18
Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
Alarm Tables
UNIT ALARMS TABLE
BYTE
BIT 63
BIT 62
BIT 61
BIT 60
BIT 59
BIT 58
BIT 57
BIT 56
Spare
BIT 55
BIT 54
BIT 53
BIT 52
BIT 51
BIT 50
BIT 49
BIT 48
Spare
BIT 47
BIT 46
BIT 45
BIT 44
BIT 43
BIT 42
BIT 41
BIT 40
Spare
BIT 39
BIT 38
BIT 37
BIT 36
BIT 35
BIT 34
BIT 33
BIT 32
Spare
BYTE
BIT 31
BIT 30
BIT 29
BIT 28
BIT 27
BIT 26
BIT 25
BIT 24
Input Fault (Sensor
Errors Alarm)
Spare
Spare
Spare
Spare
Spare
Spare
EV Connection
Lost Error
BYTE
BIT 23
BIT 22
BIT 21
BIT 20
BIT 19
BIT 18
BIT 17
BIT 16
System Connection
Lost Error
Primary EV Temp
Sensor Override
Error
RCBUI to RCB
Comm Failure
Error
RCBUI Failure
Error
Static Operation
Error
Data Logging
Disrupted Error
Replace RTC
Backup
Battery Error
Evap Auxiliary
Temp Sensor
Error
BYTE
BIT 15
BIT 14
BIT 13
BIT 12
BIT 11
BIT 10
BIT 9
BIT 8
Reserved (Future)
Low Superheat
During Cooling
Error
24V Power
Supply High
Error
24V Power
Supply Low
Error
Spare Inputs
Error
Reserved (Future) Control Circuit
Open Error
Reserved (Future)
BYTE
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
BIT 2
BIT 1
BIT 0
Reserved (Future)
Reserved
(Future)
Reserved
(Future)
Reserved
(Future)
Evap Suction
Pressure Trans-
ducer Error
Evap Suction
Temp Sensor
Error
Coil Temp
Sensor Error
Box Temp Sensor
Error
To Read Unit Alarms, send command
XX 03 40 3E 00 01 XX XX
The read registers can be bit-mapped per the table above.
EX: If
00000000 00000000 00000000 00001001
is read, then there is an active box temp sensor error and an active evap suction transducer error.