3 Product description
3.5 Flap control option
Where sliding doors and gates with extended flap functionality are concerned,
the door control board TSK 03 allows opening the side flaps with a delay in
relation to the top flap. To achieve this, the alarm output of the TSK 03 can be
used to open the top cover.
The output for the hold-open device is used for the delayed energisation of the
side flaps. The delay can be set within a range from 0 to 120 seconds in 10-second
increments. An additional delay of 2 minutes and 10 minutes is available.
Alarm relay
Fig. 07:
Alarm relay
The TSK 03 detects the alarm message; the alarm relay is energised instantly and
triggers the top flaps.
Terminals 53/54 and
terminals 55/56 are both
de-energised after the
set time has elapsed
(see chapter "Hold-open
device connection")
Hold-open device 1
Fig. 08:
Hold-open device 1
After the time set on the TSK 03 has elapsed, terminals 53/54 and 55/56 are
de-energised. In the connection example above, terminals 53/54 are used to open
the side flaps with a delay and terminals 55/56 are used to release the door or
gate holding magnets with a delay.
Hold-open devices for the flaps
The hold-open devices for the flaps must be listed in the DIBt approval
document for the hold-open system.