Because of the many different physical characteristics of buildings, and the type of 

radiation, i.e., baseboard or radiant, the heat loss varies.  In one building, a 1-degree 

temperature change outdoors may require a change of 1 degree in heating water 

temperature; for another it may require a change of 2, 3, or even 4 degrees in order 

to gain the desired comfort level.  This is known as the Reset Ratio. The middle chart 

shows the wide range of Reset Ratios available for the HWE-SS.

The installer fits the HWE-SS to a specific building by adjusting the Reset Ratio.  With 

a curve of 4 (2:1 reset ratio) a 2-degree change in outdoor temperature will change the 

circulating hot water temperature by 1 degree; at an 11 curve (1:3 reset ratio) an outdoor 

change of 1 degree will change the water temperature by 3 degrees.  Most buildings 

with baseboard radiation require a curve of 6, 7, or 8. Radiant heat applications usually 

require a lower curve.  An external T-Stat input can be used to shut the heating system 

down when the thermostat is satisfied.  Another, is a Setback input that will switch the 

heating system to a lower set point determined by the Set Back setting.

Type of Radiation in Building

Reset Ratio

Offset

Radiators (Steel & Cast Iron)

1.00 (OD) : 1.00 (SYS)

0˚F

Baseboard (Finned copper tube& Cast Iron)

1.00 (OD) : 1.00 (SYS)

0˚F

Radiant (High Mass/Concrete)

4.00 (OD) : 1.00 (SYS)

-10˚F

Radiant (Low Mass/Joists) 

2.00 (OD) : 1.00 (SYS)

-10˚F

Fan Coils & Air Handlers

1.00 (OD) : 1.00 (SYS)

20˚F

An optional domestic hot water input is provided for systems where an indirect tank provides DHW.  During a DHW call, the HWE-SS will 

maintain a constant set point of 200°F regardless of outdoor temperature or the status of the optional external thermostat.  The DHW pump 

will be enabled whenever there is a call for DHW.  The heating system pump can be programmed to turn off during the first hour of a DHW 

call.  This allows the DHW tank to be satisfied quickly.

Mounting the Controller

•   The HWE-SS DIGI-Elite is designed to mount on a 

1900 (4”x4”) deep electrical box.

•   If additional room is needed for wiring use the 

extension skirt provided in the box.

•   Place the HWE-SS in a convenient location near 

the unit to be controlled.

•   Mount the HWE-SS indoors and away from 

excessive heat or cold.

•   Partially unscrew the Display Cover Mounting 

screws.  This allows for its removal.

•   Lifting the Display Section away from the base will 

unplug it from the Base section.

•   Proceed with the power and output wiring 

instructions.

•   Use the screws provided to mount the HWE-SS to the 1900 box or the extension skirt.

•   Mount Display Section back to the Base Section.  Tighten the Display Cover Mounting Screws.

Wiring

Wiring Power Input

The HWE-SS is designed to accept 

ONLY A SINGLE POWER SOURCE

.  It can be wired to either 120VAC using the two Black 

wires or 24VAC using the right most two terminals on the terminal block on bottom of the control.  Heat-Timer recommends the 

installation of a Surge Suppressor and a Power Switch before the Power Line connection for safety and ease of service.

120VAC

•   Attach line voltage, 120VAC, to the two Black wires extending from the back of the HWE-SS.  Remember to use the power line 

from a different source than the equipment being controlled.

 

WARNING

The HWE-SS can accept only one source of power: 120VAC or 24VAC.  

If more than one power source is applied, the unit may be damaged.

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Display Cover Mounting Screws

Display Section

Base Section

Base Mounting Holes

Input Terminals 24VAC optional  power input

N.O.

S.P.S.T. Output Wiring

120VAC Power Wiring

120VAC Power Source

BLACK

BLACK

Boiler

Output Wiring

N.O.

YELLOW

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

24V

AC

Comm

24VAC Power Wiring

Shield

Shield

System T

emp

Outdoor Sensor

Sensor Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Enable/Disable

Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Input Terminals

{

{

{

{

{

{

Temp

er

atur

e S

ensor

30°F - 250°F

Temp

er

atur

e S

ensor

30°F - 250°F

Temp

er

atur

e S

ensor

150°F - 950°F

Ex

ter

nal Enable/D

isable

Shut

do

wn

Pr

essur

e,

 V

acuum,

 and

4 -20mA

24V

A

C P

o

w

er Supply

N.O.

ORANGE

System Pump

Output Wiring

N.O.

VIOLET

DHW Pump

Output Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

DHW Call

Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Setback/Boost

Wiring

Outdoor Temperature (in °F)

70

60

50

40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

200

190

210

220

100

110

12 11

10

9

8

7

6

4

3

2

5

1

1:4 1:3

1:2

1:1.5

1:1.25

1:1

1.25:1

1.5:1

2:1

3:1

4:1

8:1

W

at

er

 T

em

pe

ra

tu

re

 (i

°F

)

Reset Ratio Curves

Reset Ratios are presented as

Outdoor : Water

Summary of Contents for Digi-Span Elite Series HWE-SS

Page 1: ...ydronic Heating Applications The HWE Single Stage HWE SS DIGI SPAN Elite establishes ambient comfort by varying the temperature of the heating system s circulating hot water in response to changes in...

Page 2: ...HW tank to be satisfied quickly Mounting the Controller The HWE SS DIGI Elite is designed to mount on a 1900 4 x4 deep electrical box If additional room is needed for wiring use the extension skirt pr...

Page 3: ...M The Outdoor Sensor must be used when Outdoor Reset is selected as the Control Mode from the Startup menu However in Set Point mode the Outdoor Sensor is optional When connected in that mode it will...

Page 4: ...to the next level Display Unit Options F C Default F SET System Startup Display Unit The HWE SS will offer two different temperature displays If F is selected all temperatures will display in Fahrenh...

Page 5: ...etermine the operating status of the output relays when a sensor reads Short or Open On sensor fault the Set Point will indicate FAULT TGT ON or OFF to indicate the condition of the output and the fau...

Page 6: ...nu Options Click SET Button SYSTEM 148 F TARGET 150 F SET SET SET SET SET S SET SET SET SET SET S Outdoor 48 F Cutoff 65 F Set Point Available when Startup Control Mode Set Point Options From 10 F 23...

Page 7: ...Reset Ratio Max Target Min Target Reset Ratio 10F Offset Min Target 120 F Max Target 170 F Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C...

Page 8: ...or temperature increases 2 F above the Outdoor Cutoff and after the boiler relay has de energized the SYS relay will stay on for a period set by the System Run On This allows the Pump to dissipate the...

Page 9: ...existing system The System and Outdoor Trim values adjust the System Sensor and Outdoor Sensor readings using positive or negative values System Trim 0 F Outdoor Trim 0 F Enable Disable Input The HWE...

Page 10: ...temperature is below the Target water temperature minus the Differential If not wait until the System temperature falls and then the stage LED should come on and the boiler should fire Otherwise remov...

Page 11: ...ED WITH 24VAC T1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor DHW Call Enable Dry Contact Setback Timer Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 1...

Page 12: ...P 6Amp resistive at 120 VAC 60 Hz Control Modes Outdoor Reset Set Point Reset Ratios 12 Standard ranging from 8 1 to 1 4 Outdoor System and one Custom Offset from 40 F 22 C to 40 F 22 C Minimum Water...

Reviews: