AUXILIARY SETUP
Mode
- Function of the auxiliary thermistor port at
originate from the upper contacts EXT. THM. You can
choose from 3 options: Setpoint, Outdoor , Display.
If you choose Setpoint, the ZON-0600 will display the
following:
•
Thermistor Target
(Off, 35-200°F) this will be a
heating only target for the Auxiliary thermistor input
•
Differential
(2-100) the differential selected will
be split above and below the target. For example
a differential set for 8 and a target set for 120 would
mean that AUX Setpoint will call for heat at 116 and
then shut off at 124.
•
Priority
(Shield, None, 1-7) Priority for this Auxiliary
Thermistor
Shield:
not affected by another zones priority
None:
No priority for this zone, any other zone
with priority will pause this call
1:
60 min priority over zones set to (none, 2-7)
2-7:
Priority over zones that are next in line, for
example 2 has a greater priority than 3, 4, 5, 6,
7 and None
Any zone that is being affected by a priority will have
it’s current call greyed out.
If you choose Outdoor, this will be for an actual
outdoor sensor (OUT-0100) connected to the ZON-
0600 for exact location temperature and used for
WWSD
If you choose Display Only, this will be an external
thermistor to only monitor a temperature of the users
choosing (ie: chiller, cold room, humidor, pool, etc)