6 Electrical installation
6.3 SVK 47 connection
A
Mains connection
230 V AC
B
Relay outputs
- Mains
- Low voltage
- Collective fault
C
Battery connection
D
24 V DC outputs
E
Fuse 2 A 250 VT
G
Operator panel
connector
F4
LED 4 (green)
The LED is lit while
230 V AC mains voltage
is applied
F3
LED 3 (green)
The LED is lit when the
voltage is above 21 V
F2
LED 2 (red)
The LED is lit in the
event of a collective
fault (battery failure,
processor failure)
See p. 26, table-01
F1
LED 1 (green)
The LED is lit when the
voltage is above 0 V
(no short-circuit)
A
D
E
B
C
G
F1
F2
F3
F4
Fig. 14:
SVK 47 connection
LED 2
(SVK 47)
LED fault
(see Fig. 04 Operator panel TSK 03)
State
Measure
Off
Off
Operation
---
Off
On
Processor failure Replace SVK 47
On
Off
Power failure
Check mains voltage
On
On
Battery failure
Test/exchange batteries
Table-01: Indicator matrix of LED 2 of the SVK 47 and the "Störung" LED (fault) on the
front label
Mains cable
Strip the mains cable (A) only directly in front of the provided connection
terminals.
Contact protection
Re-install the contact protection (transparent cover plate) over the power
supply board before turning power on.