Safety   Certification IEC/EN

IEC/EN 60730-1 and IEC/EN 60730-2-14

  Certification UL

cULus according to UL60730-1A, UL60730-2-

14 and CAN/CSA E60730-1:02

  Certification UL note

The UL marking on the actuator depends on the 

production site, the device is UL-compliant in 

any case

  Mode of operation

Type 1

  Rated impulse voltage supply / control

0.8 kV

  Control pollution degree

3

  Ambient temperature

-30...50°C

  Storage  temperature

-40...80°C

  Ambient humidity

Max. 95% r.H., non-condensing

  Servicing

maintenance-free

Weight   Weight

1.7 kg

Safety notes

!

•  The device must not be used outside the specified field of application, especially not 

in aircraft or in any other airborne means of transport.

•  Outdoor application: only possible in case that no (sea) water, snow, ice, insolation 

or aggressive gases interfere directly with the actuator and that is ensured that the 

ambient conditions remain at any time within the thresholds according to the data 

sheet.

•  Only authorised specialists may carry out installation. All applicable legal or 

institutional installation regulations must be complied during installation.

•  The device may only be opened at the manufacturer’s site. It does not contain any 

parts that can be replaced or repaired by the user.

•  Cables must not be removed from the device.
•  To calculate the torque required, the specifications supplied by the damper 

manufacturers concerning the cross-section, the design, the installation site and the 

ventilation conditions must be observed.

•  The device contains electrical and electronic components and must not be disposed 

of as household refuse. All locally valid regulations and requirements must be 

observed.

Product features

Mode of operation

The actuator is fitted with an integrated interface for BACnet MS/TP, Modbus RTU and 

MP-Bus. It receives the digital positioning signal from the control system and returns 

the current status.

Converter for sensors

Connection option for a sensor (passive, active or with switching contact). In this way, 

the analogue sensor signal can be easily digitised and transferred to the bus systems : 

BACnet, Modbus or MP-Bus.

Parametrisable actuators

The factory settings cover the most common applications. Single parameters can be 

modified with the Belimo Service Tools MFT-P or ZTH EU.

The communication parameters of the bus systems (address, baud rate etc.) are set 

with the ZTH EU. Pressing the “Address” button on the actuator while connecting the 

supply voltage, resets the communication parameters to the factory setting.

Quick addressing: The BACnet and Modbus address can alternatively be set using the 

buttons on the actuator and selecting 1...16. The value selected is added to the «Basic 

address» parameter and results in the effective BACnet and Modbus address.

Combination analogue - communicative 

(hybrid mode)

With conventional control by means of an analogue positioning signal, BACnet or 

Modbus can be used for the communicative position feedback

Simple direct mounting

Simple direct mounting on the damper shaft with a universal shaft clamp, supplied with 

an anti-rotation device to prevent the actuator from rotating.

Manual override

Manual override with push-button possible (the gear is disengaged for as long as the 

button is pressed or remains locked).

Adjustable angle of rotation

Adjustable angle of rotation with mechanical end stops.

GM24A-MOD

Rotary actuator, modulating, communicative, hybrid, AC/

DC 24 V, 40 Nm

Technical data

www.belimo.com

GM24A-MOD • en-gb • 2020-04-21 • subject to changes

2

Summary of Contents for GM24A-MOD

Page 1: ...y 5 Direction of motion motor selectable with switch 0 1 Direction of motion note Y 0 At switch position 0 ccw rotation 1 cw rotation Direction of motion variable electronically reversible Manual override with push button can be locked Angle of rotation Max 95 Angle of rotation note can be limited on both sides with adjustable mechanical end stops Running time motor 150 s 90 Running time motor var...

Page 2: ...e observed Product features Mode of operation The actuator is fitted with an integrated interface for BACnet MS TP Modbus RTU and MP Bus It receives the digital positioning signal from the control system and returns the current status Converter for sensors Connection option for a sensor passive active or with switching contact In this way the analogue sensor signal can be easily digitised and tran...

Page 3: ...on P200A Feedback potentiometer 500 Ω add on P500A Feedback potentiometer 500 Ω add on grau P500A GR Feedback potentiometer 1 kΩ add on P1000A Feedback potentiometer 1 kΩ add on grau P1000A GR Feedback potentiometer 2 8 kΩ add on P2800A Feedback potentiometer 2 8 kΩ add on grau P2800A GR Feedback potentiometer 5 kΩ add on P5000A Feedback potentiometer 5 kΩ add on grau P5000A GR Feedback potentiome...

Page 4: ...D A C2 D B Connection with passive sensor e g Pt1000 Ni1000 NTC 1 2 T 3 5 6 7 Ni1000 PT1000 NTC 28 98 C 35 155 C 10 160 C 1 850 1600 Ω 2 850 1600 Ω 2 200 Ω 60 kΩ 2 MFT C2 C1 D D 1 depending on type 2 Resolution 1 Ohm Connection with active sensor e g 0 10 V 0 50 C 1 2 T 3 5 6 7 MFT C2 C1 D D Possible voltage range 0 32 V resolution 30 mV Connection with switching contact e g Δp monitor 1 2 T 3 5 6...

Page 5: ...Push button and LED display yellow Off On Flickering Press button Standard mode Adaptation or synchronising process active or actuator in address mode LED display green flashing BACnet Modbus communication active In operation 3 s Switch address mode on and off In address mode Address setting by pressing several times When starting 5 s Reset to factory setting Communication 4 Gear disengagement but...

Page 6: ...ACnet MS TP and Modbus RTU address is made up of the set basic address plus the short address e g 100 7 107 Service Tools connection The actuator can be parametrised by ZTH EU via the service socket For an extended parametrisation the PC tool can be connected AC 24 V DC 24 V 1 2 T 3 5 6 7 MFT D D BELIMO PC Tool USB MP USB i esc OK ZTH EU Dimensions mm Spindle length L Min 52 Min 20 Clamping range ...

Reviews: