6 Electrical installation
Caution! Contact load!
The load of the relay contacts must not exceed 30 V DC 1 A.
The functional position "light barrier failure" depends on the configuration
of the TSK 03.
The failure relay can be used for individual transfer. The relay drops out in the
event of light barrier failure. In addition, the "light barrier disabled" signal
(adjustable by means of DIP switches, see chapter 7.1 "Configuration") also initi-
ates a fault message.
Fig. 42:
Functional position in state "light barrier failure/light barrier disabled"
Fig. 43:
Functional position in operating state; no failure or disabling of the light
barrier
6.5.13 Connecting the "closing initiated" relay
Name
Data stream
Function
Data
Activation
Terminal 41
Potential-free
Closed when closing has been
initiated
NC
Unassigned
Terminal 42
Potential-free
Common contact,
max. 30 V DC 1 A
COM
Unassigned
Terminal 43
Potential-free
Open when closing has been
initiated
NO
Unassigned
Terminal 44
Output
The voltage drops when clos-
ing has been initiated
24 V DC Unassigned