Heat & Glo • 6000GLX-IPI-S/-R, 6000GLX-IPILP-S/-R • 2101-900 Rev. K • 12/07
16
Figure 5.11
Two Elbows
V
1
H
1
Maximum
V
2
V
1
+ V
2
Min.
Elbow only
2 ft.
610 mm
*
*
*
6 in.
152 mm
6 ft.
1.8 m
*
*
*
2 ft.
610 mm
11 ft.
3.4 m
*
*
*
3 ft.
914 mm
16 ft.
4.9 m
*
*
*
4 ft.
1.2 m
20 ft
6.1 m
*
*
*
V
1
+ V
2
+ H
1
= 50 ft (15.2 m) Maximum
*No specifi c restrictions on this value EXCEPT
V
1
+ V
2
+ H
1
cannot exceed 50 ft (15.2 m)
Figure 5.10
4
. Center the Flue Restrictor on vent and secure in place
by using two self-tapping screws (see Figure 5.10).
3.
Match the amount of vertical you have in the sys-
tem with the chart to fi nd the appropriate position
to set the Flue Restrictor (see Figure 5.9).
Figure 5.9
1 2 3 4 5
SETTINGS
1 2 3 4 5
Vertical
TOP VENT
REAR VENT
NG
LP
NG
LP
4 ft.
1-1
No
Restrictor
No
Restrictor
No
Restrictor
8 ft.
2-2
1-2
1-1
No
Restrictor
15 ft.
3-3
3-2
2-2
1-2
20 ft.
3-4
3-3
3-3
2-3
25 ft.
3-4
3-3
3-3
2-3
30 ft.
4-4
3-4
3-4
3-3
35 ft.
4-4
3-4
3-4
3-3
40 ft.
5-4
4-4
4-4
3-4
Note:
If the DVP-2SL adapter and SL pipe is used, you MUST subtract one number from the table above. Example: Top
vent 40 ft. vertical with DVP pipe = 5-4. Top vent 40 ft. vertical with SL pipe = 4-3.
Î