Troubleshoot

No Display or LED Lights 

   Check the power to the HWE-SS.  The HWE-SS requires 120VAC power to the Black wires or 

24VAC to the right most terminals.  Turn the power off and back on to restore the display.  If 

unsuccessful, make sure the Display Cover of the control is securely mounted to the Base.

System or Outdoor Reads OPEN or SHORT

   If Open, short the sensor input terminals. The display should read SHORT.   If it doesn’t, the 

HWE-SS may be damaged.

   If Short, remove the wires from the input terminals.  The display should read OPEN.  If it 

doesn’t, the HWE-SS may be damaged.

System or Outdoor Reads an Incorrect Temperature 

   Remove the wires from the input terminals.  The display should change to read OPEN.  If 

it doesn’t, the HWE-SS may be damaged.  Take an ohm reading across the detached sensor 

wires.  The ohm reading should correspond to the Temperature Sensor Chart.  If the difference 

is within 5°F adjust the Trim for the sensor Otherwise, the sensor may be damaged.

 

No Heat - All LEDs are OFF

   Check the outdoor temperature and Outdoor Cutoff readings.  If the outdoor temperature is 

above the Outdoor Cutoff, the HWE-SS will not give heat.   If the display shows 

TSTAT 

OPEN

  then, check the EXT terminals.  If the EXT terminals are not jumped together, the 

HWE-SS will not give heat.

No Heat - All LEDs are ON

   Remove any connections to the Yellow wires for the Heating System Pump.  Test for 

continuity across the pair of Yellow wires.  If the wires are continuous, the HWE-SS is calling 

for the Heating System Pump to run and the problem is not with the HWE-SS.  Check the 

power source and the pump to determine why it is not circulating.

No Heat - System Pump LED ON

   Check that the displayed System water temperature is below the Target water temperature 

minus the Differential.  If not, wait until the System temperature falls, and then the stage 

LED should come on and the boiler should fire

.  Otherwise, remove all connections from the 

Blue pair of wires for boiler control.  Check for continuity across the pair of Blue wires.  If 

the wires are continuous, the HWE-SS is calling for the boiler to run.  Check the boiler to 

determine why it is not firing.

No Heat - Boiler LED ON 

   The HWE-SS is registering a call for DHW.  If the DHW Priority is set to a value other 

than NO, the Heating System Pump will not run during the priority period of a DHW call.  

Generally the DHW will be satisfied before a drop in ambient temperature is noticeable.  If the 

DHW load is large or the boiler can satisfy both loads, change the Priority setting to NO, this 

will allow the Heating System Pump to circulate heating water while the DHW tank is being 

satisfied.

Cold DHW - Boiler LED ON 

   Check if the System water temperature display is approximately 200°F or above Max. Target.  

If it is cooler, remove any connections across the Blue pair of boiler wires.  If the Blue 

wires are continuous, then the HWE-SS is calling for the boiler to run.  Check the boiler to 

determine why it is not firing.  If the System Water temperature is hot, remove any connections 

to the pair of White wires for the DHW pump.  Check for continuity across the pair of White 

wires.  If the wires are continuous, the HWE-SS is calling for the DHW pump to circulate.  

Check the pump to determine why it is not circulating.

Temperature Sensor Chart

TEMPERATURE 

(in Degrees 

°

F)

Value

(in Ohms)

-30

117720

-20

82823

-10

59076

0

42683

10

31215

20

23089

25

19939

30

17264

35

14985

40

13040

45

11374

50

9944

55

8714

60

7653

70

5941

80

4649

90

3667

100

2914

110

2332

120

1879

130

1524

140

1243

150

1021

160

842

170

699

180

583

190

489

200

412

210

349

220

297

230

253

240

217

250

187

Summary of Contents for Digi-Span Elite Series HWE-SS

Page 1: ...ydronic Heating Applications The HWE Single Stage HWE SS DIGI SPAN Elite establishes ambient comfort by varying the temperature of the heating system s circulating hot water in response to changes in...

Page 2: ...HW tank to be satisfied quickly Mounting the Controller The HWE SS DIGI Elite is designed to mount on a 1900 4 x4 deep electrical box If additional room is needed for wiring use the extension skirt pr...

Page 3: ...M The Outdoor Sensor must be used when Outdoor Reset is selected as the Control Mode from the Startup menu However in Set Point mode the Outdoor Sensor is optional When connected in that mode it will...

Page 4: ...to the next level Display Unit Options F C Default F SET System Startup Display Unit The HWE SS will offer two different temperature displays If F is selected all temperatures will display in Fahrenh...

Page 5: ...etermine the operating status of the output relays when a sensor reads Short or Open On sensor fault the Set Point will indicate FAULT TGT ON or OFF to indicate the condition of the output and the fau...

Page 6: ...nu Options Click SET Button SYSTEM 148 F TARGET 150 F SET SET SET SET SET S SET SET SET SET SET S Outdoor 48 F Cutoff 65 F Set Point Available when Startup Control Mode Set Point Options From 10 F 23...

Page 7: ...Reset Ratio Max Target Min Target Reset Ratio 10F Offset Min Target 120 F Max Target 170 F Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C...

Page 8: ...or temperature increases 2 F above the Outdoor Cutoff and after the boiler relay has de energized the SYS relay will stay on for a period set by the System Run On This allows the Pump to dissipate the...

Page 9: ...existing system The System and Outdoor Trim values adjust the System Sensor and Outdoor Sensor readings using positive or negative values System Trim 0 F Outdoor Trim 0 F Enable Disable Input The HWE...

Page 10: ...temperature is below the Target water temperature minus the Differential If not wait until the System temperature falls and then the stage LED should come on and the boiler should fire Otherwise remov...

Page 11: ...ED WITH 24VAC T1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor DHW Call Enable Dry Contact Setback Timer Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 1...

Page 12: ...P 6Amp resistive at 120 VAC 60 Hz Control Modes Outdoor Reset Set Point Reset Ratios 12 Standard ranging from 8 1 to 1 4 Outdoor System and one Custom Offset from 40 F 22 C to 40 F 22 C Minimum Water...

Reviews: