b) Identify and match the IOM SAS address and sg device for both IOMs from the output. Each address
appears bolded in the example below.
Addressed logical unit:
designator type: NAA,
code set: Binary
0x
5000ccab0300003c
Target port:
designator type: NAA,
code set: Binary
transport: Serial Attached SCSI Protocol (SPL-4)
0x
5000ccab0300003c
designator type: Relative target port,
code set: Binary
transport: Serial Attached SCSI Protocol (SPL-4)
Relative target port: 0x1
Target device that contains addressed lu:
designator type: NAA,
code set: Binary
transport: Serial Attached SCSI Protocol (SPL-4)
0x
5000ccab0300003c
4. Build the sg_senddiag command using the information recorded in earlier steps.
a) Use the example of the sg_senddiag command shown in the image above to complete the specific
sg_senddiag command for IOM A. Replace letters a through d with the information recorded in previous
steps.
Figure 184: sg_senddiag Command
a. sg device (<dev>): device associated with IOM A
b. Enable Zoning: 61
c. Zoning Configuration: configuration 01, 02, or 03
Note: For information on preconfigured zoning configurations, see:
on page 162.
d. IOM SAS Address: SAS Address associated with IOM A
Note: A comma should be placed after each bit of data in the IOM SAS Address that was
recorded. For example, if the IOM SAS Address output was 5000CCAB0300003C, the address
that should be added to the sg_senddiag command should be 50,00,CC,AB,03,00,00,3C.
170
5
System Management
User Guide
5.2
Zoning