background image

Heat & Glo  •  6000GLX-IPI-S/-R, 6000GLX-IPILP-S/-R  •  2101-900  Rev. K  •  12/07

32

E.     Installing Wall Shield Firestops and Horizontal Termination Cap

NOTE: 

Where required, an exterior wall fl ashing is 

available.

When penetrating a brick wall, a brick extension kit 
is available for framing the brick.

Installing the Horizontal Termination Cap

Vent termination must not be recessed in the wall. Siding 
may be brought to the edge of the cap base. 

Flash and seal as appropriate for siding material at outside 
edges of cap.

When installing a horizontal termination cap, follow the cap 
location guidelines as prescribed by current 

ANSI Z223.1 

and 

CAN/CGA-B149

 installation codes.

Figure 8.14   Hole and Vent Pipe

WALL SHIELD

FIRESTOP

(EXTERIOR)

WALLSHIELD

FIRESTOP

(INTERIOR)

HEAT SHIELD

TRIM HEAT SHIELD IF
TOO LONG. 

USE EXTENDED HEAT 
SHIELD (DVP-HSM-B) IF 
TOO SHORT.

Figure 8.15  Heat Shield, Interior & Exterior Wall Shield Firestops

Fire Risk
Exhaust Fumes Risk
Impaired Performance of Appliance

 

WARNING

•  Ensure vent components are locked together correctly.
•  Pipe may separate if not properly joined.

•  Position the wall shield fi restops on both sides of the 

hole previously cut and secure the wall shield fi restops 
with nails or screws. 

•  The heat shields of the wall shield fi restops 

MUST BE

 

placed towards the top of the hole.

•  Continue the vent run through the wall shield fi restops.

Fire Risk.   
Explosion Risk.

Do NOT pack insulation or other 
combustibles between fi restops.

WARNING

•  ALWAYS maintain specifi ed clearances around venting 

and fi restop systems.

• Install 

fi restops as specifi ed.

Failure to keep insulation or other material away from vent 
pipe may cause fi re.

VENT PIPE

1 in. (25.4 mm)

10 in.

(254mm)

10 in.

(254mm)

For Horizontal Runs 

- Wall shield fi restops are 

REQUIRED

 on 

both sides of a combustible wall through which the vent passes.

NOTE: Model SLK-01TRD does not need an exterior 
wall shield

 

fi restop on an exterior combustible wall.

To install wall shield fi restops for horizontal runs that pass 
through either interior or exterior walls:

Cut a 10 in. x 10 in. (254mm x 254mm) hole for SL-D-
series pipe. The center of the framing hole is one (1) inch 
(25.4mm) above the center of the horizontal vent pipe.

WARNING

Fire Hazard

 

Impaired performance of appliance

• Telescoping 

fl ue section of termination 

cap MUST be used when connecting pipe 
section to termination cap.

•  Maintain a 1-1/2 inch minimum overlap on 

telescoping fl ue section of termination cap.

Burn  Risk
•  Termination caps may be hot. Consider their 

proximity to doors or other traffi c areas. 

•  Local codes may require installation of a cap 

shield to prevent anything or anyone from 
touching the hot cap.

WARNING

Summary of Contents for 6000GLX-IPI-R

Page 1: ... Standard for Installation in Mobile Homes CAN CSA Z240MH This appliance is only for use with the type s of gas indicated on the rating plate Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or technicians supervised by an NFI certified professional Leave this manual with party res...

Page 2: ...arding your specific appliance can be found on the rating plate usually located in the control area of the appliance Homeowner Reference Information Heat Glo a of Hearth Home Technologies Inc 20802 Kensington Boulevard Lakeville MN 55044 brand Not for use with solid fuel Ne doit pas entre utilise avec un combustible solide This appliance must be installed in accordance with local codes if any if n...

Page 3: ...Vent Sections 27 B Disassembly of Vent Sections 29 C Installing Heat Shield Termination Cap 30 D SL D Pipe Assembly of Vent Sections 31 E Installing Wall Shield Firestops and Horizontal Termination Caps 32 F Installing Roof Flashing and Vertical Termination Cap 33 Table of Contents Î Contains updated information Section 9 Gas Information A Fuel Conversions 35 B Gas Pressures 35 C Gas Connection 35...

Page 4: ...iters Laboratories Inc UL TYPE Direct Vent Gas Appliance Heater STANDARD ANSI Z21 88 2000 CSA2 33 M98 UL307B WARNING Do NOT use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water This product is listed to ANSI standards for Vented Gas Ap...

Page 5: ... read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5 08 2 a 1...

Page 6: ...the packaging The vent system components and trim doors are shipped in separate packages The gas logs may be packaged separately and must be field installed Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starting the in stallation Follow these instructions carefully dur ing the installation to ensure maximum safety an...

Page 7: ...ecting a location for your appliance it is important to consider the required clearances to walls see Figure 3 1 Figure 3 1 Appliance Locations NOTE For actual appliance dimensions refer to Sec tion 16 In addition to these framing dimensions also reference the following sections Clearances and Mantel Projections Sections 3 C and 3 D Vent Clearances and Framing Section 6 A B C D E F G H Inches 51 4...

Page 8: ...gional codes for the rest of the home Additionally in regions where cold air infiltration may be an issue the inside surfaces may be sheetrocked and taped for maximum air tightness To further prevent drafts the wall shield and ceiling firestops should be caulked with high temperature caulk to seal gaps Gas line holes and other openings should C Clearances Figure 3 2 Clearances to Combustibles Fire...

Page 9: ... TOP EDGE OF THE OPENING 5 10 11 12 2 1 2 13 14 15 16 17 18 19 32 TO CEILING 9 10 11 12 8 7 6 5 4 3 25 18 A Top View INTERIOR WALL FIREPLACE OPENING B MANTEL LEG OR WALL PROJECTIONS Note All measurements in inches If A minimum is ____ then B maximum is_____ A Inches 2 7 16 3 7 16 4 7 16 5 7 16 6 7 16 7 7 16 Millimeters 62 87 113 138 164 189 B Inches 1 2 3 4 5 Millimeters 25 51 76 102 127 NOTE Meas...

Page 10: ...Measure horizontal clearances from this surface Measure vertical clearances from this surface Figure 4 3 Multiple Vertical Termination Figure 4 2 specifies minimum vent heights for various pitched roofs See Figure 4 4 for specific clearances 3 foot minimum in snow regions HORIZONTAL OVERHANG VERTICAL WALL GAS DIRECT VENT TERMINATION CAP 12 X ROOF PITCH IS X 12 LOWEST DISCHARGE OPENING 2 FT MIN 20 ...

Page 11: ...driveway deck porch veranda or balcony use of a listed cap shield is suggested See vents components page NOTE 2 Termination in an alcove space spaces open only on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10 feet of a termination cap ...

Page 12: ... allowed between two 450 elbows see Figure 5 1 Figure 5 1 A Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams C Measuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards 1 Pipe measurements are shown using the effective length of pipe see Figure 5 2 2 Measurements are made from the applian...

Page 13: ... 12 2 m Maximum H1 H2 20 ft 6 1 m Maximum Fire Risk Explosion Risk Do NOT pack insulation or other combustibles between ceiling firestops ALWAYS maintain specified clearances around venting and firestop systems Install wall shield and ceiling firestops as specified Failure to keep insulation or other material away from vent pipe may cause fire NOTE The 6000 series fireplaces can adapt to SL series...

Page 14: ...mm 3 ft 914 mm 6 in 152 mm 2 ft 610 mm 1 ft 305 mm 6 ft 1 8 m 1 ft 305 mm 6 ft 1 8 m 2 ft 610 mm 11 ft 3 4 m 2 ft 610 mm 10 ft 3 1 m 3 ft 914 mm 16 ft 4 9 m 3 ft 914 mm 14 ft 4 3 m H1 H2 20 ft 6 1 m Maximum V1 V2 H1 H2 40 ft 12 2m Maximum Fire Risk When using DVP HRC SS and DVP HRC ZC SS termination caps on top vented fireplaces a 6 inch minimum vertical vent section is required before installing ...

Page 15: ...nal vertical termina tion baffle should be used V1 40 ft Max 12 4 m V1 3 ft Min 914mm Flue Restrictor Instructions 1 Remove the top piece of refractory if already installed see Figure 5 7 Figure 5 8 Flue Restrictor 2 Break the Flue Restrictor into two pieces Do this by bending the part back and forth until it breaks see Figure 5 8 Figure 5 6 Figure 5 7 BREAK HERE TOP REFRACTORY FLUE RESTRICTOR ...

Page 16: ...s see Figure 5 10 3 Match the amount of vertical you have in the sys tem with the chart to find the appropriate position to set the Flue Restrictor see Figure 5 9 Figure 5 9 1 2 3 4 5 SETTINGS 1 2 3 4 5 Vertical TOP VENT REAR VENT NG LP NG LP 4 ft 1 1 No Restrictor No Restrictor No Restrictor 8 ft 2 2 1 2 1 1 No Restrictor 15 ft 3 3 3 2 2 2 1 2 20 ft 3 4 3 3 3 3 2 3 25 ft 3 4 3 3 3 3 2 3 30 ft 4 4...

Page 17: ...on continued Three Elbows V1 H1 H2 V2 V1 V2 Minimum H1 H2 Maximum Elbow only 1 ft 305 mm 1 ft 305 mm 6 in 152 mm 2 ft 610 mm 2 ft 610 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 4 ft 1 2 m 3 ft 914 mm 9 ft 2 7 m 9 ft 2 7 m 4 ft 1 2 m 18 ft 5 5 m 18 ft 5 5 m H1 H2 20 ft 6 1m Maximum V1 V2 H1 H2 40 ft 12 2m Maximum ...

Page 18: ... R 6000GLX IPILP S R 2101 900 Rev K 12 07 18 3 Rear Vent Horizontal Termination Figure 5 13 Figure 5 14 No Elbow One 450 Elbow H1 16 in 406 mm Maximum Do not use a 450 elbow in corner installations Use two 900 elbows instead ...

Page 19: ...2 m 7 ft 2 1 m 3 ft 914 mm 3 ft 914 mm 9 ft 2 7 m 12 ft 3 7 m 3 ft 914 mm 4 ft 1 2 m 18 ft 5 5 m 20 ft 6 1 m V1 H1 H2 40 ft 12 2m Maximum H1 3 ft 914mm Maximum H1 H2 20 ft 6 1m Maximum H1 Maximum V1 Minimum H2 H3 H1 H2 H3 Maximum 1 ft 305 mm Back to Back 90º Elbows 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 6 in 152 mm 1 5 ft 457 mm 3 5 ft 1 0 m 3 ft 914 mm 1 ft 305 mm 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm ...

Page 20: ... 6 in 152 mm 2 ft 610 mm 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm 7 ft 2 1 m 4 ft 1 2 m 8 ft 2 4 m 5 ft 1 5 m 8 ft 2 4 m V1 H1 40 ft 12 2 m Maximum H1 8 ft 2 4 m Maximum H1 H2 Maximum V1 Minimum Back to Back 90 Elbows 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 4 ft 1 2 m 9 ft 2 7 m 6 ft 1 8 m 12 ft 3 7 m 8 ft 2 4 m 15 ft 4 6 m V1 H1 40 ft 12 2 m Maximum H1 H2 8 ft 2 4 m Maximum ...

Page 21: ...mum No specific restrictions on this value EXCEPT V1 H1 H2 H3 cannot exceed 40 ft 12 2m Maximum H1 H2 H3 8 ft 2 4 m Maximum INSTALLED HORIZONTALLY H2 H3 H1 V1 H1 V1 H2 V2 H1 Maximum V1 Minimum H2 H1 H2 Maximum 2 ft 610 mm 6 in 152 mm 2 ft 610 mm 4 ft 1 2 m 3 ft 914 mm 1 ft 305 mm 4 ft 1 2 m 7 ft 2 1 m 5 ft 1 5 m 2 ft 610 mm 6 ft 1 8 m 11 ft 3 4 m 7 ft 2 1 m 3 ft 914 mm 8 ft 2 4 m 15 ft 4 6 m 8 ft ...

Page 22: ...ched to them Fire Risk Explosion Risk Maintain vent clearance to combustibles as specified WARNING Do not pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause fire B Wall Penetration Framing 1 in CLEARANCE AROUND VERTICAL SECTIONS 3 in TOP CLEARANCE 1 in SIDE AND BOTTOM CLEARANCE Figure 6 1 Pipe Clearances Figure 6 3 Exterior...

Page 23: ...Fire Hazard Keep loose materials or blown insulation from touching the vent pipe Installing Attic Shield Note An additional ceiling firestop is not required if attic shield is used Frame opening for attic shield Attic shield may be installed above or below ceiling see Figure 6 5 Secure with three fasteners on each side Fold tabs at top of attic shield in toward vent pipe Tabs must keep vent pipe c...

Page 24: ...m this step Figure 7 3 Remove the white gasket material covering the seal cap CAUTION Sharp Edges Wear protective gloves and safety glasses dur ing installation Figure 7 4 Remove the seal cap Figure 7 5 Remove the insulation basket and white insu lation from the center vent pipe Figure 7 1 For top vent remove the two screws holding the elbow heat shield in place Use this heat shield over the first...

Page 25: ... and secure the appliance see Figure 7 9 Nailing tabs are pro vided to secure the appliance to the framing members Venting refer to Vent Clearances and Framing Section 6 for hole location Place the appliance into position Level appliance from side to side and front to back Shim the appliance as necessary It is acceptable to use wood shims Bend out nailing tabs on each side Keep nailing tabs flush ...

Page 26: ...lar around the exposed hole and attach it to the fireplace with 3 screws NOTE Do this BEFORE final positioning of the fireplace 3 Determine the location for the air register fan housing assembly Reference the Heat Zone kit instructions for the remaining installation steps NOTE There must be NO INSULATION or other combustibles inside the framed firestop opening Figure 7 10 HEAT ZONE GAS ATTACHES HE...

Page 27: ...onfirm it has com pletely locked into place It is acceptable to use screws no longer than 1 inch to hold outer pipe sections together If predrilling holes do NOT penetrate inner pipe For 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no lo...

Page 28: ...ection with three screws The other end of the MI pipe section can then be attached by fitting another pipe section to it and snapping it together as normal Figure 8 6 Slip Section Pilot Holes Figure 8 7 Screws into Slip Section Figure 8 5 Figure 8 4 Seams INCORRECT CORRECT Note Make sure that the seams are not aligned to prevent unintentional disconnection Note When installing a vent system with a...

Page 29: ...very 5 feet with a vent support or plumber s strap Figure 8 8 Securing Vertical Pipe Sections To disassemble any two pieces of pipe rotate either section see Figure 8 10 so that the seams on both pipe sections are aligned see Figure 8 11 They can then be carefully pulled apart Figure 8 11 Align and Disassemble Vent Sections Figure 8 10 Rotate Seams for Disassembly Figure 8 9 Securing Horizontal Pi...

Page 30: ...wall thickness does not allow the required 1 1 2 inch 38 mm heat shield overlap when installed an extended heat shield DVP HSM B must be used Important Notice Heat shields may not be field constructed The extended heat shield DVP HSM B may need to be cut to length You will attach the cut heat shield to the existing cap heat shield or wall shield firestop heat shield refer to Figure 8 12 using the ...

Page 31: ...members Attach the First Vent Component to Starting Collars To attach the first vent component to the starting collars of the appliance Lock the vent components into place by sliding the concentric pipe sections with four 4 equally spaced in terior beads into the appliance collar or previously installed component end with four 4 equally spaced indented sec tions When the internal beads of each out...

Page 32: ...he heat shields of the wall shield firestops MUST BE placed towards the top of the hole Continue the vent run through the wall shield firestops Fire Risk Explosion Risk Do NOT pack insulation or other combustibles between firestops WARNING ALWAYS maintain specified clearances around venting and firestop systems Install firestops as specified Failure to keep insulation or other material away from v...

Page 33: ... the pilot holes in the outer collar of the cap into the outer flue of the pipe see Figure 8 17 Roof Pitch H Min Ft Flat to 6 12 1 0 Over 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 6 0 Over 16 12 to 18 12 7 0 Over 18 12 to 20 12 7 5 Over 20 12 to 21 12 8 0 Figure 8...

Page 34: ... storm collar around the exposed pipe section and align brackets Insert a bolt provided through the brackets and tighten nut to complete storm collar assembly see Figure 8 20 Slide the assembled storm collar down the pipe section until it rests on the roof flashing Caulk around the top of the storm collar see Figure 8 17 CAUTION Sharp Edges Wear protective gloves and safety glasses dur ing install...

Page 35: ...f the appliance provided the hole in the outer wrap does NOT exceed 2 1 2 inches in diameter and does not penetrate the firebox NOTE A listed and Commonwealth of Massachusetts ap proved 1 2 inch 13mm T handle manual shut off valve and flexible gas connector are connected to the 1 2 inch 13mm control valve inlet If substituting for these components please consult local codes for compliance Pressure...

Page 36: ... in Canada check with local authorities Ensure that gas line does not come in contact with outer wrap of appliance Follow local codes Incoming gas line should be piped into the valve com partment and connected to the 1 2 inch connection on the manual shutoff valve CHECK FOR GAS LEAKS Explosion Risk Fire Risk Asphyxiation Risk Check all fittings and connections Do not use open flame After the gas l...

Page 37: ...recommended that the junction box be installed at this time to avoid reconstruction The battery pack requires two D cell batteries not included Batteries shouldn t be placed into the holder until needed The higher temperatures will shorten their life CAUTION Battery polarity must be correct or module damage will occur Optional Accessories Requirements Wiring for optional accessories should be done...

Page 38: ...on IPI Wiring Diagram ORG BLK NOT CONNECTED CONNECT TO ORIFICE SOLENOID RED WIRE TO RED WIRE BLACK WIRE TO BLACK WIRE BATTERY PACK NOT USED F O L CAPACITOR PART IS ENCLOSED IN SHRINK TUBING WALL SWITCH BACK VIEW CORD ASSEMBLY 2 WHT T O GROUND CLIP Note Appliance will not operate unless properly grounded ...

Page 39: ...able on both sides of opening Figure 11 1 Clearances to Mantels or other Combustibles above Appliance Fire Risk Do NOT obstruct air inlet or outlet grilles Do NOT modify grilles Modifying or covering grilles could cause temperature rise and fire hazard WARNING Finishing materials must not interfere with Air flow through grilles or louvers Operation of louvers or doors Access for service WARNING Ri...

Page 40: ...t to know what kind of a door and what kind of finishing material is going to be used on the fireplace The table below shows the door models and the finishing material thickness allowed For an inside fit there is an available template to assist with sizing the finishing material Figure 11 4 Folio Door DOOR FIT FINISH MATERIAL MAXIMUM THICKNESS SEE FIGURE Folio Inside Any 11 4 Arcadia Overlap 1 inc...

Page 41: ...ace for shipping Cut and remove the rubber bands at this time D Accessories Install approved accessories per instructions included with accessories See Service Parts List for appropriate acces sories Refer to Section 16 WARNING E Install the Refractory STEP 2 Place the left side refractory onto the left side of the burner Push the back refractory against the back wall Place the bumps on the bottom...

Page 42: ...acement of Embers EMBER MATERIAL Figure 12 5 STEP 5 Hold the top refractory with the brick pattern facing down Bring the back edge into the firebox slightly higher than the front edge Bring the back edge all the way to the metal back wall of the fireplace Raise the front edge up until it clears the side refractory pieces Drop the back edge down and nest the sides and back into the groove around th...

Page 43: ...he fireplace See Figure 12 7 G Positioning the Logs If the gas logs have been factory installed they should not need to be positioned If the logs have been packaged separately refer to the following instructions Figure 12 8 Figure 12 10 Top View 2101 910 1 1 2 2 3 3 4 4 5 5 STEP 3 Log 1 NG SRV2101 085 Log 1 LP SRV2101 087 Log 1 is the left burning log The air shutter in the end of the burner tube ...

Page 44: ...g 3 SRV2101 197 Place log 3 on top of the burner surface in front of the hump Slide it back against the hump and the V notch in the bottom of the log rests into the second grate tine from the left STEP 6 Log 4 SRV386 716 Place log 4 on top of the left side of log 2 The bottom of this log has a slot in it that goes over the tab molded into the top of log 2 The other end of the log rests in the flat...

Page 45: ...m of this log Place the slot over the tab on top of the right end of log 2 The end of this log has a square notch in it that rests into the second tine from the right on the grate Note May be necessary to tilt grate forward to interlock bottom notch in log STEP 9 Log 7 SRV530 703 Place log 7 on top of log 1 and the grate The lower right end of the log rests against the second tine from the left on...

Page 46: ...trim surround kits as desired Marble brass brick tile or other noncombustible materials can be used to cover up the gap between the sheet rock and the appliance Do not obstruct or modify the air inlet outlet grilles K Air Shutter Setting This appliance has an adjustable air shutter which controls the primary air factory set for the minimum vertical vent run see Figure 12 24 If your installation ha...

Page 47: ...any part of the control system and any gas control which has been under water WARNING This appliance has an Intellifire ignition system Before operating this appliance have a qualified tech nician Remove all shipping materials from inside and or underneath the firebox Review proper placement of logs rockwool lava rock and vermiculite Check the wiring Check the air shutter adjustment Ensure that th...

Page 48: ...IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building DO NOT CONNECT 110 VAC TO THE CONTROL VALVE Improper installation adjustment al teration service or maintenance can cause injury or property damage Refer to the owner s information manual pro vided with this appliance This appliance needs fresh air for safe operation and must b...

Page 49: ...l if absent or if appliance will not be used for an extended period of time Property damage possible from elevated temperatures CAUTION Fire Hazard Keep combustible materials gasoline and other flammable vapors and liquids clear of appliance Do NOT store flammable materials in WARNING the appliance s vicinity Do NOT use gasoline lantern fuel kerosene charcoal lighter fluid or similar liquids in th...

Page 50: ...move and verify continuity of each wire in wiring harness c Improper wall switch wiring Verify that 110 VAC power is ON to junction box d Module not grounded Verify black ground wire from module wire harness is grounded to metal chassis of appliance e Faulty module Turn ON OFF rocker switch or wall switch to OFF position Remove ignitor wire I from module Place ON OFF Rocker switch or wall switch i...

Page 51: ...ter with ohms set at lowest range e Faulty module Turn ON OFF rocker switch or wall switch to OFF posi tion Remove ignitor wire I from module Place ON OFF Rocker switch or wall switch in ON position Hold ground wire about 3 16 inch away from I terminal on module If there is no spark at I terminal module must be replaced If there is a spark at I terminal module is fine Inspect pilot assembly for sh...

Page 52: ...or Avoid striking scratching or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white film Do NOT clean glass when hot Turn off appliance after 3 4 hours of operation and ALLOW TO COOL Remove and clean glass assembly Replace glass assembly and operate appliance for additional 12 hours Refer to maintenance instructions Risk of injury or property damage Before s...

Page 53: ... and repaint as necessary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for plugged ports corrosion or deterioration Replace burner if necessary 3 Replace ember materials with new dime size and shape pieces Do not block ports or obstruct lighting paths 4 Check for...

Page 54: ...Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For framing dimensions and clearances refer to Section 3 Figure 16 1 Appliance Dimensions Location Inches Millimeters J 11 5 8 295 K 28 1 2 724 L 14 1 4 362 M 8 dia 203 N 2 1 8 54 O 6 7 8 175 P 38 965 Q 1 25 R 39 3 8 1000 Location Inches Millimeters A 41 1041 B 36 1 8 918 C 33 1 2 851 D 34 5 8 879 E 2 3 8 60 F 5 12...

Page 55: ...n 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP 10 in 254 mm 24 in 610 mm DVP HVS Vent Support DVP AS Attic Shield DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 276 mm 13 mm Pipe Effective Length Inches Millimeters DVP4 4 102 DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 914...

Page 56: ... 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield B Vent Components Diagrams continued Figure 16 3 DVP vent components EFFECTIVE LENGTH Term Cap Minimum Maximum Tr...

Page 57: ...m 24 5 8 in 625 mm 13 1 4 in 367 mm RF12M Roof Flashing Multi pak BEK Trap Cap Brick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADD Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing DV...

Page 58: ...HW Vertical Termination Cap High wind B Vent Components Diagrams continued Figure 16 5 DVP vent components PVK 80 For use with IPI and DSI appliances only 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT Fir...

Page 59: ... caps on top vented fireplaces a six inch minimum vertical vent section is required before installing first elbow WARNING DVP HRC SS DVP HRC ZC SS HORIZONTAL TERMINATION CAP 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm 10 7 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm Figure 16 6 DVP vent components ...

Page 60: ...Length Inches SL 06D 5 3 4 SL 09D 8 3 4 SL 12D 11 3 4 SL 12 17D 11 3 4 to 16 3 4 SL 17 24D 16 3 4 to 23 3 4 SL 24D 23 3 4 SL 36D 35 3 4 SL 48D 47 3 4 SL SERIES There must be a 25 reduction in total H when using the snorkel cap except when using the simple up and out installation 6 1 2 in For use on Intellifire appliances only SL SERIES WALL BRACKET ...

Page 61: ... S R 2101 900 Rev K 12 07 61 C Service Parts Service Parts Diagram 6000GLX IPI Beginning Manufacturing Date May 2006 Ending Manufacturing Date ______ Log Assembly Part number list on following page 1 2 3 4 5 6 7 17 10 12 15 14 16 9 11 13 8 ...

Page 62: ...y Red R 4 pieces Red BRICK 6GLX R N Refractory Stratford Tan S 4 pieces Stratford BRICK 6GLX S N 8 Back Refractory R SRV2101 570 N Back Refractory S SRV2101 470 N 9 Left Refractory R SRV2101 571 N Left Refractory S SRV2101 471 N 10 Right Refractory R SRV2101 572 N Right Refractory S SRV2101 472 N 11 Top Refractory R SRV2101 573 N Top Refractory S SRV2101 473 N 12 Burner Assembly Red R SRV2101 008 ...

Page 63: ...01 900 Rev K 12 07 63 Valve Assembly Diagram Service Parts 6000GLX IPI R S Beginning Manufacturing Date May 2006 Ending Manufacturing Date ______ IPI Valve Assembly Part number list on following page 14 5 7 17 18 15 19 6 3 13 12 1 2 4 9 11 10 8 16 ...

Page 64: ...4 Valve Bracket 2103 114 N 5 Flex Ball Valve Assembly 302 320A Y 7 Bulb Socket Assembly 2101 041 Y 8 Valve NG 750 500 Y Valve LP 750 501 Y 9 Orifice NG 39C 582 839 Y Orifice LP 54C 582 854 Y 10 Control Module 593 592 Y 11 Wire Assembly 593 590A Y 12 Manifold Assembly Solenoid 2101 071 Y 13 Orifice NG 53C Qty 2 582 853 Y Orifice LP 68C Qty 2 582 868 Y 14 Flex 12 2101 293 Y 15 Wall Switch Wire 2095 ...

Page 65: ...d with the Product or added thereafter are NOT covered by this warranty unless expressly authorized and approved by HEAT GLO in writing 6 Any damages caused by environmental conditions inadequate ventilation or drafting caused by tight sealing construction of the structure air handling devices such as exhaust fans or forced air furnaces or other such causes are not covered by this warranty 7 This ...

Page 66: ...______________________________________________________________ ________________________________________________________________________________ Printed in U S A Copyright 2007 DO NOT DISCARD THIS MANUAL CAUTION Leave this manual with party responsible for use and operation Read understand and follow these instructions for safe installation and operation Important operating and maintenance instruct...

Reviews: