6 Electrical installation
6.5.1 PCB TKS 03 voltage supply
Name
Data stream
Function
Data
Activation
Terminal 1
Input
TKS 03 voltage supply
24 V DC SVK 47 +UA
Terminal 2
Input
TKS 03 voltage supply
GND
SVK 47 –UA
In the SVG 522 version with TSK 03, these connections have already been pre-
wired at the factory.
Fig. 18:
Connections pre-wired at the factory
6.5.2 Incorporation of SVK 47 fault messages
Battery failure, processor failure and low battery voltage of the power supply
board SVK 47 are signalled to the door control board TSK 03 and evaluated as an
alarm from the fire detectors.
Name
Data stream
Function
Data
Activation
Terminal 3
Output
Voltage supply
24 V DC Unassigned
Terminal 4
Output
Voltage supply
GND
Unassigned
Terminal 5
Unassigned
Connection point terminal
Unas-
signed
Unassigned
Terminal 6
Output
Monitoring of SVK 47 faults
SVK 47 1.9
Terminal 7
Input
Monitoring of SVK 47 faults
SVK 47 1.4
In the SVG 522 version with TSK 03, these connections have already been pre-
wired at the factory.
Unassigned
SVK 47 fault
SVK 47 fault
Fig. 19:
Connections pre-wired at the factory