15
Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
Field Name
Read/Write
(22):
Data Address
(3344):
# Registers to read
(5566):
Data Type:
Decoding Method
Box Load Mode Time Delay
Read (03)
0x4015
0001
Integer
Unit - Minutes
Box Load Mode Maximum Override Time
Read (03)
0x4016
0001
Integer
Unit - Minutes
Low Superheat Setpoint
Read (03)
0x4017
0001
Signed Integer
Real number divided
by 10
Minimum Runtime
Read (03)
0x4018
0001
Integer
Unit – Minutes
Minimum Off Time
Read (03)
0x4019
0001
Integer
Unit – Minutes
Temperature Units
Read (03)
0x401A
0001
Integer
CELSIUS – 1,
FAHRENHEIT - 0
Pressure Units
Read (03)
0x401B
0001
Integer
PSIG – 0, KPA -1,
BAR – 2
Drain Down Period
Read (03)
0x401C
0001
Integer
Unit - Minutes
Dual Coil Termination
Read (03)
0x401D
0001
Boolean
1-Yes/ 0-No
Number of Defrosts
Read (03)
0x401F
0001
Integer
Defrost 1 Schedule
Read (03)
0x4020
0001
Integer
Time in minutes since
12 am; Example-
Byte 1 – 02
Byte 2 – D0
720 minutes in deci-
mal for 12 pm
Defrost 2 Schedule
Read (03)
0x4021
0001
Integer
Same as Defrost 1
schedule
Defrost 3 Schedule
Read (03)
0x4022
0001
Integer
Same as Defrost 1
schedule
Defrost 4 Schedule
Read (03)
0x4023
0001
Integer
Same as Defrost 1
schedule
Defrost 5 Schedule
Read (03)
0x4024
0001
Integer
Same as Defrost 1
schedule
Defrost 6 Schedule
Read (03)
0x4025
0001
Integer
Same as Defrost 1
schedule
Defrost 7 Schedule
Read (03)
0x4026
0001
Integer
Same as Defrost 1
schedule
Defrost 8 Schedule
Read (03)
0x4027
0001
Integer
Same as Defrost 1
schedule
Defrost 9 Schedule
Read (03)
0x4028
0001
Integer
Same as Defrost 1
schedule
Defrost 10 Schedule
Read (03)
0x4029
0001
Integer
Same as Defrost 1
schedule
Defrost 11 Schedule
Read (03)
0x402A
0001
Integer
Same as Defrost 1
schedule
Defrost 12 Schedule
Read (03)
0x402B
0001
Integer
Same as Defrost 1
schedule
Defrost Failsafe Time
Read (03)
0x402C
0001
Integer
Unit - Minutes
Defrost End Temperature
Read (03)
0x402D
0001
Integer
Real number divided
by 10
Refreeze Time Safety
Read (03)
0x402E
0001
Integer
Unit – Minutes
Refreeze Suction Setpoint
Read (03)
0x402F
0001
Signed Integer
Real number divided
by 10
Summary of Contents for intelliGen Integration Card iIC