6 Electrical installation
Caution! Contact load!
The load of the relay contacts must not exceed 30 V DC 1 A.
The functional position "Open door" depends on the connected door limit
switches.
Fig. 46:
Functional position in state "door not open" by limit switch
Fig. 47:
Functional position in state "Open door" by limit switch
6.5.15 Connecting the "Close door" relay
Name
Data stream
Function
Data
Activation
Terminal 49
Potential-free
Open with signal input:
"Close door" by limit switch
NC
Unassigned
Terminal 50
Potential-free
Common contact,
max. 30 V DC 1 A
COM
Unassigned
Terminal 51
Potential-free
Closed with signal input:
"Close door" by limit switch
NO
Unassigned
Terminal 52
Output
Voltage is applied with signal
input: "Close door" by limit
switch
24 V DC Unassigned
Caution! Contact load!
The load of the relay contacts must not exceed 30 V DC 1 A.
The functional position "Close door" depends on the connected door limit
switches.