Outdoor Reset Mode

•   When Output-On is selected, the HWE-SS will energize the boiler and system relay when System reads Short or Open and Outdoor 

is below Outdoor Cutoff.  Thus, the boiler will run on its limits.  However, if the Outdoor sensor fails and the Outdoor reads Short or 

Open, the HWE-SS will change the Target Set Point to the Max Water Temperature.

•   When Output-Off is selected, the HWE-SS will turn the boiler Off when the System sensor reads Short or Open.  However, when 

the Outdoor sensor fails, reads short or open, the HWE-SS will change the Target Set Point to be the Min Water Temperature.

Set Point Mode

•   When Output On is selected, the HWE-SS will turn the boiler On when the System sensor reads Short or Open.

•   When Output-Off is selected, the HWE-SS will turn boiler Off when the System sensor reads Short or Open.

•   The Outdoor Sensor Short or Open status will not affect the control operation in Set Point mode.

Setting the Control to Factory Default

To Reset the HWE-SS control to its original factory defaults, power down the control.  Hold down the 

SET and DOWN buttons while powering the control back up until the Loading Default Values screen 

appears.  The Display will direct you to the Startup menu after the defaults are loaded to program the 

control.

SET

SET

SET

SET

SET

SET

Loading Default

Values...

NOTE:

 When resetting the control to original factory defaults all control settings will be over written and will no longer exist.

Default Display

The default display will show the current System temperature and the Target temperture.  In addition, 

by clicking the Up or Down button, the display will show the current Outdoor temperture and the 

Outdoor Cutoff.

Operating Menu Options

(Click SET Button)

SYSTEM= 

148 F

TARGET= 

150 F

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

Outdoor= 

48 F

Cutoff= 

65 F

Set Point (Available when Startup Control Mode = Set Point)

Options: 

From -10ºF/-23

º

C to 230ºF/110

º

 

Default: 70

º

F/21

º

C

SET

SET

SET

SET

SET

SET

/Set Point

•   The Set Point option provides the user with an adjustable fixed Target temperature to control the 

system.  If an Outdoor Sensor was connected, the next menu option will show the Outdoor Cutoff, 

otherwise there will be no Outdoor Cutoff option.

•   The Set Point less the Differential should be set above the boiler manufacturer minimum water 

temperature requirements.

Set Point:

 70 F   140 F

SYSTEM= 

68 F

TARGET= 

140 F

Outdoor Reset (Available when Startup Control Mode = Outdoor Reset)

Options: 

From 1(8.00º/1.00

º

) to 12(1.00º/4.00

º

), Custom

 

Default: 7(1.00º/1.00

º

)

SET

SET

SET

SET

SET

SET

/<Out. Reset>/Reset Ratio

•   The Reset Ratio determines how the System water temperature will vary with Outdoor temperature 

(OD).  With any of the ratios, the colder it becomes outside, the hotter the temperature of the system 

water.  The Ratio is measured as; Outdoor : System Water temperature.

•   With a 1.00:4.00 ratio, the System water temperature will increase rapidly as the outside 

temperature falls, hitting the maximum water temperature of 240°F at 24°F outdoor temperature.  

With a 4.00 (OD):1.00 (SYS) ratio, the System water temperature (SYS) will increase slowly as the 

outside temperature falls.

•   The Reset Ratio controls the amount of heat that enters the heating system based on the outdoor 

temperature. A higher numbered Reset Ratio will result in a higher Calculated water temperature. 

See the Reset Ratio chart on the second page.  If the application has radiant heat, a lower numbered 

Reset Ratio curve should be selected.

Reset Ratio O/S:

 Custom
 1(8.00 : 1.00)
 2(4.00 : 1.00)
 3(3.00 : 1.00)
 4(2.00 : 1.00)
 5(1.50 : 1.00)
 6(1.25 : 1.00)

 

7(1.00 : 1.00)

 8(1.00 : 1.25)
 9(1.00 : 1.50)
 10(1.00 : 2.00)
 11(1.00 : 3.00)
 12(1.00 : 4.00)

Summary of Contents for Digi-Span Elite Series HWE-SS

Page 1: ...ydronic Heating Applications The HWE Single Stage HWE SS DIGI SPAN Elite establishes ambient comfort by varying the temperature of the heating system s circulating hot water in response to changes in...

Page 2: ...HW tank to be satisfied quickly Mounting the Controller The HWE SS DIGI Elite is designed to mount on a 1900 4 x4 deep electrical box If additional room is needed for wiring use the extension skirt pr...

Page 3: ...M The Outdoor Sensor must be used when Outdoor Reset is selected as the Control Mode from the Startup menu However in Set Point mode the Outdoor Sensor is optional When connected in that mode it will...

Page 4: ...to the next level Display Unit Options F C Default F SET System Startup Display Unit The HWE SS will offer two different temperature displays If F is selected all temperatures will display in Fahrenh...

Page 5: ...etermine the operating status of the output relays when a sensor reads Short or Open On sensor fault the Set Point will indicate FAULT TGT ON or OFF to indicate the condition of the output and the fau...

Page 6: ...nu Options Click SET Button SYSTEM 148 F TARGET 150 F SET SET SET SET SET S SET SET SET SET SET S Outdoor 48 F Cutoff 65 F Set Point Available when Startup Control Mode Set Point Options From 10 F 23...

Page 7: ...Reset Ratio Max Target Min Target Reset Ratio 10F Offset Min Target 120 F Max Target 170 F Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C...

Page 8: ...or temperature increases 2 F above the Outdoor Cutoff and after the boiler relay has de energized the SYS relay will stay on for a period set by the System Run On This allows the Pump to dissipate the...

Page 9: ...existing system The System and Outdoor Trim values adjust the System Sensor and Outdoor Sensor readings using positive or negative values System Trim 0 F Outdoor Trim 0 F Enable Disable Input The HWE...

Page 10: ...temperature is below the Target water temperature minus the Differential If not wait until the System temperature falls and then the stage LED should come on and the boiler should fire Otherwise remov...

Page 11: ...ED WITH 24VAC T1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor DHW Call Enable Dry Contact Setback Timer Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 1...

Page 12: ...P 6Amp resistive at 120 VAC 60 Hz Control Modes Outdoor Reset Set Point Reset Ratios 12 Standard ranging from 8 1 to 1 4 Outdoor System and one Custom Offset from 40 F 22 C to 40 F 22 C Minimum Water...

Reviews: