7 TKS 03 setting
7 TKS 03 setting
7.1 Configuration
DIP switches for
configuration
Ribbon cable
connector
Hexagon switch
Time setting
DIP switch
configuration
Fig. 57:
DIP switches on the TSK 03
The system can be configured as follows using the DIP switches on the TSK 03
Recommended settings
DIP no.
Position
Function/configuration
DIP 6
ON
Light barrier is checked in the event of controller failure
DIP 6
OFF
Light barrier is not checked in the event of controller failure
DIP 5
ON
No active light barrier or only one reflection light barrier
connected
DIP 5
OFF
Active light barrier or two reflection light barriers connected
DIP 4
ON
Alarm relay drops out with "silent closing"
DIP 4
OFF
Alarm relay does not drop out with "silent closing"
DIP 3
ON
Fault message in the event of disabled light barrier after
10 min
DIP 2
OFF
DIP 3
OFF
Fault message in the event of disabled light barrier after
2 min
DIP 2
ON
DIP 3
ON
No fault message in the event of disabled light barrier
DIP 2
ON
DIP 1
ON
System with personal protection
DIP 1
OFF
System without personal protection
DIP switches 7 and 8 are without function