Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
If selecting BACnet protocol
• Enter the External Address ranging from 1 – 127
• Select BACnet Baud Rate (9600 or 38400)
If selecting MODBUS protocol
• Enter the External Address ranging from 1 – 246
OPTION 2: CONFIGURE THROUGH CONTROLLER USER INTERFACE
AFTER QUICK CONFIGURATION
• Under
GENERAL SETTINGS
select the protocol to be used
If selecting BACnet protocol
• EXTERNAL MODBUS ADDR must be set to 0
• Enter the External Address ranging from 1 – 127
• Select BACnet Baud Rate (9600 or 38400)
If selecting MODBUS protocol
• EXTERNAL BACnet ADDR must be set to 0
• Enter the External Address ranging from 1 – 246
Integration Guide
BACnet SETTINGS
• Baud Rate (9600 or 38400)
• Set all BACnet devices on an MS/TP network to consecutive MAC addresses, starting at 1,
so that there are no gaps between MAC address values.
MODBUS SETTINGS
• Baud Rate- 38400 (Fixed)
• 8 Data Bits
• 1 Stop Bit
• Even Parity
TO READ/WRITE PARAMETERS OVER BACnet:
• Baud rate must be set to 38400/9600
• All temperature values to be read according to the parameter value “Temperature
Units” either °F or °C
Summary of Contents for intelliGen Integration Card iIC