39/68
7002985 300709.KET Release 06.06.2017
Hekatron Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg
6 Electrical installation
6.5.10 Connecting the "external reset input"
Name
Data stream
Function
Data
Activation
Terminal 31
Input
TKS 03 reset
Optional
button
Terminal 32
Input
TKS 03 reset
Optional
button
Caution when using the reset button!
A reset should only be made after the system has been checked on site. We
recommend to install any external reset button in the immediate vicinity of
the monitored fire barrier.
This input is provided for an external reset option for the TSK 03, e.g., using the
push-button DKT 02.
Function:
Contacts 31-32 open > "reset" signal not applied.
Contacts 31-32 closed > "reset" signal is applied.
If no external reset button is connected, the contacts remain open.
Fig. 38:
External reset button connected
6.5.11 Connecting the "Alarm" relay
Name
Data stream
Function
Data
Activation
Terminal 33
Potential-free
Closed in the event of alarm,
failure and voltage loss.
NC
Unassigned
Terminal 34
Potential-free
Common contact, max. 30 V
DC 1 A
COM
Unassigned
Terminal 35
Potential-free
Open in the event of alarm,
failure and voltage loss.
NO
Unassigned
Terminal 36
Output
Voltage drops in the event of
alarm and failure.
24 V DC Unassigned
Caution! Contact load!
The load of the relay contacts must not exceed 30 V DC 1 A.