17
Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
MEDIUM PROFILE EVAPORATOR
Alarm Tables
SYSTEM ALARMS TABLE
BYTE
BIT 31
BIT 30
BIT 29
BIT 28
BIT 27
BIT 26
BIT 25
BIT 24
Spare
BIT 23
BIT 22
BIT 21
BIT 20
BIT 19
BIT 18
BIT 17
BIT 16
BYTE
BIT 15
BIT 14
BIT 13
BIT 12
BIT 11
BIT 10
BIT 9
BIT 8
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Reserved (Future)
BYTE
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
BIT 2
BIT 1
BIT 0
Reserved (Future)
Reserved
(Future)
Door Switch
Open Alarm
Reserved
(Future)
Input Fault (Sen-
sor Errors Alarm)
System Startup
Failure Alarm
Low Box
Temperature
Alarm
High Box
Temperature
Alarm
To Read System Alarms, send command
XX 03 40 3E 00 01 XX XX
The read registers can be bit-mapped per the table above.
EX: If
00000000 00001001
is read, then there is an active high box temp alarm and an active input sensor fault.