16
Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
Field Name
Read/Write
(22):
Data Address
(3344):
# Registers to read
(5566):
Data Type:
Decoding Method
Alarm Low Box Temperature
Read (03)
0x4031
0001
Signed Integer
Real number divided
by 10
Alarm Delay Time
Read (03)
0x4032
0001
Integer
Unit – Minutes
Alarm Door Open Time
Read (03)
0x4033
0001
Integer
Unit – Minutes
Country
Read (03)
0x4034
0001
Integer
USA-0, CANADA-1
Time Zone
Read (03)
0x4035
0001
Integer
MST-0, NST-1, AST-2,
EST-3, CST-4, MST-5,
PST-6, AKST-7, HAST-
8, SST-9, CHST-10,
WAKT-11
UTC Offset
Read (03)
0x4036
0001
Integer
MST-0, NST-1, AST-2,
EST-3, CST-4, MST-5,
PST-6, AKST-7, HAST-
8, SST-9, CHST-10,
WAKT-11
Follow DST
Read (03)
0x4037
0001
Integer
1 – YES, 0 – NO
DST Offset
Read (03)
0x4038
0001
Integer
12/24 Hour Clock
Read (03)
0x4039
0001
Integer
0 – 12 hour clock,
1 – 24 hour clock
Number of Units
Read (03)
0x403A
0001
Integer
Controller Address
Read (03)
0x403B
0001
Integer
Box Temperature
Read (03)
0x403C
0001
Signed Integer
Real number divided
by 10
Force Defrost
Write (06)
0x403D
0001
Integer
Writing ‘1’ will force
defrost
System Alarms
Read (03)
0x403E
0001
Integer
Refer System Alarm
Table for bit decoding
Enable
Read (03)
(n * 0xC)
0001
Integer
0 – Disabled;
1 – Enabled
If Enabled is 0, below
parameters should be
ignored for that unit
Unit Address
Read (03)
(n * 0xC) + 1
0001
Integer
Unit Type
Read (03)
(n * 0xC) + 2
0001
Integer
EV Superheat Setpoint
Read (03)
(n * 0xC) + 3
0001
Signed Integer
Real number divided
by 10
Unit Alarms/Errors
Read (03)
(n * 0xC) + 4
0001
Refer Unit Alarms
Table for bit decoding
Short Unit Name
Read (03)
(n * 0xC) + 8
0001
Strings
ASCII characters sent
in data bytes
Note: n is an index into number of unit records ranging from [0 to N-1] EV units where max N = 8