360077-1/O
28
i.Series® - All Models
7
Press the
BACK
button to return to the Edit Configuration screen, or press the
HOME
button to exit.
The new settings are saved.
8.8.4
Low Chamber Temperature Alarm
The Low Alarm setpoint specifies the temperature at which the Low Temperature Alarm activates. If the
temperature detected by the chamber probe is less than or equal to this value, the alarm activates.
►
Default setpoint is 1.5 °C (iB models)
►
Default setpoint is 2.0 °C (iLR models)
►
Setpoint can be changed from -40 °C to +40 °C
Change the setpoint:
1
Press the
MAIN
button.
2
Press the
DOWN
button to highlight Edit Configuration. Press the
SELECT
button.
3
Enter the password when prompted.
4
Press the
DOWN
button to highlight Alarm Setpoints. Press the
SELECT
button.
5
Press the
DOWN
button to highlight Low Alarm Setpoint.
6
Press the
INC
or
DEC
buttons to change the setting.
7
Press the
BACK
button to return to the Edit Configuration screen, or press the
HOME
button to exit.
The new settings are saved.
8.8.5
Condenser Temperature Alarm
The Condenser Alarm setpoint specifies the temperature at which the Condenser Temperature Alarm
activates. If the temperature of the condenser discharge line is greater than or equal to this value, the
alarm activates.
►
Default setpoint is 50 °C
►
Setpoint can be changed from -40 °C to +80 °C
NOTICE
Condenser Temperature Alarm should not be changed unless directed by Helmer
Technical Service.
Change the setpoint:
1
Press the
MAIN
button.
2
Press the
DOWN
button to highlight Edit Configuration. Press the
SELECT
button.
3
Enter the password when prompted.
4
Press the
DOWN
button to highlight Alarm Setpoints. Press the
SELECT
button.
5
Press the
DOWN
button to highlight Cond. Alarm Setpoint.
6
Press the
INC
or
DEC
buttons to change the setting.
7
Press the
BACK
button to return to the Edit Configuration screen, or press the
HOME
button to exit.
The new settings are saved.
8.8.6
Door Ajar Alarm
The Door Ajar Timeout specifies longest time the refrigerator door can be open before the alarm activates.
If the time elapsed since the last door opening is greater than or equal to this value, the alarm activates.
►
Default delay setting is three minutes
►
Setting can be changed from 0 minutes to 60 minutes
Change the alarm delay:
1
Press the
MAIN
button.
2
Press the
DOWN
button to highlight Edit Configuration. Press the
SELECT
button.
Summary of Contents for (Version A) HB120(Versions A and B)