H B X Z O N - 0 6 0 0 Z o n e C o n t r o l
V e r s i o n 1 . 0 . 0
Page 9
PUMP SETUP
Pump 1
- The chosen pump type will close the
lower contact at 1-2 (PUMP1) Pump choice options
explained below
Pump 1 Post Purge
– (0 -240 seconds) the amount
of time if necessary for Pump 1 to run after the call
associated with it has been removed
Pump 1 Start Delay
– (0 -240 seconds) the amount of
time if necessary for Pump 1 be delayed to run after
the call associated with it has been activated
Pump 2
- The chosen pump type will close the
lower contact at 1-2 (PUMP2) Pump choice options
explained below
Pump 2 Post Purge
– (0 -240 seconds) the amount
of time if necessary for Pump 2 to run after the call
associated with it has been removed
Pump 2 Start Delay
– (0 -240 seconds) the amount of
time if necessary for Pump 2 be delayed to run after
the call associated with it has been activated
Pump Exercise Time
– (0 -240 hours) the amount of
time that need to pass before the pumps will exercise
the system pumps. (0 = no exercising)
PUMP OPTIONS
Heating
– If there are any heating calls other than a
fancoil heating call the pump contact will close
Cooling
– If there are any cooling calls the pump
contact will close
AUX
– If the Auxiliary thermistor calls this pump
contact will close
APP
– If the virtual app switch is activated this pump
contact will close
Fancoil Heat/Cool
– If there are any heating or
cooling calls from the fancoil the pump contact will
close
Fancoil Heat
– If there is a heating call from the
fancoil the pump contact will close
Fancoil Cool
– If there is a cooling call from the fancoil
the pump contact will close
System
– If there are any heating or cooling calls the
pump contact will close