HWE-SS Elite Installation and Operation Manual

•   For example; when the calculated temperature is 160°F and the Setback is set to 20°F, a setback call 

will change the Set Point to (160v - 20°F) 140°F.

•   A typical use for Setback is to provide less system temperature to a building during the night or on 

the weekends when building is not occupied, but heat is still required.

•   The Setback is activated by closing/shorting the P+ and P- terminals using an external timer.

Boost

Options: 

 Yes, No  

Default: No

SET

SET

SET

SET

SET

SET

/Settings>/Setback/Boost.

•   The morning Boost is designed to return the building to comfortable ambient temperatures after the 

Night (Setback) period.  The HWE-SS will accomplish this by running elevated water temperatures 

(will add Setback setting to calculated water temperature) for 30 minutes after the opening of the 

setback terminals P+ and P-.  That is, if the normal set point at a specific outdoor was 145˚F and 

the Setback setting was 20˚F, the boost will raise the system calculated temperature to 165˚F for 30 

minutes after the setback.

Boost: 

No
Yes

System and Outdoor Trim

Options: 

 From -20F

º

/-11

 to +20F

º

/+11

  

Default: 11F

º

/6

SET

SET

SET

SET

SET

SET

/<Maintenance>/Sys. Trm or  Out. Trim

•   The Heat-Timer sensors are very accurate.  However, sometime it might be beneficial to adjust 

the values to match and existing system.  The System and Outdoor Trim values adjust the System 

Sensor and Outdoor Sensor readings using positive or negative values.

System Trim:

+0 F

Outdoor Trim:

+0 F

Enable/Disable Input

•   The HWE-SS will provide heat only if the EXT- and EXT+ terminals are shorted.  If no external 

equipment or switch is connected to these terminals, leave the factory installed jumper.

•   

When the terminals are OPEN, the Target will display TSTAT OPEN.

•   Even if the EXT terminals are open, a call for DHW will energize the output relays based on the 

DHW Priority configuration.

•   

The Enable /Disable terminals can be used as a Summer/Winter switch when connected to an 

external switch.

NOTE:

 On a sensor fault while the Enable/Disable terminals are open, the control will follow the 

Enable /Disable state regardless of the sensor fault condition.

N.O.

S.P.S.T. Output Wiring

120VAC Power Wiring

120VAC Power Source

BLACK

BLACK

Boiler

Output Wiring

N.O.

YELLOW

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

24V

AC

Comm

24VAC Power Wiring

Shield

Shield

System T

emp

Outdoor Sensor

Sensor Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Enable/Disable

Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Input Terminals

{

{

{

{

{

{

Temp

er

atur

e S

ensor

30°F - 250°F

Temp

er

atur

e S

ensor

30°F - 250°F

Temp

er

atur

e S

ensor

150°F - 950°F

Ex

ter

nal Enable/D

isable

Shut

do

wn

Pr

essur

e,

 V

acuum,

 and

4 -20mA

24V

A

C P

o

w

er Supply

N.O.

ORANGE

System Pump

Output Wiring

N.O.

VIOLET

DHW Pump

Output Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

DHW Call

Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Setback/Boost

Wiring

SYSTEM= 

55 F

TSTAT OPEN

  

SYSTEM= 

SHORT

TSTAT OPEN

Summary of Contents for Digi-Span Elite Series HWE-SS

Page 1: ...ydronic Heating Applications The HWE Single Stage HWE SS DIGI SPAN Elite establishes ambient comfort by varying the temperature of the heating system s circulating hot water in response to changes in...

Page 2: ...HW tank to be satisfied quickly Mounting the Controller The HWE SS DIGI Elite is designed to mount on a 1900 4 x4 deep electrical box If additional room is needed for wiring use the extension skirt pr...

Page 3: ...M The Outdoor Sensor must be used when Outdoor Reset is selected as the Control Mode from the Startup menu However in Set Point mode the Outdoor Sensor is optional When connected in that mode it will...

Page 4: ...to the next level Display Unit Options F C Default F SET System Startup Display Unit The HWE SS will offer two different temperature displays If F is selected all temperatures will display in Fahrenh...

Page 5: ...etermine the operating status of the output relays when a sensor reads Short or Open On sensor fault the Set Point will indicate FAULT TGT ON or OFF to indicate the condition of the output and the fau...

Page 6: ...nu Options Click SET Button SYSTEM 148 F TARGET 150 F SET SET SET SET SET S SET SET SET SET SET S Outdoor 48 F Cutoff 65 F Set Point Available when Startup Control Mode Set Point Options From 10 F 23...

Page 7: ...Reset Ratio Max Target Min Target Reset Ratio 10F Offset Min Target 120 F Max Target 170 F Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C...

Page 8: ...or temperature increases 2 F above the Outdoor Cutoff and after the boiler relay has de energized the SYS relay will stay on for a period set by the System Run On This allows the Pump to dissipate the...

Page 9: ...existing system The System and Outdoor Trim values adjust the System Sensor and Outdoor Sensor readings using positive or negative values System Trim 0 F Outdoor Trim 0 F Enable Disable Input The HWE...

Page 10: ...temperature is below the Target water temperature minus the Differential If not wait until the System temperature falls and then the stage LED should come on and the boiler should fire Otherwise remov...

Page 11: ...ED WITH 24VAC T1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor DHW Call Enable Dry Contact Setback Timer Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 1...

Page 12: ...P 6Amp resistive at 120 VAC 60 Hz Control Modes Outdoor Reset Set Point Reset Ratios 12 Standard ranging from 8 1 to 1 4 Outdoor System and one Custom Offset from 40 F 22 C to 40 F 22 C Minimum Water...

Reviews: