17

Please keep these instructions for future reference. 

Equipment assembly and Wiring is required before using this Guide. 

For assembly please consult Intelligen Assebly and Wiring Guide.

PRIOR ASSEMBLY NEEDED

IMPORTANT!

This Quick Start Guide is 

only for Intelligen Series XXKSJFS Model. 

IMPORTANT!

Since product improvement is a continuing effort, we reserve the

right to make changes in specifications without notice.

Normal Business Hours – 8:00 AM – 8:00 PM EDT

(800) 321-1881

After Hours (after 5:00 PM EDT, weekends and holidays)

(877) 482-7238

heatcraft.com/intelligen/support

[email protected]

US. Customer Service

Normal Business Hours – 8:00 AM – 8:00 PM EDT

(800) 321-1881

After Hours (after 5:00 PM EDT, weekends and holidays)

(877) 482-7238

heatcraft.com/intelligen/support

[email protected]

Canada Customer Service

QUICK START GUIDE

INTELLIGEN 00049DFS

MARCH 2018*

*REPLACES JANUARY 2018

PART NO. 099483

MEDIUM PROFILE EVAPORATOR

Alarm Tables

SYSTEM ALARMS TABLE

BYTE

BIT 31

BIT 30

BIT 29

BIT 28

BIT 27

BIT 26

BIT 25

BIT 24

Spare

BIT 23

BIT 22

BIT 21

BIT 20

BIT 19

BIT 18

BIT 17

BIT 16

BYTE

BIT 15

BIT 14

BIT 13

BIT 12

BIT 11

BIT 10

BIT 9

BIT 8

Spare

Spare

Spare

Spare

Spare

Spare

Spare

Reserved (Future)

BYTE

BIT 7

BIT 6

BIT 5

BIT 4

BIT 3

BIT 2

BIT 1

BIT 0

Reserved (Future)

Reserved 

(Future)

Door Switch 

Open Alarm

Reserved 

(Future)

Input Fault (Sen-

sor Errors Alarm)

System Startup 

Failure Alarm

Low Box 

Temperature 

Alarm

High Box

Temperature 

Alarm

To Read System Alarms, send command 

 XX 03 40 3E 00 01 XX XX

 

The read registers can be bit-mapped per the table above. 
EX: If 

00000000 00001001

 is read, then there is an active high box temp alarm and an active input sensor fault.

Summary of Contents for intelliGen Integration Card iIC

Page 1: ...raft com Canada Customer Service QUICK START GUIDE INTELLIGEN 00049DFS MARCH 2018 REPLACES JANUARY 2018 PART NO 099483 intelliGen 00049DFS Installation Operation Manual OCTOBER 2018 PART NO 25010401 intelliGen Webserver Card iWC and Integration Card iIC TABLE OF CONTENTS iWC intelliGen Webserver Card 2 Installation 2 Configuration and Initial Setup 2 Local Access 2 5 Remote Access 6 Web Navigation...

Page 2: ...UICK START GUIDE INTELLIGEN 00049DFS MARCH 2018 REPLACES JANUARY 2018 PART NO 099483 iWC intelliGen WEBSERVER CARD Installation While system is powered down align and insert iWC s pins into intelliGen Refrigeration Controller iRC board s plug Secure with mounting screws For proper mounting the 6 32x1 inch screws should be torqued to 64 oz inch Connect CAT5 Ethernet cable to iWC Connect other end o...

Page 3: ...M 8 00 PM EDT 800 321 1881 After Hours after 5 00 PM EDT weekends and holidays 877 482 7238 heatcraft com intelligen support support heatcraft com Canada Customer Service QUICK START GUIDE INTELLIGEN 00049DFS MARCH 2018 REPLACES JANUARY 2018 PART NO 099483 STEP 2 Select Configuration Mode Select the Web Local Wired option to obtain the IP address for local web configuration CONFIG FROM Web Local W...

Page 4: ...stomer Service Normal Business Hours 8 00 AM 8 00 PM EDT 800 321 1881 After Hours after 5 00 PM EDT weekends and holidays 877 482 7238 heatcraft com intelligen support support heatcraft com Canada Customer Service QUICK START GUIDE INTELLIGEN 00049DFS MARCH 2018 REPLACES JANUARY 2018 PART NO 099483 IF SYSTEM HAS BEEN PREVIOUSLY CONFIGURED Connect iWC to a network point router before commencing web...

Page 5: ...rt support heatcraft com Canada Customer Service QUICK START GUIDE INTELLIGEN 00049DFS MARCH 2018 REPLACES JANUARY 2018 PART NO 099483 STEP 3 Configuration IP Address Info IPv4 is defaulted to DHCP if a static IP is needed press knob and scroll to select static ip address assignment CONFIGURE IPv4 DHCP STEP 4 Obtain IPv4 Address If DHCP is selected scroll to obtain automatically generated IPv4 Add...

Page 6: ...telligen support support heatcraft com Canada Customer Service QUICK START GUIDE INTELLIGEN 00049DFS MARCH 2018 REPLACES JANUARY 2018 PART NO 099483 Remote Access USER SETUP Log in information including passwords and 6 digit pin iWC must be configured per Local Access instructions Create an account by visiting https intelligen online Log in and select REGISTER NEW SYSTEM A prompt for a 6 digit PIN...

Page 7: ...s all your sites in a single location QUESTION MARK Takes you to the Heatcraft Support Site internet Connectivity required PROFILE Change User settings including E mail and Text Alerts and Alert Frequency NOTIFICATIONS Lists all the notifications from all your systems LOG OUT To Exit the Dashboard System Menu Options MONITOR Monitor system operating conditions UNITS Monitor and control individual ...

Page 8: ...dress is displayed this should be a value other than 0 0 0 0 2 If using Windows OS open command prompt application and type ping XXX XXX XXX XXX where XXX XXX XXX XXX is the IP address displayed at the iRCUI 1 Go to Next Step 2 If ping response has data transmission information then try a different web browser and or review web browser settings to disable any proxy and firewall that may be blockin...

Page 9: ...ARY 2018 PART NO 099483 iIC intelliGen INTEGRATION CARD Installation If an iWC webserver card is used in the system be sure to connect the iIC integration card to the same evaporator board If no iWC is present in the system the iIC may be connected to ANY evaporator board While system is powered down align insert iIC s pins into iRC board s plug insert card into board Secure with mounting screws F...

Page 10: ...LACES JANUARY 2018 PART NO 099483 If selecting BACnet protocol Enter the External Address ranging from 1 127 Select BACnet Baud Rate 9600 or 38400 If selecting MODBUS protocol Enter the External Address ranging from 1 246 OPTION 2 CONFIGURE THROUGH CONTROLLER USER INTERFACE AFTER QUICK CONFIGURATION Under GENERAL SETTINGS select the protocol to be used If selecting BACnet protocol EXTERNAL MODBUS ...

Page 11: ...e 2 Year LSB Byte 3 Month Byte 4 Day Byte 5 Hour Byte 6 Minutes Byte 7 Seconds Byte 8 Week Day 2 Defrost Type 514 Integer Read AIR 0 Medium Temp Electric 1 Low Temp Electric 2 3 Defrost Style 515 Integer Read TIMED 0 SMART 1 DEMAND 2 4 Refrigerant 516 Integer Read R404A 0 R507A 1 R407A 2 R407C 3 R407F 4 R22 5 R448A 6 R449A 7 5 Box Temperature Setpoint 517 Real RW When reading divide read number by...

Page 12: ...2 Byte 2 D0 720 minutes in decimal for 12 pm 19 Defrost 2 Schedule 531 Integer Read Same as Defrost 1 schedule 20 Defrost 3 Schedule 532 Integer Read Same as Defrost 1 schedule 21 Defrost 4 Schedule 533 Integer Read Same as Defrost 1 schedule 22 Defrost 5 Schedule 534 Integer Read Same as Defrost 1 schedule 23 Defrost 6 Schedule 535 Integer Read Same as Defrost 1 schedule 24 Defrost 7 Schedule 536...

Page 13: ...perty ID Type Read Write Decoding 39 Time Zone 551 Integer Read MST 0 NST 1 AST 2 EST 3 CST 4 MST 5 PST 6 AKST 7 HAST 8 SST 9 CHST 10 WAKT 11 40 UTC Offset 552 Integer Read MST 0 NST 1 AST 2 EST 3 CST 4 MST 5 PST 6 AKST 7 HAST 8 SST 9 CHST 10 WAKT 11 41 Follow DST 553 Integer Read 1 YES 0 NO 42 Operation Mode 554 ENUM Read OP_OFF 0 OP_COOLING 1 OP_DEFROST 3 OP_ DRAIN 4 OP_DELAY 5 OP_PRODUCTLOAD 6 ...

Page 14: ...ll temperature values to be read according to the parameter value Temperature Units either F or C Field Name Read Write 22 Data Address 3344 Registers to read 5566 Data Type Decoding Method System Custom Name Read 0x03 0x4000 0001 String ASCII characters sent in data bytes Operation Mode Read 03 0x400A 0001 ENUM OP_OFF 0 OP_COOLING 1 OP_DEFROST 3 OP_DRAIN 4 OP_DELAY 5 OP_PRODUCTLOAD 6 OP_REFREEZE ...

Page 15: ...ature Units Read 03 0x401A 0001 Integer CELSIUS 1 FAHRENHEIT 0 Pressure Units Read 03 0x401B 0001 Integer PSIG 0 KPA 1 BAR 2 Drain Down Period Read 03 0x401C 0001 Integer Unit Minutes Dual Coil Termination Read 03 0x401D 0001 Boolean 1 Yes 0 No Number of Defrosts Read 03 0x401F 0001 Integer Defrost 1 Schedule Read 03 0x4020 0001 Integer Time in minutes since 12 am Example Byte 1 02 Byte 2 D0 720 m...

Page 16: ...nteger Unit Minutes Country Read 03 0x4034 0001 Integer USA 0 CANADA 1 Time Zone Read 03 0x4035 0001 Integer MST 0 NST 1 AST 2 EST 3 CST 4 MST 5 PST 6 AKST 7 HAST 8 SST 9 CHST 10 WAKT 11 UTC Offset Read 03 0x4036 0001 Integer MST 0 NST 1 AST 2 EST 3 CST 4 MST 5 PST 6 AKST 7 HAST 8 SST 9 CHST 10 WAKT 11 Follow DST Read 03 0x4037 0001 Integer 1 YES 0 NO DST Offset Read 03 0x4038 0001 Integer 12 24 H...

Page 17: ... 877 482 7238 heatcraft com intelligen support support heatcraft com Canada Customer Service QUICK START GUIDE INTELLIGEN 00049DFS MARCH 2018 REPLACES JANUARY 2018 PART NO 099483 Alarm Tables SYSTEM ALARMS TABLE BYTE BIT 31 BIT 30 BIT 29 BIT 28 BIT 27 BIT 26 BIT 25 BIT 24 Spare BIT 23 BIT 22 BIT 21 BIT 20 BIT 19 BIT 18 BIT 17 BIT 16 BYTE BIT 15 BIT 14 BIT 13 BIT 12 BIT 11 BIT 10 BIT 9 BIT 8 Spare ...

Page 18: ...44 BIT 43 BIT 42 BIT 41 BIT 40 Spare BIT 39 BIT 38 BIT 37 BIT 36 BIT 35 BIT 34 BIT 33 BIT 32 Spare BYTE BIT 31 BIT 30 BIT 29 BIT 28 BIT 27 BIT 26 BIT 25 BIT 24 Input Fault Sensor Errors Alarm Spare Spare Spare Spare Spare Spare EV Connection Lost Error BYTE BIT 23 BIT 22 BIT 21 BIT 20 BIT 19 BIT 18 BIT 17 BIT 16 System Connection Lost Error Primary EV Temp Sensor Override Error RCBUI to RCB Comm F...

Page 19: ...Notes ...

Page 20: ...tion Parts The name behind the brands you trust 2018 Heatcraft Refrigeration Products LLC Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd Stone Mountain GA 30087 www heatcraftrpd com Customer Service and Technical Support Normal Business Hours 8 00 AM 8 00 PM EDT 800 321 1881 After Hours after 5 00 PM EDT weekends and holidays 877 482 7238 ...

Reviews: