the inputs located in the reception area will be programmed so 
that the reception inputs will be in Area A and Area B, so these inputs must have the Input Areas set 
as ‘ALL’ programmed.

Area A: Office - Inputs = 3, 4, 5
Area B: Warehouse - Inputs = 6, 7, 8

Reception inputs – 1 and 2 are programmed into both Areas A and B, with both inputs configured as 
‘ALL’. The Reception Area inputs will now only become active if both Area A and Area B are both set.

Input Attributes

Attribute

Operation for both wired and wireless inputs

Chime

When enabled the system loudspeaker(s) will ‘chime’ when an input is triggered while the alarm panel is 
unset. Chime can be set to ‘single’ (sounding once) or ‘follow’ (sounding while the door is left open). NOTE: 
The chime can be turned on or off in unset mode by pressing [c] when all Entry Delay inputs are closed.

Omittable

Enables the input to be manually omitted (disabled) from the setting procedure. To omit inputs, there is a 
function in the Master Manager menu called ‘OMIT INPUTS’.

Double Knock

If enabled, if this input is triggered twice within the pre-programmed time window or if the input remains active 
for that period, an alarm will be generated. The double knock option does not work on ‘Follow’ input type.

Dual Trip

The control panel will only generate an alarm if this input, and another like-programmed input (with adjacent 
number), are in alarm condition at the same time. Either input in alarm condition will prevent the system from 
setting.

Normally Open

#

Enables the system to respond correctly when detectors of ‘normally open’ configuration are wired to the 
system. Alternatively converts input types which default to ‘normally open’ (such as Push to set) to operate 
with normally closed devices.

Walk Test

If enabled, a walk test will need to be done on the particular input before the system can be set.

Monitor Activity

This option is used in conjunction with NAT (none activity timer) in the ‘CHANGE TIMERS’ menu. When 
enabled this option will trigger an output once the NAT time has elapsed. An example scenario in which it 
might be used: A security guard who is obligated to walk a set route every hour – could be monitored by a 
detector (with this input attribute enabled). Failure to walk the route would activate an output, perhaps to a 
communications device, siren or light.

Special Log

Forces a log entry when the input is opened or closed, even when an alarm does not result. May be selected 
to apply when a system is set, when unset, or always.

Summary of Contents for Pyronix EURO 46 V10

Page 1: ...EURO 46 V10 Programming Manual RINS1942 1 Software Version 10 PD6662 2010 IA501 2015 EN50131 1 2008 A1 2009 EN50131 3 2009 Security Grade SG 3 Large Security Grade SG 2 Small Environmental Class EC II...

Page 2: ...Change Outputs 15 Assign Keypads and Readers 15 Change Timers 20 Codes And Users 22 Volume Control 23 System Options 24 Review Logs 26 Engineer Tests 26 Diagnostics 28 Engineer Restore Options 31 Comm...

Page 3: ...3 EURO 46 V10 Programming Manual Appendix 1 Input Types 43 Appendix 2 Output Types 45 Appendix 3 SMS Commands 48 Appendix 4 Factory Defaults 50 Appendix 5 Event Types SIA and Contact ID codes 57...

Page 4: ...ore the device stops working This key feature gives you enough time to change the battery in the specific device Conventional wireless alarm systems may not give you a low battery warning signal meani...

Page 5: ...d smoke detectors Customise and receive push notifications from your system Have instant access to your events and history log Control appliances such as lights garage doors gates and blinds All using...

Page 6: ...enu item will be in lower case letters In order to navigate in the menu system answer the questions in the main and sub menus For example if the question WIRELESS DEVICE CONTROL is displayed then pres...

Page 7: ...lowing Inputs 2 labels Input Number and Location Area names Site name Keypad Reader 2 labels Keypad number and location Input and output expander location descriptions User names The control panel inc...

Page 8: ...h For March enter 03 Change Day For 31st enter 31 Change Hours Use 24 hour clock format For 8pm enter 20 00 Change Minutes For 7 30 enter 30 DST Summer Time Adjust If activated this option will automa...

Page 9: ...arn Devices Entering this menu allows the learning of wireless bells onto the system Select Bell Selects the bell on the system that is to be learnt Learnt will be displayed if a bell is already learn...

Page 10: ...t may be deleted by entering this menu Delete All To delete all Wireless Arming Stations enter 2000 this is the Panel Security Code Please wait will be displayed while the EURO 46 V10 deletes them Sel...

Page 11: ...Select the user key fob to program Select Button The different buttons and button combinations that may be programmed are 1 Lock Button 2 Unlock Button 3 Button I 4 Button II 5 Lock Unlock Buttons 6...

Page 12: ...set to single sounding once or follow sounding while the door is left open NOTE The chime can be turned on or off in unset mode by pressing c when all Entry Delay inputs are closed Omittable Enables t...

Page 13: ...r Alarm The display will be show 1 Living Room Tamper on Input Meaning Tamper alarm on input 1 which is the Living Room Manually Omitting Inputs Method 1 EN50131 1 Grade 2 and 3 compliant While the sy...

Page 14: ...Inputs 25 32 3 ZEM Address 3 Inputs 33 40 4 ZEM Address 4 Inputs 41 48 5 ZEM Address 5 Inputs 49 56 6 ZEM Address 6 Inputs 57 64 7 ZEM Address 7 Inputs 65 72 ZEM Installed 0 No 1 ZEM8 EURO37R 2 ZEM32...

Page 15: ...dule to the Control Panel as well as programming of the PGM options for the outputs on the module Keypad Outputs Allows the programming of the PGM options for the outputs located on the wired keypads...

Page 16: ...k unlock doors and also is to be used to set and unset the system This option is used in conjunction with tag opens doors which can be found in Site Options which is a sub menu within SYSTEM OPTIONS T...

Page 17: ...r press for Unset Only Press 5 Set Point Sets will be displayed Select the area s Press 6 Set Point Unsets will be displayed Select the area s Press 7 Set Point In will be displayed Enter the area in...

Page 18: ...area s Press 6 Set Point Unsets will be displayed Select the area s Press 7 Set Point In will be displayed Enter the Area in which the keypad is situated and press 8 Lock Open Time will be displayed...

Page 19: ...Select then Press 6 Auto Wakeup will be displayed This option wakes the tag reader from sleep mode during the entry process walking the entry route Select to enable or disable then Press 7 Supervision...

Page 20: ...the exit time for each area that is applied when the area is set using the HomeControl Android or iOS App PLEASE NOTE This time must be set at 30 seconds or more to comply with PD6662 2010 IA 2015 0...

Page 21: ...inutes Set Fail The time after which the Set Fail operation will be invoked if the exit procedure is not completed 5 255 seconds Guard Code Alarm Minimum time an alarm must have existed before a Guard...

Page 22: ...t a system and an output type 00058 Guard Code will activate when this code is used Dial Out A dial code is used to force the panel to dial the UDL software while in Day Mode Change Master Manager Cod...

Page 23: ...6 7 Main Sounder Area A B C D 0 1 APP Exit Tone Volume 0 Completely Silent 1 Silent but beeps when the system is set 2 5 keypad 6 7 Main Sounder Alarm Volume 0 Completely Silent 1 Silent but beeps wh...

Page 24: ...r the control panel has fully set If Squawk is selected any output programmed as Siren any will activate for five seconds after the panel has set Finally if set to Both any outputs programmed as Strob...

Page 25: ...here is a wireless polling fault The panel will not display a wireless polling fault If NO the user will not be able to set the panel with a polling fault The panel will display a fault and the settin...

Page 26: ...o other information is available the display will move to the next log entry Press or again to return to the main screen for that log entry PLEASE NOTE In any unset or set period the control panel wil...

Page 27: ...perform an automatic battery load test at every power supply at 7 00am each day This will drop the power supply voltage below the battery voltage while monitoring the system diagnostics The test will...

Page 28: ...he wireless devices have been analysed From this point each device is tested every 15 seconds On the LCD display it is also possible to view each individual device s signal strength as a percentage 3...

Page 29: ...ion Inputs The status of the inputs will be shown C Closed O Open F Fault T Tamper The resistance reading can also be shown by pressing for any of the above for statuses ZEM Inputs Choose the ZEM addr...

Page 30: ...connection to the HomeControl App Last Polled Cloud Displays the time period since the last successful poll to the Pyronix Cloud Last Polled ARC Displays the time since the last successful poll to th...

Page 31: ...please refer to the Communications Guide This will also contain all the information on setting up the HomeControl App The panel can also by operated via SMS commands Please refer to Appendix 3 SMS Com...

Page 32: ...ire Alarm Starts at This feature programs the starting point of the alarm responses for a fire alarm The levels are Keypads Internal Sounders Sirens Only and Digi Fire Alarm Stops at This feature prog...

Page 33: ...Set Select the areas that the above setting will be applicable to Set Up Downloading The control panel has uploading and downloading capabilities The InSite upload download software allows you to mon...

Page 34: ...he panel is supplied with default settings that comply with EN50131 at Grade 3 Clean Start Code 2000 If Grade 2 defaults are required please use Clean Start Code 2002 Clear WLs Data This gives the opt...

Page 35: ...E Alters the volume of the tone heard when a keypad button is pressed TAG VOLUME Sets the volume when tag is presented KEYPAD VOLUME Sets the general volume of the keypad ID TAG Used to read the uniqu...

Page 36: ...e Insite software Press 10 Finally go out of this menu and then into the Site Options main menu and then scroll through until Cloud Priority set this to Normal for initial connections and then press e...

Page 37: ...re you take note of it for use later in the Insite software Press 6 Finally go out of this menu and then into the Site Options main menu and then scroll through until Cloud Priority set this to Normal...

Page 38: ...to Set This will then be displayed in the list 3 Select the action of this timer such as Set 4 Select the time 24 hour such as 14 00 NOT 02 00 when the action should start 5 Another action can now be...

Page 39: ...epetitive holidays that need to be repeated every year such as this may be needed for national events memorial days or birthdays 6 Once completed exit the screen by clicking OK and download the data t...

Page 40: ...call to the ARC has failed NOTE This is a communication problem which is rarely caused by an equipment fault Primarily this is related to the hand shake and kiss off frequency set up at the receiver...

Page 41: ...mains failure Note The system is about to be powered down MAINS FAIL xxx Mains supply failed The system detects that the mains frequency is out of specification as well as voltage Note AC FAIL timer o...

Page 42: ...splays when no polls wireless comms are received for 20 minutes before the set operation Test signal strength battery status for each wireless device especially the one that corresponds to the input n...

Page 43: ...communicator response Note May be used to act as doorbell by use of chime attribute 12 Switcher Active at all times This Input Type is used when you want an input to be used to trigger an output but...

Page 44: ...input from key switch or equivalent to set unset the areas assigned to it Requires momentary action switch to toggle set unset state 29 Interior Active when set Audible response full communicator intr...

Page 45: ...iren Any When the alarm is live When the alarm is silenced or when the siren timer expires 0016 Strobe Any When the alarm is live When the alarm is silenced or when the siren timer expires 0017 Omit R...

Page 46: ...d to trigger a relay to break the hold off connection to the Bell or even to provide the hold off directly 0044 Off During Test Output is normally active and will deactivate only when tested from the...

Page 47: ...As 0006 for Area A 0207 Tamper A As 0007 for Area A 0208 Duress A As 0008 for Area A 0209 HU Device A As 0009 for Area A 0210 Fire Reset A As 0010 for Area A 0213 Secure Int A As 0013 for Area A 0214...

Page 48: ...s called Kitchen Input omit area A Kitchen 04 Forced Set area A Omitting inputs via SMS text command Example SMS command send Description Example SMS command response 123456 Omit 6 123456 User Code Om...

Page 49: ...ord and spelled exactly as written in the panel such as Garage Door is not acceptable It has to be written as Garage Door in the panel and the respective command will be Garage Door Editing an SMS tel...

Page 50: ...uts 1 76 Unused Input In Area A Input Areas Any 0 Input Attributes Chime No 0 Omittable No 0 Double Knock No 0 Dual Trip No 0 Normally Open No 0 Walk Test No 0 Monitor Activity No 0 Special Log No 0 C...

Page 51: ...P Strobe Any 0016 OP Module Address OP Mod Installed No 0 Keypad Outputs Output 1 Not Used 0000 Reader Outputs Outputs 1 2 Not Used 0000 User Outputs User Output No 01 User Output Type Latched 0 User...

Page 52: ...s 2 9 Empty 10 Code Change Master Manager Code 2222 User Areas 01ABCD User Set Options Unset Set 0 Flexi Set Yes 1 User Name _ Change Engineer Code 1111 VOLUME CONTROL Entry 4 Exit 4 APP Exit 4 Alarm...

Page 53: ...Bell Supervision Yes 1 Download If Set No 0 Cloud Priority Low 1 System Displays Area A B C D 0 1 Text Area Full Area Text Full Sign On Message Euro 46 Display When Set No 0 Display Alarms No 0 Displa...

Page 54: ...Anti Code Restore No 0 COMMUNICATIONS App Set Up Use App No 0 System ID Cloud Password _ Security Level Normal 0 App Password _ Always Poll Cloud No 0 Data Network Set Up Program GPRS Program LAN Prog...

Page 55: ...No _ Valid Areas 01ABCD Redials 03 Time Out 30 Test Calls No 0 Event Types Default 0 User SMS Common Message Alarm System SMS Control Enable SMS Set No 0 SMS Unset No 0 SMS Status No 0 SMS Output No...

Page 56: ...2000 2002 Differences HU Starts at Digi 3 Hu Stops at Confirm 4 Medical Starts stops Digi 3 Day alarm starts stops Sirens Only 2 Start at Stop at Digi 3 If area set SET UP DOWNLOADING Download by None...

Page 57: ...BAREA SHUNT SET UNSET Sub Area Set CG 3402 4 on Shunt Closed 1402 4 Sub Area Unset OG 1402 5 Shunt Opened 3402 5 INTRUDER ALARM Intruder Alarm BA 1130 7 all all all once Gas Alarm GA 1151 7 Entry Exit...

Page 58: ...22 12 HU ALARM RESTORE HU Restore PH 3120 13 on on Silent HU Restore HH 3122 13 Keypad HU Restore PR 3120 13 MEDICAL ALARM Medical Alarm MA 1100 14 on on on on MEDICAL RESTORE Medical Alarm Restore MH...

Page 59: ...572 20 Zone Omit Restore BU 3570 20 TECHNICAL Low Volts AT 1302 21 on on on Battery Disconnect YT 1311 21 Battery Load Fail YT 1309 21 Fuse 1 IA 1300 21 Fuse 2 IA 1300 21 Fuse 3 IA 1300 21 Fuse 4 IA 1...

Page 60: ...Failed 1330 25 Modem Communication Fail 1350 25 Input Line Fail LT 1351 25 Telecom Line Fault LT 1351 25 Input Line Restored LR 3351 25 Telecom Line Restored LR 3351 25 ACCESS CONTROL Door Left Open...

Page 61: ...t 2 ARC No Arm Disarm Default 3 ARC No Arm Disarm and Alarm Restores Default SMS INFORMATION Engineer Access LB 1627 31 Engineer Exit LX 1628 31 System Restart 1305 31 Logs Cleared 1621 31 Engineer Re...

Page 62: ...62 EURO 46 V10 Programming Manual...

Page 63: ...63 EURO 46 V10 Programming Manual...

Page 64: ......

Reviews: