background image

Technical data sheet

GM24A-MOD

Communicative damper actuator 

for adjusting dampers in technical 

building installations

•  Air damper size up to approx. 8 m²

•  Torque motor 40 Nm

•  Nominal voltage AC/DC 24 V

•  Control modulating, communicative, 

hybrid

•  Conversion of sensor signals

•  Communication via BACnet MS/TP, 

Modbus RTU, Belimo-MP-Bus or 

conventional control

 

Technical data

Electrical data   Nominal voltage

AC/DC 24 V

  Nominal voltage frequency

50/60 Hz

  Nominal voltage range

AC 19.2...28.8 V / DC 21.6...28.8 V

  Power consumption in operation

4 W

  Power consumption in rest position

1.6 W

  Power consumption for wire sizing

7 VA

  Connection supply / control

Cable 1 m, 6 x 0.75 mm²

Functional data   Torque motor

40 Nm

  Torque variable

25%, 50%, 75% reduced

  Communicative control

BACnet MS/TP

Modbus RTU (ex works)

MP-Bus

  Operating range Y

2...10 V

  Operating range Y variable

0.5...10 V

  Position feedback U

2...10 V

  Position feedback U note

Max. 1 mA

  Position feedback U variable

Start point 0.5...8 V

End point 2...10 V

  Position accuracy

±5%

  Direction of motion motor

selectable with switch 0/1

  Direction of motion note

Y = 0%: At switch position 0 (ccw rotation) / 1 

(cw rotation)

  Direction of motion variable

electronically reversible

  Manual override

with push-button, can be locked

  Angle of rotation

Max. 95°

  Angle of rotation note

can be limited on both sides with adjustable 

mechanical end stops

  Running time motor

150 s / 90°

  Running time motor variable

75...290 s

  Adaptation setting range

manual

  Adaptation setting range variable

No action

Adaptation when switched on

Adaptation after pushing the gear 

disengagement button

  Override control, controllable via bus 

communication

MAX (maximum position) = 100%

MIN (minimum position) = 0%

ZS (intermediate position) = 50%

  Override control variable

MAX = (MIN + 32%)...100%

MIN = 0%...(MAX – 32%)

ZS = MIN...MAX

  Sound power level, motor

45 dB(A)

  Mechanical interface

Universal shaft clamp 12...26.7 mm

  Position indication

Mechanically, pluggable

Safety   Protection class IEC/EN

III Safety Extra-Low Voltage (SELV)

  Protection class UL

UL Class 2 Supply

  Degree of protection IEC/EN

IP54

  Degree of protection NEMA/UL

NEMA 2

  Enclosure

UL Enclosure Type 2

  EMC

CE according to 2014/30/EU

www.belimo.com

GM24A-MOD • en-gb • 2020-04-21 • subject to changes

1

Summary of Contents for GM24A-MOD

Page 1: ...y 5 Direction of motion motor selectable with switch 0 1 Direction of motion note Y 0 At switch position 0 ccw rotation 1 cw rotation Direction of motion variable electronically reversible Manual override with push button can be locked Angle of rotation Max 95 Angle of rotation note can be limited on both sides with adjustable mechanical end stops Running time motor 150 s 90 Running time motor var...

Page 2: ...e observed Product features Mode of operation The actuator is fitted with an integrated interface for BACnet MS TP Modbus RTU and MP Bus It receives the digital positioning signal from the control system and returns the current status Converter for sensors Connection option for a sensor passive active or with switching contact In this way the analogue sensor signal can be easily digitised and tran...

Page 3: ...on P200A Feedback potentiometer 500 Ω add on P500A Feedback potentiometer 500 Ω add on grau P500A GR Feedback potentiometer 1 kΩ add on P1000A Feedback potentiometer 1 kΩ add on grau P1000A GR Feedback potentiometer 2 8 kΩ add on P2800A Feedback potentiometer 2 8 kΩ add on grau P2800A GR Feedback potentiometer 5 kΩ add on P5000A Feedback potentiometer 5 kΩ add on grau P5000A GR Feedback potentiome...

Page 4: ...D A C2 D B Connection with passive sensor e g Pt1000 Ni1000 NTC 1 2 T 3 5 6 7 Ni1000 PT1000 NTC 28 98 C 35 155 C 10 160 C 1 850 1600 Ω 2 850 1600 Ω 2 200 Ω 60 kΩ 2 MFT C2 C1 D D 1 depending on type 2 Resolution 1 Ohm Connection with active sensor e g 0 10 V 0 50 C 1 2 T 3 5 6 7 MFT C2 C1 D D Possible voltage range 0 32 V resolution 30 mV Connection with switching contact e g Δp monitor 1 2 T 3 5 6...

Page 5: ...Push button and LED display yellow Off On Flickering Press button Standard mode Adaptation or synchronising process active or actuator in address mode LED display green flashing BACnet Modbus communication active In operation 3 s Switch address mode on and off In address mode Address setting by pressing several times When starting 5 s Reset to factory setting Communication 4 Gear disengagement but...

Page 6: ...ACnet MS TP and Modbus RTU address is made up of the set basic address plus the short address e g 100 7 107 Service Tools connection The actuator can be parametrised by ZTH EU via the service socket For an extended parametrisation the PC tool can be connected AC 24 V DC 24 V 1 2 T 3 5 6 7 MFT D D BELIMO PC Tool USB MP USB i esc OK ZTH EU Dimensions mm Spindle length L Min 52 Min 20 Clamping range ...

Reviews: