14
Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
Modbus Register Mapping
TO READ/WRITE PARAMETERS OVER EXTERNAL MODBUS:
• Required Baud rate fixed to 38400
• Function codes
• Read Holding Registers – 0x03
• Write Holding Registers – 0x06
• All temperature values to be read according to the parameter value “Temperature Units” either °F or °C
Field Name
Read/Write
(22):
Data Address
(3344):
# Registers to read
(5566):
Data Type:
Decoding Method
System Custom Name
Read (0x03)
0x4000
0001
String
ASCII characters sent
in data bytes
Operation Mode
Read (03)
0x400A
0001
ENUM
OP_OFF-0,
OP_COOLING-1,
OP_DEFROST-3,
OP_DRAIN-4,
OP_DELAY-5,
OP_PRODUCTLOAD-6,
OP_REFREEZE-10,
OP_SERVICE-11
Date/Time Type
Read (03)
0x400B
0001
Integer
Always 2
Date/Time
Read (03)
0x400C
0001
Integer
Time in UTC,
Byte 1 – Year MSB,
Byte 2 – Year LSB,
Byte 3 – Month,
Byte 4 – Day,
Byte 5 – Hour,
Byte 6 – Minutes,
Byte 7 – Seconds,
Byte 8 – Week Day
Defrost Type
Read (03)
0x4010
0001
Integer
AIR -0,
Medium Temp
Electric – 1,
Low Temp Electric - 2
Defrost Style
Read (03)
0x4011
0001
Integer
TIMED - 0,
SMART - 1,
DEMAND - 2
Refrigerant
Read (03)
0x4012
0001
Integer
R404A - 0, R507A - 1,
R407A - 2, R407C - 3,
R407F - 4, R22 - 5,
R448A - 6, R449A - 7
Box Temperature Setpoint
Read (03)/
Write (06)
0x4013
0001
Signed Integer
When reading, divide
read number by 10;
Example: Byte 1 –
0x01 Byte 2 – 0x5E >
To be read as 35.0 F
When writing, multiply
desired setpoint by
10; Example- to set
box temp set-point to
20.0F, Write 0x00C8.
Box Temp Setpoint
must be in whole
number increments,
non-whole number
inputs will be rounded
to the nearest ones
place.
Modbus Command is 8 bytes (generally written in hexadecimal):
11 22 33 44 55 66 77 88.
11 - The Slave Address, this must correspond with the “External
Modbus Addr” setting on the intelliGen controller.
22 - The Fuction Code - for intelliGen, this will be 03 for reading
values and 06 for writing values.
3344 - The data address of the first register requested; these
values are shown in the following table for each field name
parameter.
5566 - Total number of registers requested; the number of
registers required for each field name parameter is shown in the
following table.
7788 - CRC (cyclic redundancy check); this is a byte checksum
performed according to the Modbus protocol standard.